Wiki source code of ShowRunner BACNET

Version 2.1 by Mark Kohlmann on 2020/06/04 18:28

Show last authors
1 ShowRunner uses Crestron's BACNET stack and is bound by its licensing and limits.
2
3 === Crestron BACNET Stack Details ===
4
5 |=Control System|=Max # of Objects
6 |(((
7 * FT-TSC600 (Not Supported by SR)
8 * TPCS-4SM (Not Supported by SR)
9 * TPCS-4SMD (Not Supported by SR)
10 * TSCW-730 (Not Supported by SR)
11 )))|250
12 |(((
13 * DIN-AP3
14 * DIN-AP3MEX
15 * MC3 (Not Supported by SR)
16 * RMC3
17 )))|500
18 |(((
19 * CP3
20 * CP3N
21 )))|1000
22 |(((
23 * AV3
24 * PRO3
25 )))|2000
26
27 [[Crestron PICS Statement>>attach:Crestron_PICS.PDF]]
28
29 === ShowRunner BACNET Points ===
30
31 AreaBaseIDs are assigned automatically and maintained.  Points are discoverable. 
32
33 |=Feature|=Type|=Point|=Label|=R/W|=Units
34 |Area Scene|MV|AreaBaseID|{AreaId}:{AreaName} Scene|RW|Scene
35 |Occupancy Mode|MV|AreaBaseID + 2|{AreaId}:{AreaName} Occupancy Mode|RW|Mode
36 |Occupancy Status|BI|AreaBaseID + 1|{AreaId}:{AreaName} Occupied|R|Boolean
37 |Loads|AV|AreaBaseID + 1000 + LoadIndex|{AreaId}:{AreaName} Load{LoadId}:{LoadName}|RW|Percentage
38 |Photocell Level|AI|AreaBaseID + 100 + PhotocellIndex|{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}|R|Percentage