DALI Indexes

Last modified by Alexander Mott on 2026/06/26 22:31

 

Warning

Caveats:

  • DIN-DALI-2 uses Toolbox DALI Commissioning Tool
  • ZUMNET-JBOX-DALI-LEGACY uses Toolbox DALI Commissioning Tool 2.0
  • DIN-DLI can only be commissioned through the Crestron web interface at the device IP Address 

Table of function/value for ControllerBusIndex and  LoadBaseIndex values in the SrConfig for different types of DALI controllers.

Controller ModelControllerBusIndexLoadBaseIndex
ValueMeaningValueMeaning
DIN-DALI-21DALI Loop 1-1Broadcast
[0, 15]Groups 1-16
[100, 163]Short addresses 1 - 64
2DALI Loop 2(Same as ControllerBusIndex 1)(Same as ControllerBusIndex 1)
ZUMMESH-JBOX-DALI1DALI Broadcast

[0, 65534]

Decimal conversion of JBOX address as shown in "rfrcon [netbridge] displaydevices"
2DALI Groups[0, 15]Groups 1-16
3CCT[0, 15]See Zummesh Dynamic White/CCT
ZUMNET-JBOX-DALIApp / Zum Mode1DALI Loop 1[1, 16]Groups 1-16
17
Broadcast
Legacy / CNET Mode1DALI Loop 1-1Broadcast
[0, 15]Groups 1-16
[100, 163]Short addresses 1-64
ZUMNET-DIN-DLIApp / Zum Mode1DALI Loop 1[1, 16]Groups 1-16
17Broadcast
Legacy / CNET ModeNot supported
DIN-DLI1DALI Loop 1-1Broadcast
[0, 15]Groups 1-16
[100, 163]Short addresses 1-64