... ... @@ -14,38 +14,28 @@
14 14  
15 15  Whether connected to the CEN-GWEXER via USB or Ethernet, the process to configure the static IP addresses is the same:
16 16  
17 -* Open Text Console in Toolbox and connect to the CEN-GWEXER
18 -** Note that you may need to manually select "SSL" connection type, as "Auto" might not always redirect
19 -* Run the following commands to configure the CEN-GWEXER's static IP settings (example is for a **10.0.0.0(% style="color:darkgoldenrod" %)/24(%%)** subnet, with a static IP address of (% style="color:blue" %)**10.0.0.12**(%%), an IP-ID of (% style="color:olive" %)**C1**(%%), and a target processor IP address of (% style="color:orange" %)**10.0.0.10**(%%), and a device hostname of (% style="color:purple" %)**GWEXER-L1**(%%))
17 +* Open Text Console in Toolbox and connect **to the DIN-CENCN-2**
18 +* Run the following commands to configure the DIN-CENCN-2's IP settings (example is for a **10.0.0.0(% style="color:darkgoldenrod" %)/24(%%)** subnet, with a CENCN-2 IP address of (% style="color:blue" %)**10.0.0.12**(%%), a CENCN-2 IP-ID of (% style="color:olive" %)**D1**(%%), a processor IP address of (% style="color:orange" %)**10.0.0.10**(%%), and a hostname of (% style="color:purple" %)**CENCN-L1**(%%))
19 +** Disable DHCP: ##dhcp off##
20 20  ** Set IP address: ##ipa 0 (% style="color:blue" %)**10.0.0.12**(%%)##
21 21  ** Set IP subnet mask: ##ipm 0 (% style="color:darkgoldenrod" %)**255.255.255.0**(%%)##
22 22  ** Set default gateway: ##defr 0 **10.0.0.1**##
23 -** Disable DHCP: ##dhcp off##
24 -** Update IP table: ##addm (% style="color:olive" %)**C1**(%%) (% style="color:orange" %)**10.0.0.10**(%%)##
25 -** Set hostname: ##host (% style="color:purple" %)**GWEXER-L1**(%%)##
26 -** Reboot the CEN-GWEXER: ##reboot##
27 -* Repeat for all CEN-GWEXERs on the job
23 +** Update IP table: ##addm (% style="color:olive" %)**D1**(%%) (% style="color:orange" %)**10.0.0.10**(%%)##
24 +** Set hostname: ##host (% style="color:purple" %)**CENCN-L1**(%%)##
25 +** Reboot the DIN-CENCN-2: ##reboot##
26 +* Repeat for all DIN-CENCN-2s on the job
28 28  
29 29  = SSL Setup =
30 30  
31 -Crestron devices that support SSL require the use of a secure connection between the processor and the device. In order to establish this secure connection, the processor must have authentication enabled and there must be a user on the processor with "Connects" group permissions.
30 +Lorem
32 32  
33 -Configure the Connects user on the processor:
32 +~/~/https:~/~/wiki.chiefintegrations.com/SHOWRUNNER%E2%84%A2%20User%20Guide%20%26%20Wiki/SHOWRUNNER%E2%84%A2%20Appendix/SSL%20User%20Configuration/
33 +SSL setup on proc
34 +SSL setup on devices
34 34  
35 -* Ensure the processor has [[its IP configured and authentication enabled>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.Processor Setup.WebHome||anchor="HIPConfiguration"]]
36 -** Verify the processor has authentication enabled by running the command: ##auth## without any parameters
37 -* Create a user by running the following commands, replacing the "username" and "password" with your desired credentials
38 -** ##adduser -N:username -P:password##
39 -** ##addusertogroup -N:username -G:Connects##
40 -* Verify that the user has been created by running the command: ##listusers##
41 -* This process only needs to be performed once per processor on the jobsite
36 +~/~/Need to manually set SSL/TSL method for connecting to gwexer with auth enabled
37 +- also need to update address book if gwexer are added to address book (defaults to ctp)
42 42  
43 -Configure the CS authentication on the CEN-GWEXER:
44 -
45 -* Run the following command, replacing the "username" and "password" with the credentials of the Connects user from the previous step
46 -** ##setcsauth -N:username -P:password##
47 -* Repeat this process for every CEN-GWEXER on the jobsite
48 -
49 49  = RF Channel =
50 50  