Changes for page ShowRunnerCLC™ BACnet

Last modified by Alexander Mott on 2024/06/14 18:19

From version 7.1
edited by Mark Kohlmann
on 2021/06/16 17:35
Change comment: There is no comment for this version
To version 8.1
edited by Mark Kohlmann
on 2021/06/16 17:40
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -36,16 +36,16 @@
36 36  
37 37  AreaBaseIDs are assigned automatically and maintained.  Points are discoverable.  Each of the points may be enabled or disabled by area to optimize the integration.  This the default ShowRunner BACnet mode.
38 38  
39 -|=Feature|=Type|=Point|=Label|=R/W|=Units
40 -|Area Scene|MV|AreaBaseID|{AreaId}:{AreaName} Scene|RW|Scene
41 -|Occupancy Mode|MV|AreaBaseID + 2|{AreaId}:{AreaName} Occupancy Mode|RW|Mode
42 -|Occupancy Status|BI|AreaBaseID + 1|{AreaId}:{AreaName} Occupied|R|Boolean
43 -|Loads|AV|AreaBaseID + 1000 + LoadIndex|{AreaId}:{AreaName} Load{LoadId}:{LoadName}|RW|Percentage
44 -|Photocell Level|AI|AreaBaseID + 100 + PhotocellIndex|{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}|R|Percentage
39 +|=Feature|=Description|=Type|=Point|=Label|=R/W|=Units
40 +|Area Scene|Current Scene Active on the Area|MV|AreaBaseID|{AreaId}:{AreaName} Scene|RW|Scene
41 +|Occupancy Mode|Current Occupancy Mode for the Area|MV|AreaBaseID + 2|{AreaId}:{AreaName} Occupancy Mode|RW|Mode
42 +|Occupancy Status|Current Occupancy Status for the Area|BI|AreaBaseID + 1|{AreaId}:{AreaName} Occupied|R|Boolean
43 +|Loads|Individual Load intensities for each Load in the Area|AV|AreaBaseID + 1000 + LoadIndex|{AreaId}:{AreaName} Load{LoadId}:{LoadName}|RW|Percentage
44 +|Photocell Level|Photocell sensor reading for each Photocell in the Area|AI|AreaBaseID + 100 + PhotocellIndex|{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}|R|Percentage
45 45  
46 46  === Zum Floor Hub BACnet Point Emulation ===
47 47  
48 -ShowRunner can emulate the Zum Floor Hubs BACnet points.
48 +ShowRunner can emulate the Zum Floor Hubs BACnet points as an alternative to the standard ShowRunner mode.  Each point may be enabled/disabled individually by Area.
49 49  
50 50  Set the following Area properties:
51 51