Changes for page Shades Integrations

Last modified by Alexander Mott on 2024/06/17 18:07

From version 16.1
edited by Alexander Mott
on 2024/06/17 18:07
Change comment: There is no comment for this version
To version 8.1
edited by Alexander Mott
on 2024/06/14 23:13
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,13 +7,9 @@
1 -(% class="box warningmessage" %)
2 -(((
3 -**NOTICE: Always check manufacturer product specifications to verify features and compatibility prior to ordering hardware.** 
4 -While we at Chief Integrations strive to provide accurate and complete information, we cannot guarantee that the information provided here will always be 100% accurate and up-to-date.
5 -)))
6 -
7 7  (% class="col-xs-12 col-sm-8" %)
8 8  (((
9 9  Controlling shades from ShowRunnerCLC™ is a paid feature that can be purchased either with the initial [[ShowRunnerCLC™ order>>doc:showrunner™ Order Guide.showrunner™ Additional Features.Shades.WebHome]] or added after-the-fact as an additional charge. When shades control or integration is ordered for ShowRunnerCLC™, it is vital to ensure that the BOM includes any required hardware is also ordered.
10 10  
5 +While we strive to always provide accurate and complete information, bear in mind that we cannot guarantee that any information provided here will be 100% accurate and up-to-date: always check manufacturer product specifications to verify features and compatibility prior to ordering hardware.
6 +
11 11  = Crestron Shade Controllers =
12 12  
13 13  Crestron shades are included in all ShowRunnerCLC™ orders, but hardware will not be fully defined in the configuration unless the required information is provided prior to configuration shipment. If the required information cannot be provided with the original order, it is recommended to order [[SR-SDC>>doc:showrunner™ Order Guide.showrunner™ Additional Features.Shades.SR-SDC.WebHome]] for additional after-order Crestron shades support.
... ... @@ -40,7 +40,7 @@
40 40  EISC shades:
41 41  
42 42  * **(Required)** Type of EISC integration (TCP or UDP)
43 -* **(Required)** IP Address and IP-ID for the non-ShowRunnerCLC™ processor
39 +* **(Required)** IP Address and IP-ID of non-ShowRunnerCLC™ processor
44 44  * **(Required) **Joins to be used for shade control and feedback (see table below; not all features are required for all integrations)
45 45  
46 46  (% style="width:632px" %)
... ... @@ -60,21 +60,15 @@
60 60  While most third-party shade controllers have proprietary integration protocols specific to each manufacturer and model, there are common industry standards which dictate the wiring and hardware requirements to integrate third-party shades with ShowRunnerCLC™:
61 61  
62 62  * Contact closure (Relays)
63 -** Shades are controlled by ShowRunnerCLC™-controlled contact closure relays
64 -** Typically requires two relays per shade motor or collection of shade motors to be controlled (one relay for "open" and one relay for "close")
65 -** No standard specified length limitation for wiring (individual shade manufacturers may specify cabling and distance limitations)
59 +** No standard specified length limitation (individual shade manufacturers may specify cabling and distance limitations)
66 66  ** Relay control can be susceptible to voltage drop or EMF interference: it is highly recommended to locate the Crestron controlled relay as close as possible to the shades interface being controlled
67 67  * Serial RS-232
68 -** Shades are controlled by a ShowRunnerCLC™-controlled serial communications port through wiring which adheres to RS-232 specification
69 69  ** 50' maximum distance per specification
70 70  ** Point-to-point communication mandates a one-to-one relationship of Crestron RS-232 interfaces to shade RS-232 interfaces (i.e. there must be one RS-232 port available on the Crestron system for every RS-232 shade interface; depending on the shades design, a single shades interface may control many shades so it may be possible that a system with many shades only requires one RS-232 connection to the Crestron system)
71 71  * Serial RS-485
72 -** Shades are controlled by a ShowRunnerCLC™-controlled serial communications port through wiring which adheres to RS-485 specification
73 73  ** 4000' maximum distance per specification (individual shades manufacturers may specify lower cabling and distance limitations, and real-world conditions may reduce the actual maximum distance that can be achieved before system performance is noticeably impacted)
74 74  ** Multidrop communications allows for daisy-chain and star wiring topologies, up to 32 devices per Crestron RS-485 interface (shades manufacturers may specify lower device counts)
75 75  * TCP/IP communication (including HTTP/HTTPS, TelNet, etc.)
