Wiki source code of ShowRunnerCLC™ BACnet

Version 27.1 by Mark Kohlmann on 2023/07/21 21:35

Show last authors
1 ShowRunnerCLC™ uses Crestron's BACnet/IP stack and is bound by its licensing and limits. ShowRunnerCLC™'s BACnet feature is licensed, a license from Chief Integrations is required. Integrations of 50 points or less may use the free Crestron BACnet license. More than 50 points require the Crestron paid license and total points are limited by the platform (ZUM-HUB4 processors include a BACnet license, but require a separate license from Crestron to enable ShowRunnerCLC™ installation on the processor). The processor itself consumes a point. BACnet points are assigned during commissioning. A .csv export of the points may be downloaded from the system.
2
3 BACnet Stack Features:
4
5 * BACnet/IP
6 * Configurable BACnet UDP port (options may be limited by processor firmware)
7 * BBMD w/ Foreign Device Registration (Enabled if necessary)
8 * Points can be discovered using traditional BACnet discovery tools
9
10 === Crestron BACnet Stack Details ===
11
12 |=Control System|=Max # of Points
13 |(((
14 * FT-TSC600 (Not Supported by SR)
15 * TPCS-4SM (Not Supported by SR)
16 * TPCS-4SMD (Not Supported by SR)
17 * TSCW-730 (Not Supported by SR)
18 )))|250
19 |(((
20 * DIN-AP3
21 * DIN-AP4
22 * DIN-AP3MEX
23 * MC3 (Not Supported by SR)
24 * MC4
25 * RMC3
26 * RMC4
27 )))|500
28 |(((
29 * CP3
30 * CP4
31 * CP3N
32 * CP4N
33 )))|1000
34 |(((
35 * AV3
36 * AV4
37 * PRO3
38 * PRO4
39 )))|2000
40 |(((
41 * ZUM-HUB4
42 )))|10,000
43
44 [[Crestron PICS Statement>>attach:Crestron_PICS.PDF]]
45
46 === ShowRunnerCLC™ BACnet Points ===
47
48 ==== Area BACnet Points ====
49
50 Provides control/status for a single area within ShowRunnerCLC™. AreaBaseIDs are assigned automatically and maintained. Points are discoverable. Each of the points may be enabled or disabled by area to optimize the integration. This is the default ShowRunnerCLC™ BACnet mode.
51
52 {{{Offset is 1000 in configs generated in ShowRunner 3.30 or newer (V2 definition). Offset is 10000 in older configs or using V1 definition.
53 AreaBaseID = BACnetIndex * Offset}}}
54
55 |=Feature|=Description|=Type|=Point|=Label|=R/W|=Units
56 |Area Scene|Current Scene Active on the Area / Change Scene|MV|AreaBaseID|{AreaId}:{AreaName} Scene|RW|Scene
57 |Occupancy Mode|Current Occupancy Mode for the Area / Change Occupancy Mode|MV|AreaBaseID + 2|{AreaId}:{AreaName} Occupancy Mode|RW|Mode
58 |Occupancy Status|Current Occupancy Status for the Area|BI|AreaBaseID + 1|{AreaId}:{AreaName} Occupied|R|Boolean
59 |Area Intensity|Current Area Average Intensity/Load Level (v3.010 or later)|AV|AreaBaseID + 3|{AreaId}:{AreaName} Intensity|RW|Percentage
60 |Area Power|Current Area Power Consumption in Watts (Requires SR EM License & v3.010 or later)|AI|AreaBaseID + 4|{AreaId}:{AreaName} Power|R|Watts
61 |Loads|Individual Load intensities for each Load in the Area|AV|AreaBaseID + (V2: 100, V1: 1000) + LoadIndex|{AreaId}:{AreaName} Load{LoadId}:{LoadName}|RW|Percentage
62 |Photocell Level|Photocell sensor reading for each Photocell in the Area|AI|AreaBaseID + (V2: 50, V1: 100) + PhotocellIndex|{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}|R|Percentage
63
64 ==== Global BACnet Points ====
65
66 |=Feature|=Description|=Type|=Point|=Label|=R/W|=Units
67 |Master Override|Activates or Deactivates Master Override System Wide|BV|10|Master Override|RW|Boolean
68 |Demand Response|Activates or Deactivates Demand Response|BV|11|Demand Response|RW|Boolean
69 |Normal / After Hours|Changes System State between Normal and After Hours|MV|12|Normal / After Hours|RW|(((
70 1: Normal
71 2: After Hours
72 )))
73 |Device Offline Count|Indicates the number of devices that are offline|AV|20|Device Offline Count|R|Integer
74 |Alarm|Indicates a critical failure, see user interface for more information|BV|21|Alarm|R|Boolean
75
76 === Zūm Floor Hub BACnet Point Emulation ===
77
78 ShowRunnerCLC™ can emulate the Zūm Floor Hubs BACnet points as an alternative to the standard ShowRunnerCLC™ mode. Each point may be enabled/disabled individually by Area.  ShowRunner does not expose every point per area that the Zum Hub does, just the points listed below are exposed.
79
80 Set the following Area properties:
81
82 {{{BACnetIndex: (ID of the Room, this number of multiplied by 2048 to get the BACnet points, starts at 1)
83 BACnetMode: "ZumEmulation"
84
85 AreaBaseID = BACnetIndex * 2048}}}
86
87 |=Feature|=(% style="width: 149px;" %)Type|=(% style="width: 341px;" %)Point|=Label|=Description|=R/W|=Units
88 |Area Scene|(% style="width:149px" %)MV|(% style="width:341px" %)AreaBaseID + 8|{AreaName}>{AreaId}>ActiveScene>BI|View or change the current scene.  Off scene is 17, Scenes 1 through 16 depend on area configuration.|RW|Scene
89 |Occupancy Mode|(% style="width:149px" %)BV|(% style="width:341px" %)AreaBaseID + 6|{AreaName}>{AreaId}>OccupancySensorEnabled>BV|Enable or disable the occupancy sensor.  Enable will activate the last occupancy/vacancy mode.|RW|Boolean
90 |Occupancy Status|(% style="width:149px" %)BI|(% style="width:341px" %)AreaBaseID + 2|{AreaName}>{AreaId}>RoomOccupied>BI|Current room occupancy state|R|Boolean
91 |Online|(% style="width:149px" %)BI|(% style="width:341px" %)AreaBaseID|{AreaName}>{AreaId}>RoomOnline>BI|Current room online state, this is fixed as true.|R|Boolean
92 |On|(% style="width:149px" %)BI|(% style="width:341px" %)AreaBaseID + 1|{AreaName}>{AreaId}>RoomOn>BI|Current room load state.  If any load is on this will be true.|R|Boolean
93
94 {{{