128 128  (% class="wikigeneratedid" %)
129 129  Mecho Shade's MechoNet Network Interface (MNI) allows integrating control of MechoNet hardware with third-party systems such as ShowRunnerCLC™ through a variety of different means. ShowRunnerCLC™ currently only supports using RS-232 or contact closure integrations: reach out to Chief Integrations for pricing if RS-485 or IR integrations are required.
130 130  
131 -(% class="wikigeneratedid" id="HMNIRS-232" %)
132 -RS-232 or contact closure integration supported (reach out to Chief Integrations if RS-485 integration is required; contact closure integration is only available if Mecho wall switch ports are not being used)
133 -
134 134  === Hardware Requirements ===
135 135  
136 -Specific hardware requirements depend on which method of integration is required:
133 +Refer to [[the above table>>doc:SHOWRUNNER™ Integrations Guide.Integration Options.Shades Integrations.WebHome||anchor="HCommonIntegrationMethods"]] for general hardware compatibility. MNI-specific details are below depending on how shades are being integrated:
137 137  
135 +* For RS-232 integration:
136 +** One RS-232 port on the ShowRunnerCLC™ system must be available for each MNI to be integrated
137 +** Depending on how the MechoNet system is configured, it is possible that multiple MNI can be controlled through the RS-232 connection at a single MNI
138 +* For contact closure integration:
139 +** Contact closure integration utilizes the MNI switch input ports: **it is not possible to use contact closure integration if Mecho switches are installed to control the shades**
140 +** Two relays must be available for each Mecho motor to be controlled (it is possible to control multiple Mecho motors from a single relay pair provided that the MNI switch ports are wired in parallel)
141 +* For RS-485 or IR integration, reach out to Chief Integrations
138 138  
139 139  === Information Requirements ===
140 140  
... ... @@ -142,8 +142,10 @@
142 142  
143 143  * **(Required) **Whether integration is being done through RS-232 or contact closures
144 144  * For RS-232 integration:
149 +**
145 145  * For contact closure integration:
146 -** (Required) the same information as specified in the [[contact closure section above>>doc:SHOWRUNNER™ Integrations Guide.Integration Options.Shades Integrations.WebHome||anchor="HInformationRequirements"]] f
151 +** **(Required)** all information specified in the [[general contact closure>>doc:SHOWRUNNER™ Integrations Guide.Integration Options.Shades Integrations.WebHome||anchor="HInformationRequirements"]] section above
152 +** **(Required)** which shades are controlled by which motor output on each MNI, and which Crestron relays those outputs are expected to correspond to
147 147  
148 148  == Mecho SolarTrac4 ==
149 149