1 +(% class="box warningmessage" %)
2 +(((
3 +Device addressing using the method described below may be unreliable in newer builds of ShowRunnerCLC™ (v3.011+)
4 +The current recommendation for ShowRunnerCLC™ start-ups is to [[address devices through Toolbox>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Device Addressing.Addressing Devices from Toolbox.WebHome]], using either the Network Device Tree View tool or text console commands
5 +)))
6 +
1 1  {{box cssClass="floatinginfobox" title="**CONTENTS**"}}
2 2  {{toc/}}
3 3  {{/box}}
... ... @@ -8,7 +8,7 @@
8 8  
9 9  Serial numbers should be collected by the electrical contractor during installation and provided to the lighting controls technician prior to startup.
10 10  
11 -= Addressing Devices in ShowRunnerCLC™ =
17 += Device Addressing in the ShowRunnerCLC™ XPanel UI =
12 12  
13 13  Cresnet devices can be addressed from the ShowRunnerCLC™ UI if their serial numbers are known. (Note that Zūm Wired devices cannot currently be addressed from the ShowRunnerCLC™ UI because their serial numbers cannot be directly translated into TSIDs. Instead, they must be [[addressed through Toolbox>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Device Addressing.Addressing Devices from Toolbox.WebHome]].)