Changes for page ShowRunnerCLC™ BACnet

Last modified by Alexander Mott on 2024/06/14 18:19

From version 1.1
edited by Mark Kohlmann
on 2020/06/04 17:39
Change comment: Uploaded new attachment "Crestron_PICS.PDF", version {1}
To version 5.1
edited by Mark Kohlmann
on 2020/10/30 22:05
Change comment: There is no comment for this version

Summary

Details

Page properties
Title
... ... @@ -1,0 +1,1 @@
1 +ShowRunner BACnet
Parent
... ... @@ -1,0 +1,1 @@
1 +SHOWRUNNER™ User Guide & Wiki.SHOWRUNNER™ Appendix.WebHome
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.MarkKohlmann
1 +XWiki.mark\.kohlmann@chiefintegrations\.com
Content
... ... @@ -1,0 +1,57 @@
1 +ShowRunner uses Crestron's BACnet stack and is bound by its licensing and limits.  ShowRunner's BACnet feature is licensed.  Integrations of 50 points or less may use the free Crestron BACNET license.  More than 50 points require the Crestron license and total points are limited by the platform.
2 +
3 +=== Crestron BACnet Stack Details ===
4 +
5 +|=Control System|=Max # of Objects
6 +|(((
7 +* FT-TSC600 (Not Supported by SR)
8 +* TPCS-4SM (Not Supported by SR)
9 +* TPCS-4SMD (Not Supported by SR)
10 +* TSCW-730 (Not Supported by SR)
11 +)))|250
12 +|(((
13 +* DIN-AP3
14 +* DIN-AP3MEX
15 +* MC3 (Not Supported by SR)
16 +* RMC3
17 +)))|500
18 +|(((
19 +* CP3
20 +* CP3N
21 +)))|1000
22 +|(((
23 +* AV3
24 +* PRO3
25 +)))|2000
26 +
27 +[[Crestron PICS Statement>>attach:Crestron_PICS.PDF]]
28 +
29 +=== ShowRunner BACNET Points ===
30 +
31 +AreaBaseIDs are assigned automatically and maintained.  Points are discoverable.  Each of the points may be enabled or disabled by area to optimize the integration.
32 +
33 +|=Feature|=Type|=Point|=Label|=R/W|=Units
34 +|Area Scene|MV|AreaBaseID|{AreaId}:{AreaName} Scene|RW|Scene
35 +|Occupancy Mode|MV|AreaBaseID + 2|{AreaId}:{AreaName} Occupancy Mode|RW|Mode
36 +|Occupancy Status|BI|AreaBaseID + 1|{AreaId}:{AreaName} Occupied|R|Boolean
37 +|Loads|AV|AreaBaseID + 1000 + LoadIndex|{AreaId}:{AreaName} Load{LoadId}:{LoadName}|RW|Percentage
38 +|Photocell Level|AI|AreaBaseID + 100 + PhotocellIndex|{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}|R|Percentage
39 +
40 +=== Zum Floor Hub BACnet Point Emulation ===
41 +
42 +ShowRunner can emulate the Zum Floor Hubs BACnet points.
43 +
44 +Set the following Area properties:
45 +
46 +{{{BACnetIndex: (ID of the Room, this number of multiplied times 2048 to get the BACnet points, start at 1)
47 +BACnetMode: "ZumEmulation"}}}
48 +
49 +
50 +|=Feature|=(% style="width: 149px;" %)Type|=(% style="width: 341px;" %)Point|=Label|=Description|=R/W|=Units
51 +|Area Scene|(% style="width:149px" %)MV|(% style="width:341px" %)AreaBaseID + 8|{AreaName}>{AreaId}>ActiveScene>BI|View or change the current scene.  Off scene is 17, Scenes 1 through 16 depend on area configuration.|RW|Scene
52 +|Occupancy Mode|(% style="width:149px" %)BV|(% style="width:341px" %)AreaBaseID + 6|{AreaName}>{AreaId}>OccupancySensorEnabled>BV|Enable or disable the occupancy sensor.  Enable will activate the last occupancy/vacancy mode.|RW|Boolean
53 +|Occupancy Status|(% style="width:149px" %)BI|(% style="width:341px" %)AreaBaseID + 2|{AreaName}>{AreaId}>RoomOccupied>BI|Current room occupancy state|R|Boolean
54 +|Online|(% style="width:149px" %)BI|(% style="width:341px" %)AreaBaseID|{AreaName}>{AreaId}>RoomOnline>BI|Current room online state, this is fixed as true.|R|Boolean
55 +|On|(% style="width:149px" %)BI|(% style="width:341px" %)AreaBaseID + 1|{AreaName}>{AreaId}>RoomOn>BI|Current room load state.  If any load is on this will be true.|R|Boolean
56 +
57 +{{{AreaBaseID = BACnetIndex * 2048}}}