Wiki source code of ShowRunner BACnet

Version 12.2 by Mark Kohlmann on 2021/07/14 16:25

Show last authors
1 ShowRunner uses Crestron's BACnet stack and is bound by its licensing and limits.  ShowRunner's BACnet feature is licensed.  Integrations of 50 points or less may use the free Crestron BACNET license.  More than 50 points require the Crestron paid license and total points are limited by the platform.  The processor itself consumes a point.  BACnet points are assigned during commissioning.  A csv export of the points may be downloaded from the system.
2
3 === Crestron BACnet Stack Details ===
4
5 |=Control System|=Max # of Objects
6 |(((
7 * FT-TSC600 (Not Supported by SR)
8 * TPCS-4SM (Not Supported by SR)
9 * TPCS-4SMD (Not Supported by SR)
10 * TSCW-730 (Not Supported by SR)
11 )))|250
12 |(((
13 * DIN-AP3
14 * DIN-AP4
15 * DIN-AP3MEX
16 * MC3 (Not Supported by SR)
17 * RMC3
18 * RMC4
19 )))|500
20 |(((
21 * CP3
22 * CP4
23 * CP3N
24 * CP4N
25 )))|1000
26 |(((
27 * AV3
28 * AV4
29 * PRO3
30 * PRO4
31 )))|2000
32
33 [[Crestron PICS Statement>>attach:Crestron_PICS.PDF]]
34
35 === ShowRunner BACNET Points ===
36
37 ==== Area BACNET Points ====
38
39 AreaBaseIDs are assigned automatically and maintained.  Points are discoverable.  Each of the points may be enabled or disabled by area to optimize the integration.  This the default ShowRunner BACnet mode.
40
41 |=Feature|=Description|=Type|=Point|=Label|=R/W|=Units
42 |Area Scene|Current Scene Active on the Area|MV|AreaBaseID|{AreaId}:{AreaName} Scene|RW|Scene
43 |Occupancy Mode|Current Occupancy Mode for the Area|MV|AreaBaseID + 2|{AreaId}:{AreaName} Occupancy Mode|RW|Mode
44 |Occupancy Status|Current Occupancy Status for the Area|BI|AreaBaseID + 1|{AreaId}:{AreaName} Occupied|R|Boolean
45 |Loads|Individual Load intensities for each Load in the Area|AV|AreaBaseID + 1000 + LoadIndex|{AreaId}:{AreaName} Load{LoadId}:{LoadName}|RW|Percentage
46 |Photocell Level|Photocell sensor reading for each Photocell in the Area|AI|AreaBaseID + 100 + PhotocellIndex|{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}|R|Percentage
47
48 ==== Global BACNET Points ====
49
50 |=Feature|=Description|=Type|=Point|=Label|=R/W|=Units
51 |Master Override|Activates or Deactivates Master Override System Wide|BV|10|Master Override|RW|Boolean
52 |Demand Response|Activates or Deactivates Demand Response|BV|11|Demand Response|RW|Boolean
53 |Device Offline Count|Indicates the number of devices that are offline|AV|20|Device Offline Count|R|Integer
54 |Alarm|Indicates a critical failure, see user interface for more information|BV|21|Alarm|R|Boolean
55
56 === Zum Floor Hub BACnet Point Emulation ===
57
58 ShowRunner can emulate the Zum Floor Hubs BACnet points as an alternative to the standard ShowRunner mode.  Each point may be enabled/disabled individually by Area.
59
60 Set the following Area properties:
61
62 {{{BACnetIndex: (ID of the Room, this number of multiplied times 2048 to get the BACnet points, start at 1)
63 BACnetMode: "ZumEmulation"}}}
64
65
66 |=Feature|=(% style="width: 149px;" %)Type|=(% style="width: 341px;" %)Point|=Label|=Description|=R/W|=Units
67 |Area Scene|(% style="width:149px" %)MV|(% style="width:341px" %)AreaBaseID + 8|{AreaName}>{AreaId}>ActiveScene>BI|View or change the current scene.  Off scene is 17, Scenes 1 through 16 depend on area configuration.|RW|Scene
68 |Occupancy Mode|(% style="width:149px" %)BV|(% style="width:341px" %)AreaBaseID + 6|{AreaName}>{AreaId}>OccupancySensorEnabled>BV|Enable or disable the occupancy sensor.  Enable will activate the last occupancy/vacancy mode.|RW|Boolean
69 |Occupancy Status|(% style="width:149px" %)BI|(% style="width:341px" %)AreaBaseID + 2|{AreaName}>{AreaId}>RoomOccupied>BI|Current room occupancy state|R|Boolean
70 |Online|(% style="width:149px" %)BI|(% style="width:341px" %)AreaBaseID|{AreaName}>{AreaId}>RoomOnline>BI|Current room online state, this is fixed as true.|R|Boolean
71 |On|(% style="width:149px" %)BI|(% style="width:341px" %)AreaBaseID + 1|{AreaName}>{AreaId}>RoomOn>BI|Current room load state.  If any load is on this will be true.|R|Boolean
72
73 {{{AreaBaseID = BACnetIndex * 2048}}}