Changes for page ShowRunnerCLC™ BACnet
Last modified by Alexander Mott on 2024/06/14 18:19
From version 19.1
edited by Mark Kohlmann
on 2022/06/10 16:17
on 2022/06/10 16:17
Change comment:
There is no comment for this version
To version 20.1
edited by Alexander Mott
on 2022/07/01 18:31
on 2022/07/01 18:31
Change comment:
There is no comment for this version
Summary
-
Page properties (2 modified, 0 added, 0 removed)
Details
- Page properties
-
- Author
-
... ... @@ -1,1 +1,1 @@ 1 -XWiki. mark\.kohlmann@chiefintegrations\.com1 +XWiki.alexander\.mott@chiefintegrations\.com - Content
-
... ... @@ -1,4 +1,4 @@ 1 -S howRunneruses Crestron's BACnet stack and is bound by its licensing and limits.howRunner's BACnet feature is licensed, a license from Chief Integrations is required.1 +SHOWRUNNER™ uses Crestron's BACnet stack and is bound by its licensing and limits. SHOWRUNNER's BACnet feature is licensed, a license from Chief Integrations is required. Integrations of 50 points or less may use the free Crestron BACnet license. More than 50 points require the Crestron paid license and total points are limited by the platform (ZUM-HUB4 processors include a BACnet license, but require a separate license from Crestron to enable SHOWRUNNER™ installation on the processor). The processor itself consumes a point. BACnet points are assigned during commissioning. A .csv export of the points may be downloaded from the system. 2 2 3 3 BACnet Stack Features: 4 4 ... ... @@ -36,6 +36,9 @@ 36 36 * PRO3 37 37 * PRO4 38 38 )))|2000 39 +|((( 40 +* ZUM-HUB4 41 +)))|10,000 39 39 40 40 [[Crestron PICS Statement>>attach:Crestron_PICS.PDF]] 41 41 ... ... @@ -43,7 +43,7 @@ 43 43 44 44 ==== Area BACnet Points ==== 45 45 46 -Provides control/status for a single area within S howRunner.howRunnerBACnet mode.49 +Provides control/status for a single area within SHOWRUNNER™. AreaBaseIDs are assigned automatically and maintained. Points are discoverable. Each of the points may be enabled or disabled by area to optimize the integration. This is the default SHOWRUNNER™ BACnet mode. 47 47 48 48 |=Feature|=Description|=Type|=Point|=Label|=R/W|=Units 49 49 |Area Scene|Current Scene Active on the Area|MV|AreaBaseID|{AreaId}:{AreaName} Scene|RW|Scene ... ... @@ -66,9 +66,9 @@ 66 66 |Device Offline Count|Indicates the number of devices that are offline|AV|20|Device Offline Count|R|Integer 67 67 |Alarm|Indicates a critical failure, see user interface for more information|BV|21|Alarm|R|Boolean 68 68 69 -=== Z um Floor Hub BACnet Point Emulation ===72 +=== Zūm Floor Hub BACnet Point Emulation === 70 70 71 -S howRunnercan emulate the Zum Floor Hubs BACnet points as an alternative to the standard ShowRunnermode.74 +SHOWRUNNER™ can emulate the Zūm Floor Hubs BACnet points as an alternative to the standard SHOWRUNNER™ mode. Each point may be enabled/disabled individually by Area. 72 72 73 73 Set the following Area properties: 74 74