Wiki source code of Startup Checklist
Version 6.1 by Alexander Mott on 2023/05/19 16:21
Hide last authors
author | version | line-number | content |
---|---|---|---|
![]() |
5.1 | 1 | This is a broad-strokes checklist for what needs to be completed by a technician for a ShowRunnerCLC™ startup. This checklist is not 100% comprehensive and does not go into detail for each step. |
![]() |
1.1 | 2 | |
![]() |
5.1 | 3 | More detailed specifics and troubleshooting information are available in the [[ShowRunnerCLC™ Startup Guide>>doc:SHOWRUNNER™ Setup Guide.WebHome]]. |
![]() |
1.1 | 4 | |
5 | Startup Checklist: | ||
6 | |||
7 | * Before arriving on-site: | ||
8 | ** Ensure you have the [[required tools and software>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Preparation.Preparing to Go On-Site.WebHome]] | ||
![]() |
3.1 | 9 | ** Ensure the jobsite is meets [[site readiness requirements>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Preparation.Site Readiness Checklist.WebHome]] |
![]() |
1.1 | 10 | * Once on-site: |
![]() |
4.1 | 11 | ** Configure IP settings for networked devices (processors, TSW touch panels, DIN-CENCN-2s, ZUMNET-JBOXs, GLPACs, etc.) |
![]() |
1.1 | 12 | ** Configure clock and timezone for processors |
13 | ** Update firmware for all networked devices | ||
14 | ** If necessary, update firmware for Zūm Net and Cresnet devices | ||
![]() |
5.1 | 15 | ** Load ShowRunnerCLC™ program, license, and configuration file to the processor |
16 | ** Load the ShowRunnerCLC™ UI to any touchscreens | ||
17 | ** Load the ShowRunnerCLC™ expansion program to any GLPACs | ||
![]() |
4.1 | 18 | ** Configure the IP table for any required devices (TSW touch panels, DIN-CENCN-2s, ZUMNET-JBOXs, GLPACs, etc.) |
![]() |
1.1 | 19 | ** Poll Cresnet and verify devices are online in Toolbox |
![]() |
5.1 | 20 | ** Assign Cresnet IDs to devices and verify they are reporting online to ShowRunnerCLC™ |
![]() |
1.1 | 21 | ** Verify load schedule and fixture functionality |
![]() |
6.1 | 22 | *** Toggle each load individually and verify they dim and switch correctly |
![]() |
1.1 | 23 | *** Verify loads are assigned to correct areas |
24 | *** Assign friendly load labels as necessary | ||
![]() |
6.1 | 25 | *** Use the "Verification" checkbox to add a verified timestamp to the load |
![]() |
1.1 | 26 | ** Verify occupancy sensors |
27 | *** Verify correct area assignments | ||
28 | *** Adjust timeouts and sensitivities as necessary | ||
29 | ** Verify keypad functionality | ||
30 | *** Verify correct area assignments | ||
31 | *** Verify correct button layouts and functionality | ||
32 | ** Verify photocell functionality | ||
33 | *** Assign photocells to appropriate lighting zones and enable for required scenes | ||
34 | *** Adjust sensitivity as necessary | ||
35 | ** Verify partition sensor functionality | ||
36 | *** Verify correct area assignments | ||
37 | *** Adjust sensitivity as required | ||
38 | ** Set up any schedules as required per the sequence of operations | ||
![]() |
2.1 | 39 | ** Complete functionality test (QC, make sure each room functions from an end-user perspective) |
40 | ** End-user training |