Changes for page ShowRunnerCLC™ BACnet

Last modified by Alexander Mott on 2024/06/14 18:19

From version 30.1
edited by Alexander Mott
on 2024/06/14 18:06
Change comment: There is no comment for this version
To version 29.1
edited by Mark Kohlmann
on 2024/03/11 18:53
Change comment: There is no comment for this version

Summary

Details

Page properties
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.alexander\.mott@chiefintegrations\.com
1 +XWiki.mark\.kohlmann@chiefintegrations\.com
Content
... ... @@ -1,7 +1,5 @@
1 -ShowRunnerCLC™ uses Crestron's BACnet/IP stack and is bound by its licensing and limitations. Integrations of 50 points or less may use the free Crestron BACnet license, while integrations with more than 50 points require the Crestron paid license (ZUM-HUB4 processors include a BACnet license, but require a separate license from Crestron to enable ShowRunnerCLC™ installation on the processor). The maximum number of BACnet points available is limited per processor and detailed in the table below (note that the processor itself consumes a point).
1 +ShowRunnerCLC™ uses Crestron's BACnet/IP stack and is bound by its licensing and limits. ShowRunnerCLC™'s BACnet feature is licensed, a license from Chief Integrations is required. Integrations of 50 points or less may use the free Crestron BACnet license. More than 50 points require the Crestron paid license and total points are limited by the platform (ZUM-HUB4 processors include a BACnet license, but require a separate license from Crestron to enable ShowRunnerCLC™ installation on the processor). The processor itself consumes a point. BACnet points are assigned during commissioning. A .csv export of the points may be downloaded from the system.
2 2  
3 -ShowRunnerCLC™'s BACnet feature is licensed, and an additional license from Chief Integrations is required. BACnet points are automatically created and assigned during commissioning, and a .csv export of the points may be downloaded from the system. It is recommended to wait until the end of the project to provide BACnet points to third parties as changes to the ShowRunnerCLC™ program during commissioning may affect the names and IDs for automatically generated BACnet points. ShowRunnerCLC™ version 3.050 and newer includes support for fully custom BACnet points, but it is recommended that custom BACnet points only be used where required by existing jobsite conditions (i.e. when ShowRunnerCLC™ is being used to upgrade an older system with existing BACnet integrations) due to the labor involved with manually creating BACnet points. Automatic point generation is recommended for all ShowRunnerCLC™ deployments on new construction.
4 -
5 5  BACnet Stack Features:
6 6  
7 7  * BACnet/IP