Changes for page ShowRunnerCLC™ BACnet

Last modified by Alexander Mott on 2024/06/14 18:19

From version 30.1
edited by Alexander Mott
on 2024/06/14 18:06
Change comment: There is no comment for this version
To version 31.1
edited by Alexander Mott
on 2024/06/14 18:19
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,7 +1,9 @@
1 1  ShowRunnerCLC™ uses Crestron's BACnet/IP stack and is bound by its licensing and limitations. Integrations of 50 points or less may use the free Crestron BACnet license, while integrations with more than 50 points require the Crestron paid license (ZUM-HUB4 processors include a BACnet license, but require a separate license from Crestron to enable ShowRunnerCLC™ installation on the processor). The maximum number of BACnet points available is limited per processor and detailed in the table below (note that the processor itself consumes a point).
2 2  
3 -ShowRunnerCLC™'s BACnet feature is licensed, and an additional license from Chief Integrations is required. BACnet points are automatically created and assigned during commissioning, and a .csv export of the points may be downloaded from the system. It is recommended to wait until the end of the project to provide BACnet points to third parties as changes to the ShowRunnerCLC™ program during commissioning may affect the names and IDs for automatically generated BACnet points. ShowRunnerCLC™ version 3.050 and newer includes support for fully custom BACnet points, but it is recommended that custom BACnet points only be used where required by existing jobsite conditions (i.e. when ShowRunnerCLC™ is being used to upgrade an older system with existing BACnet integrations) due to the labor involved with manually creating BACnet points. Automatic point generation is recommended for all ShowRunnerCLC™ deployments on new construction.
3 +ShowRunnerCLC™'s BACnet feature is licensed, and an additional license from Chief Integrations is required. BACnet points are automatically created and assigned during commissioning, and a .csv export of the points may be downloaded from the system. It is recommended to wait until after ShowRunnerCLC™ has been fully started up to provide BACnet points to third parties as changes to the ShowRunnerCLC™ program made during start-up may affect the names and IDs for automatically generated BACnet points.
4 4  
5 +ShowRunnerCLC™ version 3.050 and newer includes support for fully customized BACnet points, but it is labor intensive to implement. Discuss with Chief Integrations if you believe your job requires custom BACnet points (e.g. upgrading a non-ShowRunnerCLC™ system with existing BACnet integrations to ShowRunnerCLC™).
6 +
5 5  BACnet Stack Features:
6 6  
7 7  * BACnet/IP
... ... @@ -8,7 +8,7 @@
8 8  * Configurable BACnet UDP port (options may be limited by processor firmware)
9 9  * BBMD w/ Foreign Device Registration (Enabled if necessary)
10 10  * Points can be discovered using traditional BACnet discovery tools
11 -* ShowRunner version 3.050 and later support custom BACnet points.  Please discuss with Chief Integrations.
13 +* ShowRunnerCLC™ version 3.050 and later support custom BACnet points. Please discuss with Chief Integrations.
12 12  
13 13  === Crestron BACnet Stack Details ===
14 14