Changes for page ShowRunnerCLC™ BACnet

Last modified by Alexander Mott on 2024/06/14 18:19

From version 15.1
edited by Mark Kohlmann
on 2022/03/14 21:28
Change comment: There is no comment for this version
To version 7.1
edited by Mark Kohlmann
on 2021/06/16 17:35
Change comment: There is no comment for this version

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -SHOWRUNNER™ Integrations Guide.Integration Options.WebHome
1 +SHOWRUNNER™ User Guide & Wiki.SHOWRUNNER™ Appendix.WebHome
Content
... ... @@ -1,8 +1,8 @@
1 -ShowRunner uses Crestron's BACnet stack and is bound by its licensing and limits.  ShowRunner's BACnet feature is licensed.  Integrations of 50 points or less may use the free Crestron BACNET license.  More than 50 points require the Crestron paid license and total points are limited by the platform.  The processor itself consumes a point.  BACnet points are assigned during commissioning.  A csv export of the points may be downloaded from the system.
1 +ShowRunner uses Crestron's BACnet stack and is bound by its licensing and limits.  ShowRunner's BACnet feature is licensed.  Integrations of 50 points or less may use the free Crestron BACNET license.  More than 50 points require the Crestron paid license and total points are limited by the platform.  The processor itself consumes a point.
2 2  
3 3  === Crestron BACnet Stack Details ===
4 4  
5 -|=Control System|=Max # of Points
5 +|=Control System|=Max # of Objects
6 6  |(((
7 7  * FT-TSC600 (Not Supported by SR)
8 8  * TPCS-4SM (Not Supported by SR)
... ... @@ -14,7 +14,6 @@
14 14  * DIN-AP4
15 15  * DIN-AP3MEX
16 16  * MC3 (Not Supported by SR)
17 -* MC4
18 18  * RMC3
19 19  * RMC4
20 20  )))|500
... ... @@ -35,30 +35,18 @@
35 35  
36 36  === ShowRunner BACNET Points ===
37 37  
38 -==== Area BACNET Points ====
37 +AreaBaseIDs are assigned automatically and maintained.  Points are discoverable.  Each of the points may be enabled or disabled by area to optimize the integration.  This the default ShowRunner BACnet mode.
39 39  
40 -AreaBaseIDs are assigned automatically and maintained.  Points are discoverable.  Each of the points may be enabled or disabled by area to optimize the integration.  This is the default ShowRunner BACnet mode.
39 +|=Feature|=Type|=Point|=Label|=R/W|=Units
40 +|Area Scene|MV|AreaBaseID|{AreaId}:{AreaName} Scene|RW|Scene
41 +|Occupancy Mode|MV|AreaBaseID + 2|{AreaId}:{AreaName} Occupancy Mode|RW|Mode
42 +|Occupancy Status|BI|AreaBaseID + 1|{AreaId}:{AreaName} Occupied|R|Boolean
43 +|Loads|AV|AreaBaseID + 1000 + LoadIndex|{AreaId}:{AreaName} Load{LoadId}:{LoadName}|RW|Percentage
44 +|Photocell Level|AI|AreaBaseID + 100 + PhotocellIndex|{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}|R|Percentage
41 41  
42 -|=Feature|=Description|=Type|=Point|=Label|=R/W|=Units
43 -|Area Scene|Current Scene Active on the Area|MV|AreaBaseID|{AreaId}:{AreaName} Scene|RW|Scene
44 -|Occupancy Mode|Current Occupancy Mode for the Area|MV|AreaBaseID + 2|{AreaId}:{AreaName} Occupancy Mode|RW|Mode
45 -|Occupancy Status|Current Occupancy Status for the Area|BI|AreaBaseID + 1|{AreaId}:{AreaName} Occupied|R|Boolean
46 -|Area Intensity|Current Area Average Intensity/Load Level (v3.010 or later)|AV|AreaBaseID + 3|{AreaId}:{AreaName} Intensity|RW|Percentage
47 -|Area Power|Current Area Power Consumption in Watts (Requires EM License & v3.010 or later)|AI|AreaBaseID + 4|{AreaId}:{AreaName} Power|R|Watts
48 -|Loads|Individual Load intensities for each Load in the Area|AV|AreaBaseID + 1000 + LoadIndex|{AreaId}:{AreaName} Load{LoadId}:{LoadName}|RW|Percentage
49 -|Photocell Level|Photocell sensor reading for each Photocell in the Area|AI|AreaBaseID + 100 + PhotocellIndex|{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}|R|Percentage
50 -
51 -==== Global BACNET Points ====
52 -
53 -|=Feature|=Description|=Type|=Point|=Label|=R/W|=Units
54 -|Master Override|Activates or Deactivates Master Override System Wide|BV|10|Master Override|RW|Boolean
55 -|Demand Response|Activates or Deactivates Demand Response|BV|11|Demand Response|RW|Boolean
56 -|Device Offline Count|Indicates the number of devices that are offline|AV|20|Device Offline Count|R|Integer
57 -|Alarm|Indicates a critical failure, see user interface for more information|BV|21|Alarm|R|Boolean
58 -
59 59  === Zum Floor Hub BACnet Point Emulation ===
60 60  
61 -ShowRunner can emulate the Zum Floor Hubs BACnet points as an alternative to the standard ShowRunner mode.  Each point may be enabled/disabled individually by Area.
48 +ShowRunner can emulate the Zum Floor Hubs BACnet points.
62 62  
63 63  Set the following Area properties:
64 64