1 Older systems with GLPACs wired to the processor via Cresnet can be added to showrunner™ by created a program for slot 2.
2
3 * Create a SIMPL windows program
4 * Add the GLPAC-DIMFLV8 (Cresnet) to the appropriate Cresnet IDs
5 * Define the Level In and Level Out analog signals on the GLPAC Remote Standard Intersystem Communications
6
7 [[image:1660773651340-476.png]]
8
9 * Add a 3 Series TCP/IP Ethernet Intersystem Communications to the appropriate Ethernet ID
10 * In Device Settings, set the Default IP Address to 127.0.0.2 (Loop back address)
11
12 [[image:image-20220817145415-2.png]]
13
14 * Copy the GLPACs Level In and Level Out signals and paste them to the 3 Series TCP/IP Ethernet Intersystem Communications Analog signals
15
16 [[image:1660773665229-324.png]]
17
18 * In the showrunner™ config, the lighting controller will be defined with the following settings
19 ** Controller Type = "3SeriesEisc"
20 ** ID and Device Connection Id = IP ID used
21 ** Properties Value = "127.0.0.2"