... ... @@ -6,20 +6,17 @@
6 6  
7 7  Each job with Cresnet devices will have at least one Cresnet bus network. Every Cresnet bus network has a single //host// or //primary// device and one or more //client// or //secondary// devices (older materials may refer to hosts as //masters// and clients as //slaves//). Every Cresnet device on a Cresnet bus must be assigned a unique, one-byte hexadecimal Cresnet address. The range of available addresses is determined by the bus host:
8 8  
9 -|=(% style="width: 186px;" %)Host|=(% style="width: 62px;" %)Available Addresses|=Start|=End|=Notes
10 -|(% style="width:186px" %)3-Series or 4-Series processor |(% style="width:62px" %)252^^1^^|03|FE|^^1^^Chief Integrations has experienced significant communications slowdowns on systems with more than 100 devices, and recommends using DIN-CENCN-2(-POE) or additional processors to break up larger networks
11 -|(% style="width:186px" %)DIN-CENCN-2(-POE)|(% style="width:62px" %)(((
12 -25 per Net (50 total)
13 -)))|03|1B|
14 -|(% style="width:186px" %)ZUMNET-JBOX-*|(% style="width:62px" %)32^^1^^|03|22|(((
15 -Zūm Link and Cresnet can be intermingled; more details are available [[here>>doc:SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Troubleshooting.Zūm Wired Wiring Overview.WebHome]]
9 +| | | | |
10 +| | | | |
11 +| | | | |
12 +| | | | |
13 +| | | | |
16 16  
17 -^^1^^ZUMNET-JBOX local controller counts as a device; only 31 additional Zūm Link or Cresnet devices may be connected
18 -)))
19 -|(% style="width:186px" %)GLPAC-DIMFLV*|(% style="width:62px" %) |03| |
20 -
21 21  Power considerations also play a role in determining the number of Cresnet devices which can be supported on a Cresnet bus, however we will not cover them here due to the wide array of variables which impact power calculations and determining whether there is sufficient power for a given device.
22 22  
17 +
18 +Zūm Link wiring is covered in more detail [[here>>doc:SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Troubleshooting.Zūm Wired Wiring Overview.WebHome]].
19 +
23 23  = Cabling =
24 24  
25 25  Cresnet cabling provides the physical infrastructure for communication between Crestron Cresnet devices and consists of a 4-wire, 2-pair cable available directly from Crestron with either plenum and non-plenum rated jackets.