... ... @@ -1,1 +1,89 @@
1 -SDF
1 +=== SHOWRUNNER™ Startups ===
2 +
3 +The SHOWRUNNER™ program has many features to simplify and streamline Crestron lighting control startups, reducing the amount of technical knowledge required and time spent on-site. Even so, there are a number of different software programs and tools required for a successful SHOWRUNNER™ startup.
4 +
5 +"Required" items are absolutely necessary for startup, while "Recommended" items are not strictly necessary but are good to have.
6 +
7 +==== All Startups ====
8 +
9 +====== Required: ======
10 +
11 +* Windows Laptop (Windows 10 recommended)
12 +** Internet access is required to generate and download the SHOWRUNNER™ license on-site
13 +*** Most cellphones can be used as hot spots for this purpose, but a **dedicated hot spot **is** highly recommended**
14 +** Laptop must have an RJ-45 Ethernet port or a suitable adapter
15 +* Software:
16 +** [[Crestron Toolbox>>https://www.crestron.com/Products/Control-Hardware-Software/Software/Development-Software/SW-TB]] (requires Crestron account; always update to the latest version)
17 +** Web Browser ([[Chrome>>https://www.google.com/chrome/]] or [[Firefox>>https://www.mozilla.org/en-US/firefox/new/]])
18 +** Text Editor ([[Notepad++>>https://notepad-plus-plus.org/downloads/]] or [[VS Code>>https://code.visualstudio.com/]] recommended)
19 +* Downloads:
20 +** Latest [[SHOWRUNNER™ .puf file>>https://files.chiefintegrations.com/index.php/s/WHNzXrrZbB5jC3E]]
21 +** Job-specific SHOWRUNNER™ configuration .json file
22 +** Latest Crestron firmware for installed devices
23 +** Latest [[SHOWRUNNER™ UI .puf file>>https://files.chiefintegrations.com/index.php/s/WHNzXrrZbB5jC3E]] (only required for jobs with touchscreens other than TSW-770)
24 +** SHOWRUNNER™ GLPAC expansion program (only required for jobs with GLPAC controllers)
25 +* Cables:
26 +** Cat5/Cat5e/Cat6 Ethernet cable (multiple cables and multiple lengths are recommended)
27 +** USB-A to USB-B cable (required for most devices; 15' minimum cable length recommended for jobs with GLPACs)
28 +** USB-A to Mini-B cable (required for RMC3 processors only)
29 +** USB-A to Micro-B cable (required for CEN-GWEXER, RMC4 processors, and some other devices)
30 +
31 +====== Recommended: ======
32 +
33 +* Secondary device with internet access (e.g. tablet, second laptop, or cell phone) and remote access software (such as Splashtop or TeamViewer)
34 +** This allows you to "untether" yourself from the lighting network; your laptop stays connected to the lighting network, but is controlled via the remote access software on your second device
35 +* Remotes:
36 +** [[GLS-REMOTE-ODT/OIR>>https://www.crestron.com/Products/Control-Surfaces/Remotes/Lighting-System-Companion-Remotes/GLS-REMOTE-ODT-OIR]] (**required **for jobs with Crestron occupancy sensors)
37 +** [[GLPPA-REMOTE-PROG>>https://www.crestronlighting.com/product/products-control-surfaces-remotes-lighting-system-companion-remotes-glppa-remote?sku=GLPPA-REMOTE-USER&user=67fefcbf860500c91fb9509b97bdfc5a]] (**required **for jobs with GLPPs)
38 +** RC3 Service Remote or [[Smart Remote>>https://www.steinel.de/en/sensors-professional/products/products/sensors/accessories/remote-control-smart-remote-009151.html]] (**required **for jobs with Steinel occupancy sensors)
39 +* Hand Tools:
40 +** Standard Screwdriver (#1 and #2 Phillips, 1/4" and 3/16" Slotted)
41 +** Precision Screwdriver (2.5mm or 3/32" Slotted; for use with Phoenix Connectors)
42 +** Wire Stripper (standard Cresnet cable has both 18 AWG and 22 AWG stranded wires)
43 +** Bright flashlight or laser pointer (for testing photocells)
44 +* Measurement devices:
45 +** Low-voltage Multimeter (continuity testing and low voltage DC measurements are frequently required for troubleshooting)
46 +** Ethernet Network Cable Tester (these are expensive, but useful for verifying Ethernet run lengths and terminations)
47 +* Software:
48 +** Chief Integrations Remote Help Tool (download from [[http:~~/~~/help.chiefintegrations.com/>>http://help.chiefintegrations.com/]]; requires internet access on-site to use)
49 +** FTP client (such as FileZilla or WinSCP)
50 +** SSH client (such as PuTTY)
51 +** File archiver (such as 7-Zip or WinRAR)
52 +** IP scanning utility (such as Advanced IP Scanner)
53 +** DHCP server software (or the [[built-in SHOWRUNNER™ DHCP Server>>doc:SHOWRUNNER™ User Guide & Wiki.Troubleshooting.DHCP Server.WebHome]])
54 +
55 +==== Zūm Wired Startups ====
56 +
57 +Zūm Wired startups require all the items listed under "All Startups" plus the following:
58 +
59 +====== Required: ======
60 +
61 +* Bluetooth-capable Android device with the [[Crestron Zūm app>>https://play.google.com/store/apps/details?id=com.crestron.zum]] installed
62 +** The [[iOS Crestron Zūm app>>https://apps.apple.com/us/app/crestron-z%C5%ABm/id1212507034]] does not currently support Zūm Wired as of June 2022
63 +** Officially Android 5.0 is the minimum requirement, but Chief Integrations recommends Android 10.0 or higher
64 +
65 +====== Recommended: ======
66 +
67 +* Router or third-party DHCP server software (**required **if the [[built-in SHOWRUNNER™ DHCP Server>>doc:SHOWRUNNER™ User Guide & Wiki.Troubleshooting.DHCP Server.WebHome]] is not going to be used)
68 +
69 +==== DMX Startups ====
70 +
71 +DMX startups require all the items listed under "All Startups" plus the following:
72 +
73 +====== Required: ======
74 +
75 +* [[Pharos Designer 2>>https://www.pharoscontrols.com/downloads/software/designer-2/]] (for jobs using Pharos LPC)
76 +* [[Enttec NMU>>https://www.enttec.com/product/controls/dmx-ethernet-lighting-control/nmu/]] (for jobs using Enttec controllers)
77 +
78 +====== Recommended: ======
79 +
80 +* DMX Tester (e.g. a [[Swisson XMT-120A>>https://www.swisson.com/en/products/light-control/dmx-tester/]])
81 +* XLR adapters (3-pin male/female, 5-pin male/female, RJ-45, etc.)
82 +
83 +==== DALI Startups ====
84 +
85 +DALI startups require all the items listed under "All Startups" plus the following:
86 +
87 +====== Required: ======
88 +
89 +* Crestron Toolbox DALI Commissioning Tool (usually included with [[Crestron Toolbox>>https://www.crestron.com/Products/Control-Hardware-Software/Software/Development-Software/SW-TB]] installation)