1 -Older systems with GLPACs wired to the processor via Cresnet can be added by created a program for slot 2.
2 -
3 -* Create a SIMPL windows program
4 -* Add the GLPAC-DIMFLV8 (Cresnet) to the appropriate Cresnet IDs
5 -* Define the Level In and Level Out analog signals on the GLPAC Remote Standard Intersystem Communications
6 -
7 -[[image:1660773651340-476.png]]
8 -
9 -* Add a 3 Series TCP/IP Ethernet Intersystem Communications to the appropriate Ethernet ID
10 -* In Device Settings, set the Default IP Address to 127.0.0.2 (Loop back address)
11 -
12 -[[image:image-20220817145415-2.png]]
13 -
14 -* Copy the GLPACs Level In and Level Out signals and paste them to the 3 Series TCP/IP Ethernet Intersystem Communications Analog signals
15 -
16 -[[image:1660773665229-324.png]]
17 -
18 -* In the showrunner config, the lighting controller will be defined with the following settings
19 -** Controller Type = "3SeriesEisc"
20 -** ID and Device Connection Id = IP ID used
21 -** Properties Value = "127.0.0.2"
22 -** Loads Index for each load = the analog joins defined in the SIMPL program EISC Analog signals
23 -
24 -
25 -[[image:image-20220817145415-4.png]]