Last modified by Mark Kohlmann on 2024/11/19 23:23

From version 21.1
edited by Mark Kohlmann
on 2024/08/22 20:58
Change comment: There is no comment for this version
To version 23.1
edited by Mark Kohlmann
on 2024/11/19 23:22
Change comment: There is no comment for this version

Summary

Details

Page properties
Title
... ... @@ -1,1 +1,1 @@
1 -Ethernet Intersystem Communications Export (Crestron)
1 +Ethernet Intersystem Communications xport (Crestron)
Content
... ... @@ -2,15 +2,20 @@
2 2  (((
3 3  Note: For AV Integration EISCs, any changes to load or shade/shade group quantity, ExtendedSceneExport, or ExtendedLoadExport settings will require a regeneration of the EISC and will result in signal changes. When importing a new or updated RSD file to the A/V program, ensure the appropriate options are selected:
4 4  
5 -* "Disconnect signal from Etherenet ISC symbol in program."
5 +* "Disconnect signal from Ethernet ISC symbol in program."
6 6  * "Change Locally: Update signal name in EISC ISC symbol only."
7 7  
8 8  [[image:MicrosoftTeams-image.png||queryString="width=394&height=413" height="413" width="394"]]
9 9  )))
10 10  
11 +(% class="box errormessage" %)
12 +(((
13 +Chief Integrations does not recommend using the 3-Series TCP/IP Ethernet Intersystem Communications (ThreeSeriesEisc).  We have reports of this type locking up SIMPL Windows programs attempting to integrate with showrunner™ on 4-series processors.  3-Series EISCs try to negotiate who is the server and who is the client.  Use the table below for recommendations on EISC types.
14 +)))
15 +
11 11  ShowRunnerCLC™ provides Ethernet Intersystem Communications interfaces for integration with 3rd party Crestron systems.
12 12  
13 -* EISCs may be Classic, 3-Series, or Server/Client (VC-4) types
18 +* EISCs may be Classic, 3-Series, or Server/Client types
14 14  * EISCs can have their IP-ID and IP Address of the remote changed at run-time without a program restart
15 15  * An RSD file will be built for each EISC and a URL will be displayed on the touchscreen to retrieve it
16 16  * There are 2 EISC modes and only one mode is supported on an EISC definition, multiple EISCs may be defined