Changes for page ShowRunnerCLC™ BACnet

Last modified by Alexander Mott on 2024/06/14 18:19

From version 18.1
edited by Mark Kohlmann
on 2022/06/10 16:12
Change comment: There is no comment for this version
To version 13.1
edited by Mark Kohlmann
on 2021/10/12 20:56
Change comment: There is no comment for this version

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -SHOWRUNNER™ Integrations Guide.Integration Options.WebHome
1 +SHOWRUNNER™ User Guide & Wiki.SHOWRUNNER™ Appendix.Integration Options.WebHome
Content
... ... @@ -1,7 +1,5 @@
1 -ShowRunner uses Crestron's BACnet stack and is bound by its licensing and limits.  ShowRunner's BACnet feature is licensed.  Integrations of 50 points or less may use the free Crestron BACnet license.  More than 50 points require the Crestron paid license and total points are limited by the platform.  The processor itself consumes a point.  BACnet points are assigned during commissioning.  A csv export of the points may be downloaded from the system.
1 +ShowRunner uses Crestron's BACnet stack and is bound by its licensing and limits.  ShowRunner's BACnet feature is licensed.  Integrations of 50 points or less may use the free Crestron BACNET license.  More than 50 points require the Crestron paid license and total points are limited by the platform.  The processor itself consumes a point.  BACnet points are assigned during commissioning.  A csv export of the points may be downloaded from the system.
2 2  
3 -Crestron's BACnet stack supports configurable ports and a BBMD.
4 -
5 5  === Crestron BACnet Stack Details ===
6 6  
7 7  |=Control System|=Max # of Points
... ... @@ -35,11 +35,11 @@
35 35  
36 36  [[Crestron PICS Statement>>attach:Crestron_PICS.PDF]]
37 37  
38 -=== ShowRunner BACnet Points ===
36 +=== ShowRunner BACNET Points ===
39 39  
40 -==== Area BACnet Points ====
38 +==== Area BACNET Points ====
41 41  
42 -AreaBaseIDs are assigned automatically and maintained.  Points are discoverable.  Each of the points may be enabled or disabled by area to optimize the integration.  This is the default ShowRunner BACnet mode.
40 +AreaBaseIDs are assigned automatically and maintained.  Points are discoverable.  Each of the points may be enabled or disabled by area to optimize the integration.  This the default ShowRunner BACnet mode.
43 43  
44 44  |=Feature|=Description|=Type|=Point|=Label|=R/W|=Units
45 45  |Area Scene|Current Scene Active on the Area|MV|AreaBaseID|{AreaId}:{AreaName} Scene|RW|Scene
... ... @@ -50,15 +50,11 @@
50 50  |Loads|Individual Load intensities for each Load in the Area|AV|AreaBaseID + 1000 + LoadIndex|{AreaId}:{AreaName} Load{LoadId}:{LoadName}|RW|Percentage
51 51  |Photocell Level|Photocell sensor reading for each Photocell in the Area|AI|AreaBaseID + 100 + PhotocellIndex|{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}|R|Percentage
52 52  
53 -==== Global BACnet Points ====
51 +==== Global BACNET Points ====
54 54  
55 55  |=Feature|=Description|=Type|=Point|=Label|=R/W|=Units
56 56  |Master Override|Activates or Deactivates Master Override System Wide|BV|10|Master Override|RW|Boolean
57 57  |Demand Response|Activates or Deactivates Demand Response|BV|11|Demand Response|RW|Boolean
58 -|Normal / After Hours|Changes System State between Normal and After Hours|MV|12|Normal / After Hours|RW|(((
59 -1: Normal
60 -2: After Hours
61 -)))
62 62  |Device Offline Count|Indicates the number of devices that are offline|AV|20|Device Offline Count|R|Integer
63 63  |Alarm|Indicates a critical failure, see user interface for more information|BV|21|Alarm|R|Boolean
64 64