Changes for page Shades Integrations

Last modified by Alexander Mott on 2024/06/17 18:07

From version 7.1
edited by Alexander Mott
on 2024/06/14 22:31
Change comment: There is no comment for this version
To version 5.3
edited by Alexander Mott
on 2024/06/14 22:06
Change comment: (Autosaved)

Summary

Details

Page properties
Content
... ... @@ -2,7 +2,7 @@
2 2  (((
3 3  (% class="box infomessage" %)
4 4  (((
5 -Note: this page is currently under construction, check back later for updates
5 +Note: page is under construction, check back later for updates
6 6  )))
7 7  
8 8  (% class="col-xs-12 col-sm-8" %)
... ... @@ -74,7 +74,7 @@
74 74  * TCP/IP communication (including HTTP/HTTPS, TelNet, etc.)
75 75  ** Standard [[Ethernet wiring limitations>>doc:SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Troubleshooting.Ethernet Wiring Overview.WebHome]] apply
76 76  
77 -Below is a non-exhaustive table showing which pieces of Crestron hardware have interfaces for each kind of integration (all processors are capable of TCP/IP integration provided the network has been configured correctly):
77 +Below is a non-exhaustive table showing which pieces of Crestron hardware have interfaces for each kind of integration:
78 78  
79 79  |=Hardware|=Relay Outputs|=RS-485 Serial Ports|=RS-232 Serial Ports
80 80  |C2N-IO|2|✖|1
... ... @@ -92,28 +92,17 @@
92 92  
93 93  == Contact Closure (Relays) ==
94 94  
95 -ShowRunnerCLC™ can use output relays on Crestron hardware to control shades provided that the shades controller is capable of accepting a contact closure input for third-party control of the shades. All contact closure shade integrations are assumed to use two relays per shade zone with standard outputs as follows:
95 +ShowRunnerCLC™ can use output relays on Crestron hardware to control shades provided that the shades controller is capable of accepting a contact closure input for third-party control of the shades.
96 96  
97 -* Open: close relay 1
98 -* Close: close relay 2
99 -* Stop: close both relays simultaneously
100 -
101 -Shade motors must be wired accordingly by the EC or the shades contractor (Chief Integrations technicians do not touch wiring). If the shades interfaces cannot be controlled this way, contact Chief Integrations to see about possibilities for support for shade controls using either a single relay or three or more relays per zone.
102 -
103 103  === Hardware Requirements ===
104 104  
105 -* Crestron devices with output relays must be specified (refer to [[the above table>>doc:SHOWRUNNER™ Integrations Guide.Integration Options.Shades Integrations.WebHome||anchor="HCommonIntegrationMethods"]] for commonly specified hardware)
106 -* Two Crestron output relays must be available for each zone of shades to be controlled
107 -** Depending on the shade hardware and the job requirements, it may be possible to combine multiple shades to be controlled together onto a single pair of Crestron relays
108 -* It is recommended that shade interfaces be installed as close as possible to the Crestron relays controlling them to prevent issues from voltage drop or EMF interference in the wiring between the relay and the shade interface
99 +* Two relays must be available for each shade controller
100 +* It is recommended that shade interfaces be installed as close as possible to the Crestron relays controlling them to prevent issues from voltage drop or EMF in the wiring between the relay and the shade interface
109 109  
110 110  === Information Requirements ===
111 111  
112 -* **(Required)** Quantity and location of Crestron devices to be used for contact closure shade control
113 -* **(Required)** Quantity and locations of shade zones to be controlled
114 -* **(Required)** Information associating each shade zone with a relay pair
115 -** If C2N-IO or other in-field relay modules are being used, then we must know which shade(s) in which room(s) are controlled by each C2N-IO
116 -** If a processor or other in-panel modules are being used, then we must know which shade(s) in which room(s) are controlled by relays 1 & 2, which are controlled by relays 3 & 4, etc. for each module
104 +* (Required) Quantity and location of Crestron devices to be used for contact closure shade control
105 +* (Required) Quantity and location of shades to be controlled
117 117  
118 118  == Draper IntelliFlex I/O A\V Gateway ==
119 119  
... ... @@ -133,7 +133,7 @@
133 133  == MechoNet Network Interface (MNI) ==
134 134  
135 135  (% class="wikigeneratedid" id="HMNIRS-232" %)
136 -RS-232 or contact closure integration supported (reach out to Chief Integrations if RS-485 integration is required; contact closure integration is only available if Mecho wall switch ports are not being used)
125 +Only RS-232 integration supported (contact closure available if Mecho wall switch ports are not used)
137 137  
138 138  == Mecho SolarTrac4 ==
139 139