... ... @@ -1,11 +5,9 @@
1 -(% class="box warningmessage" %)
2 -(((
3 -While we strive to always provide accurate and complete information, bear in mind that we cannot guarantee that any information provided here will be 100% accurate and up-to-date: always check manufacturer product specifications to verify features and compatibility prior to ordering hardware.
4 -)))
5 5  (% class="col-xs-12 col-sm-8" %)
6 6  (((
7 7  Controlling shades from ShowRunnerCLC™ is a paid feature that can be purchased either with the initial [[ShowRunnerCLC™ order>>doc:showrunner™ Order Guide.showrunner™ Additional Features.Shades.WebHome]] or added after-the-fact as an additional charge. When shades control or integration is ordered for ShowRunnerCLC™, it is vital to ensure that the BOM includes any required hardware is also ordered.
8 8  
5 +While we strive to always provide accurate and complete information, bear in mind that we cannot guarantee that any information provided here will be 100% accurate and up-to-date: always check manufacturer product specifications to verify features and compatibility prior to ordering hardware.
6 +
9 9  = Crestron Shade Controllers =
10 10  
11 11  Crestron shades are included in all ShowRunnerCLC™ orders, but hardware will not be fully defined in the configuration unless the required information is provided prior to configuration shipment. If the required information cannot be provided with the original order, it is recommended to order [[SR-SDC>>doc:showrunner™ Order Guide.showrunner™ Additional Features.Shades.SR-SDC.WebHome]] for additional after-order Crestron shades support.
... ... @@ -38,7 +38,7 @@
38 38  EISC shades:
39 39  
40 40  * **(Required)** Type of EISC integration (TCP or UDP)
41 -* **(Required)** IP Address and IP-ID for the non-ShowRunnerCLC™ processor
39 +* **(Required)** IP Address and IP-ID of non-ShowRunnerCLC™ processor
42 42  * **(Required) **Joins to be used for shade control and feedback (see table below; not all features are required for all integrations)
43 43  
44 44  (% style="width:632px" %)
... ... @@ -58,21 +58,15 @@
58 58  While most third-party shade controllers have proprietary integration protocols specific to each manufacturer and model, there are common industry standards which dictate the wiring and hardware requirements to integrate third-party shades with ShowRunnerCLC™:
59 59  
60 60  * Contact closure (Relays)
61 -** Shades are controlled by ShowRunnerCLC™-controlled contact closure relays
62 -** Typically requires two relays per shade motor or collection of shade motors to be controlled (one relay for "open" and one relay for "close")
63 -** No standard specified length limitation for wiring (individual shade manufacturers may specify cabling and distance limitations)
59 +** No standard specified length limitation (individual shade manufacturers may specify cabling and distance limitations)
64 64  ** Relay control can be susceptible to voltage drop or EMF interference: it is highly recommended to locate the Crestron controlled relay as close as possible to the shades interface being controlled
65 65  * Serial RS-232
66 -** Shades are controlled by a ShowRunnerCLC™-controlled serial communications port through wiring which adheres to RS-232 specification
67 67  ** 50' maximum distance per specification
68 68  ** Point-to-point communication mandates a one-to-one relationship of Crestron RS-232 interfaces to shade RS-232 interfaces (i.e. there must be one RS-232 port available on the Crestron system for every RS-232 shade interface; depending on the shades design, a single shades interface may control many shades so it may be possible that a system with many shades only requires one RS-232 connection to the Crestron system)
69 69  * Serial RS-485
70 -** Shades are controlled by a ShowRunnerCLC™-controlled serial communications port through wiring which adheres to RS-485 specification
71 71  ** 4000' maximum distance per specification (individual shades manufacturers may specify lower cabling and distance limitations, and real-world conditions may reduce the actual maximum distance that can be achieved before system performance is noticeably impacted)
72 72  ** Multidrop communications allows for daisy-chain and star wiring topologies, up to 32 devices per Crestron RS-485 interface (shades manufacturers may specify lower device counts)
73 73  * TCP/IP communication (including HTTP/HTTPS, TelNet, etc.)
74 -** Shades are controlled by ShowRunnerCLC™ through the LAN port using standard Ethernet cabling and TCP/IP (% style="display:none" %) (%%)communications protocols(% style="display:none" %)  
75 -** ShowRunnerCLC™ processor and shades interface must be able to communicate with each other, typically requiring either that the shades interface and lighting processor are  located on the same LAN/VLAN or that the building IT be involved to ensure that communications are possible between the two systems
76 76  ** Standard [[Ethernet wiring limitations>>doc:SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Troubleshooting.Ethernet Wiring Overview.WebHome]] apply
77 77  
78 78  Below is a non-exhaustive table showing which pieces of Crestron hardware have interfaces for each kind of integration (all processors are capable of TCP/IP integration provided the network has been configured correctly):
... ... @@ -158,7 +158,7 @@
158 158  *** MechoNet devices are assigned three-part Zone, Group, Node addresses similar to an IPv4 address with 3 parts instead of 4
159 159  *** e.g. a ZGN address of 128.151.253 represents a device in zone 128, group 151, and node 253
160 160  ** **(Required) **ZGN addresses must be provided for all shades to be controlled
161 -** **(Required)** location for each shade to be controlled so that they can be assigned to the correct areas in ShowRunnerCLC™
153 +** (Required) locat
162 162  * For contact closure integration:
163 163  ** **(Required)** all information specified in the [[general contact closure>>doc:SHOWRUNNER™ Integrations Guide.Integration Options.Shades Integrations.WebHome||anchor="HInformationRequirements"]] section above
164 164  ** **(Required)** indicate which Crestron relays correspond to each motor on each MNI, and which shades are controlled by each motor