Wiki source code of Legacy Hardware (Cresnet)
Last modified by Craig Lewis on 2024/12/02 14:48
Hide last authors
author | version | line-number | content |
---|---|---|---|
![]() |
20.1 | 1 | Older systems with Legacy Hardware not in SIMPL# library, such as CNLDM-6 or GLPACs, wired to the processor via Cresnet can be added to ShowRunnerCLC™ by created a program for slot 2. |
![]() |
7.1 | 2 | |
![]() |
11.2 | 3 | * Create a SIMPL windows program |
![]() |
20.1 | 4 | * Add the Legacy Hardware or GLPAC-DIMFLV8 (Cresnet) to the appropriate Cresnet IDs |
![]() |
11.6 | 5 | * Define the Level In and Level Out analog signals on the GLPAC Remote Standard Intersystem Communications |
![]() |
7.1 | 6 | |
![]() |
11.2 | 7 | [[image:1660773651340-476.png]] |
![]() |
7.1 | 8 | |
![]() |
11.3 | 9 | * Add a 3 Series TCP/IP Ethernet Intersystem Communications to the appropriate Ethernet ID |
10 | * In Device Settings, set the Default IP Address to 127.0.0.2 (Loop back address) | ||
![]() |
7.1 | 11 | |
![]() |
11.3 | 12 | [[image:image-20220817145415-2.png]] |
13 | |||
14 | * Copy the GLPACs Level In and Level Out signals and paste them to the 3 Series TCP/IP Ethernet Intersystem Communications Analog signals | ||
15 | |||
![]() |
11.1 | 16 | [[image:1660773665229-324.png]] |
![]() |
7.1 | 17 | |
![]() |
14.1 | 18 | * In the showrunner™ config, the lighting controller will be defined with the following settings |
![]() |
11.4 | 19 | ** Controller Type = "3SeriesEisc" |
20 | ** ID and Device Connection Id = IP ID used | ||
21 | ** Properties Value = "127.0.0.2" | ||
![]() |
12.1 | 22 | ** Loads Index for each load = the analog joins defined in the SIMPL program EISC Analog signals |
![]() |
7.1 | 23 | |
24 | [[image:image-20220817145415-4.png]] | ||
![]() |
19.1 | 25 | |
26 | |||
27 | GLPACs on Cresnet directly to the processor can be added to ShowRunnerCLC™, without requiring a second programming slot, by deleting the properties lines and setting the Model to: | ||
28 | |||
29 | "Model": "GLPAC-DIMFLV8_Cresnet", |