Wiki source code of ShowRunnerCLC™ BACnet

Version 25.1 by Mark Kohlmann on 2023/07/21 21:29

Show last authors
1 ShowRunnerCLC™ uses Crestron's BACnet stack and is bound by its licensing and limits. ShowRunnerCLC™'s BACnet feature is licensed, a license from Chief Integrations is required. Integrations of 50 points or less may use the free Crestron BACnet license. More than 50 points require the Crestron paid license and total points are limited by the platform (ZUM-HUB4 processors include a BACnet license, but require a separate license from Crestron to enable ShowRunnerCLC™ installation on the processor). The processor itself consumes a point. BACnet points are assigned during commissioning. A .csv export of the points may be downloaded from the system.
2
3 BACnet Stack Features:
4
5 * Configurable BACnet port
6 * BBMD w/ Foreign Device Registration (Enabled if necessary)
7 * Points can be discovered using traditional BACnet discovery tools
8
9 === Crestron BACnet Stack Details ===
10
11 |=Control System|=Max # of Points
12 |(((
13 * FT-TSC600 (Not Supported by SR)
14 * TPCS-4SM (Not Supported by SR)
15 * TPCS-4SMD (Not Supported by SR)
16 * TSCW-730 (Not Supported by SR)
17 )))|250
18 |(((
19 * DIN-AP3
20 * DIN-AP4
21 * DIN-AP3MEX
22 * MC3 (Not Supported by SR)
23 * MC4
24 * RMC3
25 * RMC4
26 )))|500
27 |(((
28 * CP3
29 * CP4
30 * CP3N
31 * CP4N
32 )))|1000
33 |(((
34 * AV3
35 * AV4
36 * PRO3
37 * PRO4
38 )))|2000
39 |(((
40 * ZUM-HUB4
41 )))|10,000
42
43 [[Crestron PICS Statement>>attach:Crestron_PICS.PDF]]
44
45 === ShowRunnerCLC™ BACnet Points ===
46
47 ==== Area BACnet Points ====
48
49 Provides control/status for a single area within ShowRunnerCLC™. AreaBaseIDs are assigned automatically and maintained. Points are discoverable. Each of the points may be enabled or disabled by area to optimize the integration. This is the default ShowRunnerCLC™ BACnet mode.
50
51 {{{Offset is 1000 in configs generated in ShowRunner 3.30 or newer (V2 definition). Offset is 10000 in older configs or using V1 definition.
52 AreaBaseID = BACnetIndex * Offset}}}
53
54 |=Feature|=Description|=Type|=Point|=Label|=R/W|=Units
55 |Area Scene|Current Scene Active on the Area|MV|AreaBaseID|{AreaId}:{AreaName} Scene|RW|Scene
56 |Occupancy Mode|Current Occupancy Mode for the Area|MV|AreaBaseID + 2|{AreaId}:{AreaName} Occupancy Mode|RW|Mode
57 |Occupancy Status|Current Occupancy Status for the Area|BI|AreaBaseID + 1|{AreaId}:{AreaName} Occupied|R|Boolean
58 |Area Intensity|Current Area Average Intensity/Load Level (v3.010 or later)|AV|AreaBaseID + 3|{AreaId}:{AreaName} Intensity|RW|Percentage
59 |Area Power|Current Area Power Consumption in Watts (Requires EM License & v3.010 or later)|AI|AreaBaseID + 4|{AreaId}:{AreaName} Power|R|Watts
60 |Loads|Individual Load intensities for each Load in the Area|AV|AreaBaseID + (V2: 100, V1: 1000) + LoadIndex|{AreaId}:{AreaName} Load{LoadId}:{LoadName}|RW|Percentage
61 |Photocell Level|Photocell sensor reading for each Photocell in the Area|AI|AreaBaseID + (V2: 50, V1: 100) + PhotocellIndex|{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}|R|Percentage
62
63 ==== Global BACnet Points ====
64
65 |=Feature|=Description|=Type|=Point|=Label|=R/W|=Units
66 |Master Override|Activates or Deactivates Master Override System Wide|BV|10|Master Override|RW|Boolean
67 |Demand Response|Activates or Deactivates Demand Response|BV|11|Demand Response|RW|Boolean
68 |Normal / After Hours|Changes System State between Normal and After Hours|MV|12|Normal / After Hours|RW|(((
69 1: Normal
70 2: After Hours
71 )))
72 |Device Offline Count|Indicates the number of devices that are offline|AV|20|Device Offline Count|R|Integer
73 |Alarm|Indicates a critical failure, see user interface for more information|BV|21|Alarm|R|Boolean
74
75 === Zūm Floor Hub BACnet Point Emulation ===
76
77 ShowRunnerCLC™ can emulate the Zūm Floor Hubs BACnet points as an alternative to the standard ShowRunnerCLC™ mode. Each point may be enabled/disabled individually by Area.
78
79 Set the following Area properties:
80
81 {{{BACnetIndex: (ID of the Room, this number of multiplied times 2048 to get the BACnet points, start at 1)
82 BACnetMode: "ZumEmulation"}}}
83
84
85 |=Feature|=(% style="width: 149px;" %)Type|=(% style="width: 341px;" %)Point|=Label|=Description|=R/W|=Units
86 |Area Scene|(% style="width:149px" %)MV|(% style="width:341px" %)AreaBaseID + 8|{AreaName}>{AreaId}>ActiveScene>BI|View or change the current scene.  Off scene is 17, Scenes 1 through 16 depend on area configuration.|RW|Scene
87 |Occupancy Mode|(% style="width:149px" %)BV|(% style="width:341px" %)AreaBaseID + 6|{AreaName}>{AreaId}>OccupancySensorEnabled>BV|Enable or disable the occupancy sensor.  Enable will activate the last occupancy/vacancy mode.|RW|Boolean
88 |Occupancy Status|(% style="width:149px" %)BI|(% style="width:341px" %)AreaBaseID + 2|{AreaName}>{AreaId}>RoomOccupied>BI|Current room occupancy state|R|Boolean
89 |Online|(% style="width:149px" %)BI|(% style="width:341px" %)AreaBaseID|{AreaName}>{AreaId}>RoomOnline>BI|Current room online state, this is fixed as true.|R|Boolean
90 |On|(% style="width:149px" %)BI|(% style="width:341px" %)AreaBaseID + 1|{AreaName}>{AreaId}>RoomOn>BI|Current room load state.  If any load is on this will be true.|R|Boolean
91
92 {{{AreaBaseID = BACnetIndex * 2048}}}