1 -SHOWRUNNER™ BACnet
1 +ShowRunnerCLC™ BACnet
Content
... ... @@ -1,4 +1,4 @@
1 -SHOWRUNNER™ uses Crestron's BACnet stack and is bound by its licensing and limits. SHOWRUNNER's BACnet feature is licensed, a license from Chief Integrations is required. Integrations of 50 points or less may use the free Crestron BACnet license. More than 50 points require the Crestron paid license and total points are limited by the platform (ZUM-HUB4 processors include a BACnet license, but require a separate license from Crestron to enable SHOWRUNNER™ installation on the processor). The processor itself consumes a point. BACnet points are assigned during commissioning. A .csv export of the points may be downloaded from the system.
1 +ShowRunnerCLC™ uses Crestron's BACnet stack and is bound by its licensing and limits. ShowRunnerCLC™'s BACnet feature is licensed, a license from Chief Integrations is required. Integrations of 50 points or less may use the free Crestron BACnet license. More than 50 points require the Crestron paid license and total points are limited by the platform (ZUM-HUB4 processors include a BACnet license, but require a separate license from Crestron to enable ShowRunnerCLC™ installation on the processor). The processor itself consumes a point. BACnet points are assigned during commissioning. A .csv export of the points may be downloaded from the system.
2 2  
3 3  BACnet Stack Features:
4 4  
... ... @@ -42,14 +42,16 @@
42 42  
43 43  [[Crestron PICS Statement>>attach:Crestron_PICS.PDF]]
44 44  
45 -=== ShowRunner BACnet Points ===
45 +=== ShowRunnerCLC™ BACnet Points ===
46 46  
47 47  ==== Area BACnet Points ====
48 48  
49 -Provides control/status for a single area within SHOWRUNNER™. AreaBaseIDs are assigned automatically and maintained. Points are discoverable. Each of the points may be enabled or disabled by area to optimize the integration. This is the default SHOWRUNNER™ BACnet mode.
49 +Provides control/status for a single area within ShowRunnerCLC™. AreaBaseIDs are assigned automatically and maintained. Points are discoverable. Each of the points may be enabled or disabled by area to optimize the integration. This is the default ShowRunnerCLC™ BACnet mode.
50 50  
51 -AreaBaseID = BACnetIndex * 10000
51 +Offset is 1000 in configs generated in ShowRunner 3.30 or newer (V2 definition).  Offset is 10000 in older configs or using V1 definition.
52 52  
53 +AreaBaseID = BACnetIndex * Offset
54 +
53 53  |=Feature|=Description|=Type|=Point|=Label|=R/W|=Units
54 54  |Area Scene|Current Scene Active on the Area|MV|AreaBaseID|{AreaId}:{AreaName} Scene|RW|Scene
55 55  |Occupancy Mode|Current Occupancy Mode for the Area|MV|AreaBaseID + 2|{AreaId}:{AreaName} Occupancy Mode|RW|Mode
... ... @@ -56,8 +56,8 @@
56 56  |Occupancy Status|Current Occupancy Status for the Area|BI|AreaBaseID + 1|{AreaId}:{AreaName} Occupied|R|Boolean
57 57  |Area Intensity|Current Area Average Intensity/Load Level (v3.010 or later)|AV|AreaBaseID + 3|{AreaId}:{AreaName} Intensity|RW|Percentage
58 58  |Area Power|Current Area Power Consumption in Watts (Requires EM License & v3.010 or later)|AI|AreaBaseID + 4|{AreaId}:{AreaName} Power|R|Watts
59 -|Loads|Individual Load intensities for each Load in the Area|AV|AreaBaseID + 1000 + LoadIndex|{AreaId}:{AreaName} Load{LoadId}:{LoadName}|RW|Percentage
60 -|Photocell Level|Photocell sensor reading for each Photocell in the Area|AI|AreaBaseID + 100 + PhotocellIndex|{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}|R|Percentage
61 +|Loads|Individual Load intensities for each Load in the Area|AV|AreaBaseID + (V2: 100, V1: 1000) + LoadIndex|{AreaId}:{AreaName} Load{LoadId}:{LoadName}|RW|Percentage
62 +|Photocell Level|Photocell sensor reading for each Photocell in the Area|AI|AreaBaseID + (V2: 50, V1: 100) + PhotocellIndex|{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}|R|Percentage
61 61  
62 62  ==== Global BACnet Points ====
63 63  
... ... @@ -73,7 +73,7 @@
73 73  
74 74  === Zūm Floor Hub BACnet Point Emulation ===
75 75  
76 -SHOWRUNNER™ can emulate the Zūm Floor Hubs BACnet points as an alternative to the standard SHOWRUNNER™ mode. Each point may be enabled/disabled individually by Area.
78 +ShowRunnerCLC™ can emulate the Zūm Floor Hubs BACnet points as an alternative to the standard ShowRunnerCLC™ mode. Each point may be enabled/disabled individually by Area.
77 77  
78 78  Set the following Area properties:
79 79