... ... @@ -115,32 +115,32 @@
115 115  )))|N/A
116 116  |BACNET Settings Scope
117 117  (What Points are Exposed)|Per Area|Per Area|(((
118 -SHOWRUNNER™: Per Area
118 +ShowRunnerCLC™: Per Area
119 119  Floor Hub: Global
120 120  )))|Global|N/A
121 -|BACNET Points Supported|Depends on Crestron License and Hardware|Depends on Crestron License and Hardware|SHOWRUNNER™: Depends on Crestron License and Hardware
121 +|BACNET Points Supported|Depends on Crestron License and Hardware|Depends on Crestron License and Hardware|ShowRunnerCLC™: Depends on Crestron License and Hardware
122 122  Floor Hub: 1000|1000|N/A
123 123  |Crestron Fusion|Y|Y|(((
124 -SHOWRUNNER™: Y
124 +ShowRunnerCLC™: Y
125 125  Floor Hub: N
126 126  )))|N|N/A
127 -|Export to Zūm Floor Hub|Y, Licensed|Y, Licensed|SHOWRUNNER™: Y, Licensed|N/A|N/A
128 -|GLPAC|Y|Y|SHOWRUNNER™: Y
129 -Floor Hub: Via SHOWRUNNER™|N|N/A
127 +|Export to Zūm Floor Hub|Y, Licensed|Y, Licensed|ShowRunnerCLC™: Y, Licensed|N/A|N/A
128 +|GLPAC|Y|Y|ShowRunnerCLC™: Y
129 +Floor Hub: Via ShowRunnerCLC™|N|N/A
130 130  |System to System Link|Y|Y|(((
131 -SHOWRUNNER™: Y
131 +ShowRunnerCLC™: Y
132 132  Floor Hub: N
133 133  )))|N|N/A
134 134  |Minimum NETBRIDGE Firmware|v1.13.0020 (PUF Zum MESHNET v1.07.16)|v1.010|N/A|See Crestron|See Crestron
135 135  |Minimum Gateway Firmware|v1.4469.00022|N/A|N/A|See Crestron|See Crestron
136 -|Minimum SHOWRUNNER™ Version|2.198|2.198|N/A|N/A|N/A
136 +|Minimum ShowRunnerCLC™ Version|2.198|2.198|N/A|N/A|N/A
137 137  
138 138  {{{* Zūm Setup App works as long as the NETBRIDGE is physically near the iOS/Android device running the Zūm Setup App.
139 -** Fade time is automatically applied if scene is set longer than 1 second. Must be triggered from SHOWRUNNER™, cannot be triggered from Zūm keypad with current firmware (as of April 2020).
139 +** Fade time is automatically applied if scene is set longer than 1 second. Must be triggered from ShowRunnerCLC™, cannot be triggered from Zūm keypad with current firmware (as of April 2020).
140 140  *** Zūm wireless does not support direct coupling of fade times and the behavior is different internally within the dimmer versus other Crestron products. Raise/Lower level accuracy is not guaranteed. For best performance when settings scenes, set the slider manually which will send exact levels to the dimmer.
141 -**** Zūm wireless scenes cannot presently be read on command. Scenes should be created and saved from SHOWRUNNER™ directly. Saved scenes are stored directly on the Zūm wireless dimmer and in ShowRunner. ShowRunner will query the NETBRIDGE after scene recall and attempt to build scene information but operations are done one at a time.
142 -***** Zūm wireless real time load status is not available.  Any changes to loads performed using the raise/lower functions in room will not be propagated back to ShowRunner.  Levels set by the daylight sensor with daylighting enabled will not be reported by ShowRunner. Sometimes delays in sending load levels occur. Feature is primarily intended for remotely setting scenes.
143 -****** Zūm wireless does not support a true override but ShowRunner will disable keypads and occupancy sensors and recall scene 15. The occupancy sensor enabled state and current scene will be remembered and recalled when leaving occupancy mode.
141 +**** Zūm wireless scenes cannot presently be read on command. Scenes should be created and saved from ShowRunnerCLC™ directly. Saved scenes are stored directly on the Zūm wireless dimmer and in ShowRunnerCLC™. ShowRunner will query the NETBRIDGE after scene recall and attempt to build scene information but operations are done one at a time.
142 +***** Zūm wireless real time load status is not available.  Any changes to loads performed using the raise/lower functions in room will not be propagated back to ShowRunner.  Levels set by the daylight sensor with daylighting enabled will not be reported by v. Sometimes delays in sending load levels occur. Feature is primarily intended for remotely setting scenes.
143 +****** Zūm wireless does not support a true override but ShowRunnerCLC™ will disable keypads and occupancy sensors and recall scene 15. The occupancy sensor enabled state and current scene will be remembered and recalled when leaving occupancy mode.
144 144  }}}
145 145  
146 146  {{id name="caveats"/}}
... ... @@ -148,17 +148,17 @@
148 148  ==== Caveats ====
149 149  
150 150  * Consult Chief Integrations to verify sequence of operations if there are any concerns.  Zum wireless is not a direct replacement for Crestron wired and infiNET EX wireless products.
151 -* Zum Wireless has an internal rate limit that will shutdown communication if a number of commands are received in a short period of time.  This can be seen when repeatedly pressing buttons on a keypad as well as repeatedly triggering actions from ShowRunner.
151 +* Zum Wireless has an internal rate limit that will shutdown communication if a number of commands are received in a short period of time.  This can be seen when repeatedly pressing buttons on a keypad as well as repeatedly triggering actions from ShowRunnerCLC™.