76 -** Shades are controlled by ShowRunnerCLC™ through the LAN port using standard Ethernet cabling and TCP/IP (% style="display:none" %) (%%)communications protocols(% style="display:none" %)  
77 -** ShowRunnerCLC™ processor and shades interface must be able to communicate with each other, typically requiring either that the shades interface and lighting processor are  located on the same LAN/VLAN or that the building IT be involved to ensure that communications are possible between the two systems
78 78  ** Standard [[Ethernet wiring limitations>>doc:SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Troubleshooting.Ethernet Wiring Overview.WebHome]] apply
79 79  
80 80  Below is a non-exhaustive table showing which pieces of Crestron hardware have interfaces for each kind of integration (all processors are capable of TCP/IP integration provided the network has been configured correctly):
... ... @@ -123,42 +123,37 @@
123 123  (% class="wikigeneratedid" %)
124 124  RS-232 or RS-485 integration supported
125 125  
126 -== Lutron Sivoia QS (Quantum) ==
116 +== Lutron Sivoia QS ==
127 127  
128 128  (% class="wikigeneratedid" id="HSivoiaQSRS-232" %)
129 129  RS-232 or TelNet integration supported
130 130  
121 +== Lutron Quantum ==
122 +
123 +(% class="wikigeneratedid" id="HQuantumRS-232" %)
124 +RS-232 or TelNet integration supported
125 +
131 131  == MechoNet Network Interface (MNI) ==
132 132  
133 133  (% class="wikigeneratedid" %)
134 134  Mecho Shade's MechoNet Network Interface (MNI) allows integrating control of MechoNet hardware with third-party systems such as ShowRunnerCLC™ through a variety of different means. ShowRunnerCLC™ currently only supports using RS-232 or contact closure integrations: reach out to Chief Integrations for pricing if RS-485 or IR integrations are required.
135 135  
131 +(% class="wikigeneratedid" id="HMNIRS-232" %)
132 +RS-232 or contact closure integration supported (reach out to Chief Integrations if RS-485 integration is required; contact closure integration is only available if Mecho wall switch ports are not being used)
133 +
136 136  === Hardware Requirements ===
137 137  
138 -Refer to [[the above table>>doc:SHOWRUNNER™ Integrations Guide.Integration Options.Shades Integrations.WebHome||anchor="HCommonIntegrationMethods"]] for general hardware compatibility. MNI-specific details are below depending on how shades are being integrated:
136 +Specific hardware requirements depend on which method of integration is required:
139 139  
140 -* For RS-232 integration:
141 -** One RS-232 port on the ShowRunnerCLC™ system must be available for each MNI to be integrated
142 -** Depending on how the MechoNet system is designed, it may be possible to control many shades through a single RS-232 integration provided that any additional MNI and controlled MechoNet hardware are networked together and configured on the MechoNet side
143 -* For contact closure integration:
144 -** Contact closure integration utilizes the MNI switch input ports: **it is not possible to use contact closure integration if Mecho switches are installed to control the shades**
145 -** Two relays must be available for each Mecho motor to be controlled (it is possible to control multiple Mecho motors from a single relay pair provided that the MNI switch ports are wired in parallel)
146 -* For RS-485 or IR integration, reach out to Chief Integrations for potentially adding these integrations
147 147  
148 148  === Information Requirements ===
149 149  
150 150  Specific information requirements depend on which method of integration is required:
151 151  
152 -* **(Required)** Specify whether integration is being done through RS-232 or contact closures
143 +* **(Required) **Whether integration is being done through RS-232 or contact closures
153 153  * For RS-232 integration:
154 -** **(Required) **MechoNet devices must be addressed so that it is possible to control them per the SOO using their Zone, Group, Node addresses
155 -*** MechoNet devices are assigned three-part Zone, Group, Node addresses similar to an IPv4 address with 3 parts instead of 4
156 -*** e.g. a ZGN address of 128.151.253 represents a device in zone 128, group 151, and node 253
157 -** **(Required) **ZGN addresses must be provided for all shades to be controlled
158 -** **(Required)** location for each shade to be controlled so that they can be assigned to the correct areas in ShowRunnerCLC™
159 159  * For contact closure integration:
160 -** **(Required)** all information specified in the [[general contact closure>>doc:SHOWRUNNER™ Integrations Guide.Integration Options.Shades Integrations.WebHome||anchor="HInformationRequirements"]] section above
161 -** **(Required)** indicate which Crestron relays correspond to each motor on each MNI, and which shades are controlled by each motor
146 +** (Required) the same information as specified in the [[contact closure section above>>doc:SHOWRUNNER™ Integrations Guide.Integration Options.Shades Integrations.WebHome||anchor="HContactClosure%28Relays%29"]] f
162 162  
163 163  == Mecho SolarTrac4 ==
164 164