Changes for page Cresnet Wiring Overview

Last modified by Alexander Mott on 2024/01/05 23:42

From version 20.14
edited by Alexander Mott
on 2024/01/05 21:27
Change comment: (Autosaved)
To version 20.26
edited by Alexander Mott
on 2024/01/05 22:17
Change comment: (Autosaved)

Summary

Details

Page properties
Content
... ... @@ -6,17 +6,22 @@
6 6  
7 7  Each job with Cresnet devices will have at least one Cresnet bus network. Every Cresnet bus network has a single //host// or //primary// device and one or more //client// or //secondary// devices (older materials may refer to hosts as //masters// and clients as //slaves//). Every Cresnet device on a Cresnet bus must be assigned a unique, one-byte hexadecimal Cresnet address. The range of available addresses is determined by the bus host:
8 8  
9 -|=(% style="width: 186px;" %)Host|=(% style="width: 62px;" %)Available Addresses|=Start|=End|=Notes
10 -|(% style="width:186px" %)3-Series or 4-Series processor |(% style="width:62px" %)252^^1^^|03|FE|^^1^^Chief Integrations has experienced significant communications slowdowns on systems with more than 100 devices, and recommends using DIN-CENCN-2(-POE) or additional processors to break up larger networks
11 -|(% style="width:186px" %)DIN-CENCN-2(-POE)|(% style="width:62px" %)(((
9 +(% class="table-condensed" %)
10 +|=(% style="width: 171px;" %)Host|=(% style="width: 96px;" %)Available Addresses|=Start|=End|=Notes
11 +|(% style="width:171px" %)3-Series or
12 +4-Series processors|(% style="width:96px" %)252|03|FE|Chief Integrations has experienced significant communications slowdowns on systems with more than 100 devices, and recommends using DIN-CENCN-2(-POE) or additional processors to break up larger Cresnet bus networks
13 +|(% style="width:171px" %)(((
14 +DIN-CENCN-2 or
15 +DIN-CENCN-2-POE
16 +)))|(% style="width:96px" %)(((
12 12  25 per Net (50 total)
13 13  )))|03|1B|
14 -|(% style="width:186px" %)ZUMNET-JBOX-*|(% style="width:62px" %)32^^1^^|03|22|(((
15 -Zūm Link and Cresnet can be intermingled; more details are available [[here>>doc:SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Troubleshooting.Zūm Wired Wiring Overview.WebHome]]
19 +|(% style="width:171px" %)ZUMNET-JBOX-16A-LV
20 +or ZUMNET-JBOX-DALI|(% style="width:96px" %)32|03|22|(((
21 +ZUMNET-JBOX local controller counts as a device; only 31 additional Zūm Link or Cresnet devices may be connected
16 16  
17 -^^1^^ZUMNET-JBOX local controller counts as a device; only 31 additional Zūm Link or Cresnet devices may be connected
23 +Zūm Link and Cresnet can be intermingled; more details are available [[here>>doc:SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Troubleshooting.Zūm Wired Wiring Overview.WebHome]]
18 18  )))
19 -|(% style="width:186px" %)GLPAC-DIMFLV*|(% style="width:62px" %) |03| |
20 20  
21 21  Power considerations also play a role in determining the number of Cresnet devices which can be supported on a Cresnet bus, however we will not cover them here due to the wide array of variables which impact power calculations and determining whether there is sufficient power for a given device.
22 22  
... ... @@ -31,7 +31,8 @@
31 31  |(% colspan="1" rowspan="2" style="width:307px" %)22 AWG shielded twisted pair|(% style="width:287px" %)White|(% style="width:380px" %)Data +
32 32  |(% style="width:287px" %)Blue|(% style="width:380px" %)Data -
33 33  
34 -= Terminations =
39 +(% class="wikigeneratedid" %)
40 +Terminations
35 35  
36 36  Lorem ipsum dolor sit amet,
37 37