Changes for page Shades Integrations

Last modified by Alexander Mott on 2024/06/17 18:07

From version 2.3
edited by Alexander Mott
on 2024/06/14 21:12
Change comment: (Autosaved)
To version 5.2
edited by Alexander Mott
on 2024/06/14 22:01
Change comment: (Autosaved)

Summary

Details

Page properties
Content
... ... @@ -17,16 +17,45 @@
17 17  
18 18  ShowRunnerCLC™ provides native support for most Crestron shade controllers as well as integration with shades controlled from third-party Crestron processors via Ethernet Inter-Systems Communication (EISC). If integration with a Crestron shades controller or system that is not detailed below is required, reach out to Chief Integrations directly to see about potentially adding support to ShowRunnerCLC™.
19 19  
20 -== C2N-SDC(-DC) ==
20 +== Supported Hardware ==
21 21  
22 -== CSA-PWS10S-HUB-ENET ==
22 +ShowRunnerCLC™ includes support for the following Crestron shade controllers:
23 23  
24 -== DIN-2MC2 ==
24 +* C2N-SDC and C2N-SDC-DC
25 +* CSC Series Controllers (discontinued)
26 +* CSA-PWS10S-HUB-ENET (controlling QMT-series motors)
27 +* DIN-2MC2
28 +* Ethernet Inter-System Communications (Crestron-to-Crestron)
25 25  
26 -== Ethernet Inter-Systems Communication (EISC) ==
30 +For any integrations over Ethernet, the lighting network must be configured such that the lighting control processor running ShowRunnerCLC™ can communicate with all required hardware.
27 27  
28 -= Third-Party Shade Controllers =
32 +== Information Required ==
29 29  
34 +In order to fully define shades in the ShowRunnerCLC™ configuration, the following information must be provided by the Agent. Incomplete information will result in incomplete hardware definitions in the shipped ShowRunnerCLC™ configuration.
35 +
36 +Non-EISC shades:
37 +
38 +* **(Required)** Quantity of shade controllers
39 +* **(Required)** Quantity and location of each shade motor to be controlled
40 +** For all controllers, we must know which shade motor (i.e. window and room) is connected to each output
41 +** For systems with multiple CSA-PSW10S-HUB-ENET, we must know which HUB is the Cresnet primary
42 +
43 +EISC shades:
44 +
45 +* **(Required)** Type of EISC integration (TCP or UDP)
46 +* **(Required)** IP Address and IP-ID of non-ShowRunnerCLC™ processor
47 +* **(Required) **Joins to be used for shade control and feedback (see table below; not all features are required for all integrations)
48 +
49 +(% style="width:632px" %)
50 +|=Join|=(% style="width: 344px;" %)Description|=(% style="width: 6px;" %)Type|=(% style="width: 101px;" %)Direction
51 +|JoinOpen|(% style="width:344px" %)Sends a digital pulse when open is triggered|(% style="width:6px" %)Digital|(% style="width:101px" %)To 3rd Party
52 +|JoinClose|(% style="width:344px" %)Sends a digital pulse when close is triggered|(% style="width:6px" %)Digital|(% style="width:101px" %)To 3rd Party
53 +|JoinStop|(% style="width:344px" %)Sends a digital pulse when stop is triggered|(% style="width:6px" %)Digital|(% style="width:101px" %)To 3rd Party
54 +|JoinPosition|(% style="width:344px" %)Sends an analog value when the position is changed (0-65535 = 0-100%)|(% style="width:6px" %)Analog|(% style="width:101px" %)To 3rd Party
55 +|JoinPositionFeedback|(% style="width:344px" %)Receives an analog value for the current shade position (0-65535 = 0-100%)|(% style="width:6px" %)Analog|(% style="width:101px" %)From 3rd Party
56 +
57 += Third-Party Shade Integrations =
58 +
30 30  ShowRunnerCLC™ supports integrating with a wide range of common shade control manufacturers, but this integration is not included in basic ShowRunnerCLC™ orders and requires the [[SR-SDN>>doc:showrunner™ Order Guide.showrunner™ Additional Features.Shades.SR-SDN.WebHome]] additional feature. If integration with a shades manufacturer or system that is not detailed below is required, reach out to Chief Integrations directly to see about potentially adding support to ShowRunnerCLC™.
31 31  
32 32  == Common Integration Methods ==
... ... @@ -45,22 +45,30 @@
45 45  * TCP/IP communication (including HTTP/HTTPS, TelNet, etc.)
46 46  ** Standard [[Ethernet wiring limitations>>doc:SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Troubleshooting.Ethernet Wiring Overview.WebHome]] apply
47 47  
48 -Below is a table showing which pieces of Crestron hardware have interfaces for each kind of integration:
77 +Below is a non-exhaustive table showing which pieces of Crestron hardware have interfaces for each kind of integration:
49 49  
50 50  |=Hardware|=Relay Outputs|=RS-485 Serial Ports|=RS-232 Serial Ports
51 51  |C2N-IO|2|✖|1
81 +|INET-IOEX-RYIO|2|✖|✖
52 52  |CP3N / CP4N|8|1*|3*
53 53  |DIN-IO8|8|✖|✖
54 54  |DIN-AP3 / DIN-AP4|4|2*|2*
55 55  |(((
56 56  GLPAC-DIMFLV4-PM / GLPAC-DIMFLV8-PM
87 +(PM models only)
57 57  )))|4|✖|✖
58 58  |RMC3 / RMC4|2|1*|1*
59 -|ZUM-HUB4| | |
90 +|ZUM-HUB4|||
60 60  |(% colspan="4" %)* Some serial ports are dual-purpose and can be //either// RS-485 //or// RS-232; other serial ports are //only// RS-232
61 61  
62 62  == Contact Closure (Relays) ==
63 63  
95 +ShowRunnerCLC™ can use output relays on Crestron hardware to control shades provided that the shades controller is capable of accepting a contact closure input
96 +
97 +=== Supported Hardware ===
98 +
99 +=== Information Requirements ===
100 +
64 64  == Draper IntelliFlex I/O A\V Gateway ==
65 65  
66 66  (% class="wikigeneratedid" %)
... ... @@ -76,10 +76,10 @@
76 76  (% class="wikigeneratedid" id="HQuantumRS-232" %)
77 77  RS-232 or TelNet integration supported
78 78  
79 -== MechoNet Interface (MNI) ==
116 +== MechoNet Network Interface (MNI) ==
80 80  
81 81  (% class="wikigeneratedid" id="HMNIRS-232" %)
82 -Only RS-232 integration supported
119 +Only RS-232 integration supported (contact closure available if Mecho wall switch ports are not used)
83 83  
84 84  == Mecho SolarTrac4 ==
85 85