152 152  * Raise/Lower operations from ShowRunner cannot track directly with the load response, see ~*~** above.  ShowRunner will poll the NETBRIDGE for current levels ~~3 seconds after the raise/lower is stopped to obtain current load levels.
153 153  * Lower operations can turn the load off.  The load will not come on with a raise.  This is a firmware behavior in the Zum hardware.
154 154  * Wireless control presents some additional latency possibilities.  Commands required to provide full functionality (load control/raise/lower) with Zum wireless are more intensive than traditional Crestron hardware and may impact performance under heavy load.  Local operation of the Zum wireless room is not impacted.
155 -* Real time load status is not available.  Any changes to loads performed using the raise/lower functions in room will not be propagated back to ShowRunner.  Levels set by the daylight sensor with daylighting enabled will not be reported by ShowRunner.
156 -* Keypad behaviors cannot be modified in ShowRunner.  Some modifications are permitted within the Zum app.  Custom keypads can be implemented using the AVBRIDGE connected to the system via a serial port, Zum requires an AV specific keypad for this purpose; or via export buttons ([[Details>>doc:SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Advanced Tools.Zummesh Keypad Custom Programming.WebHome]]).
155 +* Real time load status is not available.  Any changes to loads performed using the raise/lower functions in room will not be propagated back to ShowRunnerCLC™.  Levels set by the daylight sensor with daylighting enabled will not be reported by ShowRunnerCLC™.
156 +* Keypad behaviors cannot be modified in ShowRunnerCLC™.  Some modifications are permitted within the Zum app.  Custom keypads can be implemented using the AVBRIDGE connected to the system via a serial port, Zum requires an AV specific keypad for this purpose; or via export buttons ([[Details>>doc:SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Advanced Tools.Zummesh Keypad Custom Programming.WebHome]]).
157 157  * Zum Partition Sensors do not report back to the system and cannot be used to handle room divide/combine logic externally to the linked Zum rooms.
158 158  * Off Scene cannot be saved and is always room Off
159 159  * Scenes 1 through 16 are supported and may be modified and saved.
160 -* Scenes with fade times greater than 1 second will result in loads being commanded individual from ShowRunner and may not be in sync depending on load quantity, RF gateway load, and RF signal integrity.  Zum hardware does not support a fade time as part of the Scene setting.  Fade times must be commanded from ShowRunner.  Scene fade times will be ignored when scenes are activated by Zum keypads or internal occupancy logic.
161 -* Saving scenes from ShowRunner captures the levels set in ShowRunner at the time of the save.  ShowRunner will attempt to learn scenes as they are recalled.
160 +* Scenes with fade times greater than 1 second will result in loads being commanded individual from ShowRunnerCLC™ and may not be in sync depending on load quantity, RF gateway load, and RF signal integrity.  Zum hardware does not support a fade time as part of the Scene setting.  Fade times must be commanded from ShowRunnerCLC™.  Scene fade times will be ignored when scenes are activated by Zum keypads or internal occupancy logic.
161 +* Saving scenes from ShowRunnerCLC™ captures the levels set in ShowRunnerCLC™ at the time of the save.  ShowRunner will attempt to learn scenes as they are recalled.
162 162  * Override/Override Level features are not supported
163 163  * Load disable is not supported
164 164  * After hours logic is not supported
... ... @@ -165,8 +165,8 @@
165 165  * Blink before timeout is not supported
166 166  * CCT control is presently not supported (ZUMMESH-JBOX-DALI support may be available in the future)
167 167  * RGB loads are not supported
168 -* Minimum/Maximum Levels are not supported when loads are being recalled locally.  ShowRunner will honor them when control occurs from ShowRunner except for raise/lower which is performed on hardware.
169 -* Dimming curves are not supported when loads are being recalled locally.  Use Zum app to adjust dimming curves if necessary.  Recommended to leave ShowRunner dimming curve set to "Unaffected".
168 +* Minimum/Maximum Levels are not supported when loads are being recalled locally.  ShowRunnerCLC™ will honor them when control occurs from ShowRunnerCLC™ except for raise/lower which is performed on hardware.
169 +* Dimming curves are not supported when loads are being recalled locally.  Use Zum app to adjust dimming curves if necessary.  Recommended to leave ShowRunnerCLC™ dimming curve set to "Unaffected".
170 170  * BACNET support requires a processor hardware license and ShowRunner BACNET license.  BACNET point availability can be configured per Area.
171 171  * Chief Integrations recommends one 4-series (preferred) or 3-series processor per building floor at a minimum.
172 172  * Zummesh and infiNET EX devices are not officially supported on the same gateway, discuss with Crestron if needing both.
... ... @@ -176,19 +176,19 @@
176 176  
177 177  (% class="box" %)
178 178  (((
179 -**SHOWRUNNER™ Total Control**
179 +**ShowRunnerCLC™ Total Control**
180 180  [[image:ZumSr\@2x.png||alt="Zum SHOWRUNNER™ Total Control Topology"]]
181 181  )))
182 182  
183 183  (% class="box" %)
184 184  (((
185 -**SHOWRUNNER™ + AVBRIDGE + Serial Port**
185 +**ShowRunnerCLC™ + AVBRIDGE + Serial Port**
186 186  [[image:ZumAvbSr\@2x.png||alt="Zum AVBRIDGE + SHOWRUNNER™ Topology"]]
187 187  )))
188 188  
189 189  (% class="box" %)
190 190  (((
191 -**SHOWRUNNER™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)**
191 +**ShowRunnerCLC™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)**
192 192  [[image:ZumFhSr\@2x.png||alt="Zum Floor Hub + SHOWRUNNER™ Topology"]]
193 193  )))
194 194