Wiki source code of SHOWRUNNER™ BACnet
Version 22.1 by Mark Kohlmann on 2023/03/10 05:10
Show last authors
author | version | line-number | content |
---|---|---|---|
1 | SHOWRUNNER™ uses Crestron's BACnet stack and is bound by its licensing and limits. SHOWRUNNER's BACnet feature is licensed, a license from Chief Integrations is required. Integrations of 50 points or less may use the free Crestron BACnet license. More than 50 points require the Crestron paid license and total points are limited by the platform (ZUM-HUB4 processors include a BACnet license, but require a separate license from Crestron to enable SHOWRUNNER™ installation on the processor). The processor itself consumes a point. BACnet points are assigned during commissioning. A .csv export of the points may be downloaded from the system. | ||
2 | |||
3 | BACnet Stack Features: | ||
4 | |||
5 | * Configurable BACnet port | ||
6 | * BBMD w/ Foreign Device Registration (Enabled if necessary) | ||
7 | * Points can be discovered using traditional BACnet discovery tools | ||
8 | |||
9 | === Crestron BACnet Stack Details === | ||
10 | |||
11 | |=Control System|=Max # of Points | ||
12 | |((( | ||
13 | * FT-TSC600 (Not Supported by SR) | ||
14 | * TPCS-4SM (Not Supported by SR) | ||
15 | * TPCS-4SMD (Not Supported by SR) | ||
16 | * TSCW-730 (Not Supported by SR) | ||
17 | )))|250 | ||
18 | |((( | ||
19 | * DIN-AP3 | ||
20 | * DIN-AP4 | ||
21 | * DIN-AP3MEX | ||
22 | * MC3 (Not Supported by SR) | ||
23 | * MC4 | ||
24 | * RMC3 | ||
25 | * RMC4 | ||
26 | )))|500 | ||
27 | |((( | ||
28 | * CP3 | ||
29 | * CP4 | ||
30 | * CP3N | ||
31 | * CP4N | ||
32 | )))|1000 | ||
33 | |((( | ||
34 | * AV3 | ||
35 | * AV4 | ||
36 | * PRO3 | ||
37 | * PRO4 | ||
38 | )))|2000 | ||
39 | |((( | ||
40 | * ZUM-HUB4 | ||
41 | )))|10,000 | ||
42 | |||
43 | [[Crestron PICS Statement>>attach:Crestron_PICS.PDF]] | ||
44 | |||
45 | === ShowRunner BACnet Points === | ||
46 | |||
47 | ==== Area BACnet Points ==== | ||
48 | |||
49 | Provides control/status for a single area within SHOWRUNNER™. AreaBaseIDs are assigned automatically and maintained. Points are discoverable. Each of the points may be enabled or disabled by area to optimize the integration. This is the default SHOWRUNNER™ BACnet mode. | ||
50 | |||
51 | AreaBaseID = BACnetIndex * 10000 | ||
52 | |||
53 | |=Feature|=Description|=Type|=Point|=Label|=R/W|=Units | ||
54 | |Area Scene|Current Scene Active on the Area|MV|AreaBaseID|{AreaId}:{AreaName} Scene|RW|Scene | ||
55 | |Occupancy Mode|Current Occupancy Mode for the Area|MV|AreaBaseID + 2|{AreaId}:{AreaName} Occupancy Mode|RW|Mode | ||
56 | |Occupancy Status|Current Occupancy Status for the Area|BI|AreaBaseID + 1|{AreaId}:{AreaName} Occupied|R|Boolean | ||
57 | |Area Intensity|Current Area Average Intensity/Load Level (v3.010 or later)|AV|AreaBaseID + 3|{AreaId}:{AreaName} Intensity|RW|Percentage | ||
58 | |Area Power|Current Area Power Consumption in Watts (Requires EM License & v3.010 or later)|AI|AreaBaseID + 4|{AreaId}:{AreaName} Power|R|Watts | ||
59 | |Loads|Individual Load intensities for each Load in the Area|AV|AreaBaseID + 1000 + LoadIndex|{AreaId}:{AreaName} Load{LoadId}:{LoadName}|RW|Percentage | ||
60 | |Photocell Level|Photocell sensor reading for each Photocell in the Area|AI|AreaBaseID + 100 + PhotocellIndex|{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}|R|Percentage | ||
61 | |||
62 | ==== Global BACnet Points ==== | ||
63 | |||
64 | |=Feature|=Description|=Type|=Point|=Label|=R/W|=Units | ||
65 | |Master Override|Activates or Deactivates Master Override System Wide|BV|10|Master Override|RW|Boolean | ||
66 | |Demand Response|Activates or Deactivates Demand Response|BV|11|Demand Response|RW|Boolean | ||
67 | |Normal / After Hours|Changes System State between Normal and After Hours|MV|12|Normal / After Hours|RW|((( | ||
68 | 1: Normal | ||
69 | 2: After Hours | ||
70 | ))) | ||
71 | |Device Offline Count|Indicates the number of devices that are offline|AV|20|Device Offline Count|R|Integer | ||
72 | |Alarm|Indicates a critical failure, see user interface for more information|BV|21|Alarm|R|Boolean | ||
73 | |||
74 | === Zūm Floor Hub BACnet Point Emulation === | ||
75 | |||
76 | SHOWRUNNER™ can emulate the Zūm Floor Hubs BACnet points as an alternative to the standard SHOWRUNNER™ mode. Each point may be enabled/disabled individually by Area. | ||
77 | |||
78 | Set the following Area properties: | ||
79 | |||
80 | {{{BACnetIndex: (ID of the Room, this number of multiplied times 2048 to get the BACnet points, start at 1) | ||
81 | BACnetMode: "ZumEmulation"}}} | ||
82 | |||
83 | |||
84 | |=Feature|=(% style="width: 149px;" %)Type|=(% style="width: 341px;" %)Point|=Label|=Description|=R/W|=Units | ||
85 | |Area Scene|(% style="width:149px" %)MV|(% style="width:341px" %)AreaBaseID + 8|{AreaName}>{AreaId}>ActiveScene>BI|View or change the current scene. Off scene is 17, Scenes 1 through 16 depend on area configuration.|RW|Scene | ||
86 | |Occupancy Mode|(% style="width:149px" %)BV|(% style="width:341px" %)AreaBaseID + 6|{AreaName}>{AreaId}>OccupancySensorEnabled>BV|Enable or disable the occupancy sensor. Enable will activate the last occupancy/vacancy mode.|RW|Boolean | ||
87 | |Occupancy Status|(% style="width:149px" %)BI|(% style="width:341px" %)AreaBaseID + 2|{AreaName}>{AreaId}>RoomOccupied>BI|Current room occupancy state|R|Boolean | ||
88 | |Online|(% style="width:149px" %)BI|(% style="width:341px" %)AreaBaseID|{AreaName}>{AreaId}>RoomOnline>BI|Current room online state, this is fixed as true.|R|Boolean | ||
89 | |On|(% style="width:149px" %)BI|(% style="width:341px" %)AreaBaseID + 1|{AreaName}>{AreaId}>RoomOn>BI|Current room load state. If any load is on this will be true.|R|Boolean | ||
90 | |||
91 | {{{AreaBaseID = BACnetIndex * 2048}}} |