1 Crestron Zūm Wireless is a locally integrated lighting control system with various global control options.  Zūm rooms are self-contained control units with primary logic occurring at the room level.  Central control systems offer scheduling and management.  SHOWRUNNER™ provides a number of integrations options that allow the designer to optimize the solution design.
2
3 ==== Integration Options ====
4
5 * **SHOWRUNNER™ Total Control** - The most comprehensive option.  Allows seamless (see [[Caveats>>||anchor="caveats"]]) integration of Zūm and non-Zūm Crestron lighting control products.  Extensive feature set allows centralized control and management of Zūm rooms.  Advanced scheduler provides more flexibility to the facility operator.  This solution replaces the ZUM-FLOOR-HUB in the system design.
6 * **SHOWRUNNER™ + AVBRIDGE + Serial Port** - Provides scene setting and load control via a dedicated AVBRIDGE in each Zūm room.  Requires a dedicated serial port (C2N-IO/CEN-IO-COM2/etc) and a dedicated ZUMMESH-AVBRIDGE per room.
7 * **SHOWRUNNER™ + ZUM-FLOOR-HUB** - Provides limited scene recall and room status for Zūm rooms paired with the Floor Hub.  SHOWRUNNER™ can export its own areas to the Floor Hub.
8
9 ==== Feature Matrix ====
10
11 (% border="1" style="margin-left:auto; margin-right:auto" %)
12 |=Feature|=SHOWRUNNER™ Total Control|=SHOWRUNNER™ + AVBRIDGE + Serial Port|=SHOWRUNNER™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)|=ZUM-FLOOR-HUB Only|=Zūm iOS/Android Setup App*
13 |(% colspan="6" %)**Hardware Requirements**
14 |Requires JBOX with ZUMMESH-NETBRIDGE|Y|N|Y|Y|Y
15 |Requires ZUMMESH-GATEWAY|Y|N|Y|Y|N/A
16 |Requires Dedicated RS-232 Serial Port per Room|N|Y|N|N|N/A
17 |Requires 3 or 4-Series Control System|Y|Y|Y|N|N/A
18 |Requires Physical Presence in Room to Change Scenes|N|N|Y, via Zūm Setup App|Y, via Zūm Setup App|Y
19 |(% colspan="6" %)**User Interfaces**
20 |Web Browser|(((
21 Crestron SmartGraphics XPanel
22 HTML5 UI Under Development (Q4 2020)
23 )))|Crestron SmartGraphics XPanel
24 HTML5 UI Under Development (Q4 2020)|SHOWRUNNER™ - Crestron SmartGraphics XPanel
25 ZUM-FLOOR-HUB - HTML5 UI|HTML5 UI|N
26 |iOS/Android|Y, Crestron App (Paid Upgrade)|Y, Crestron App (Paid Upgrade)|Y, Crestron App (Paid Upgrade), Limited Features for Zūm Rooms|N|Y*
27 |Touchscreens (Crestron TSW series)|Y|Y|Y, Limited Features for Zūm Rooms|N|N
28 |(% colspan="6" %)**Features**
29 |Scene Recall|Y ~*~*~*~*|Y ~*~*~*~*|Y|Y|Y
30 |Override Fade Time for Scene Recall ~*~*|Y|N|N|N|N
31 |Scene Save|Y ~*~*~*~*|Y ~*~*~*~*|N|N|Y
32 |Load Control|Y ~*~**/~*~*~*~**|Y ~*~**|N|N|Y
33 |Demand Response|Y|N|Y, separate triggers for SHOWRUNNER™ and ZUM-FLOOR-HUB required|Y|N
34 |Enable/Disable Occupancy|Y|Y|Y, from Floor Hub|Y|Y
35 |Override Occupancy Logic|Y|Y|N|N|N
36 |Plug Load On/Off|Y|Y|Y|Y|By Hardware
37 |Integration with Non-Zūm Crestron Hardware|Y|Y|N|N|N
38 |Custom Zūm Keypad Programming|N|Y, Zūm AV Keypad Only|N|N|Y, within the limits of the hardware
39 |New Feature Release Cycle|Aggressive|Aggressive|SHOWRUNNER™: Aggressive
40 Floor Hub: 6-12 months|6-12 months|6-12 months
41 |Room Organization|(((
42 Under Development:
43 Building/Floor/Sub-Group/Area
44 Categorization to Filter by Category/Tag
45 )))|See SHOWRUNNER™ Total Control|SHOWRUNNER™: See SHOWRUNNER™ Total Control
46 Floor Hub: Category/Room|Category/Room|(((
47 N/A
48 )))
49 |Room Discovery|Automatic Discovery of Gateways and NETBRIDGES|Pre-Configured at Order|SHOWRUNNER™: Pre-Configured at Order
50 Floor Hub: Map Mirrored Rooms to SHOWRUNNER™ and Discovery External Rooms|Automatic Discovery of Gateways and NETBRIDGES|N/A
51 |Firmware Updates|PUF Tool
52 Automatic Support on Roadmap|(((
53 PUF Tool
54 Automatic Support on Roadmap
55 )))|SHOWRUNNER™: PUF Tool
56 Floor Hub: Automatic, Internet Connection Required|Automatic, Internet Connection Required|N/A
57 |(% colspan="6" %)**Calendar/Scheduling**
58 |Logic Type|Event Driven
59 Profile Support (Under Development)|Event Driven
60 Profile Support (Under Development)|SHOWRUNNER™: Event Driven
61 Floor Hub: Pattern assigned to Category|Pattern assigned to Category|N/A
62 |Astronomical Clock|Y|Y|Y, Per Category|Y, Per Category|N/A
63 |Holidays|Pattern|Pattern|SHOWRUNNER™: Pattern
64 Floor Hub: Hard Coded|Hard Coded|N/A
65 |Custom Patterns|Y, Advanced Scheduler License|Y, Advanced Scheduler License|SHOWRUNNER™: Y, Advanced Scheduler License
66 Floor Hub: N|N|N/A
67 |(% colspan="6" %)**Integrations**
68 |A/V Integration: API|Y|Y|SHOWRUNNER™: Y
69 Floor Hub: Limited|Limited|N/A
70 |A/V Integration: Crestron EISC|Y|Y|SHOWRUNNER™: Y
71 Floor Hub: N|N|N/A
72 |A/V Integration: RS-232|Y|Y|(((
73 SHOWRUNNER™: Y
74 Floor Hub: AVBRIDGE per Area
75 )))|AVBRIDGE per Area|N/A
76 |BACNET|Y, SHOWRUNNER™ and Crestron Licenses Needed|Y, SHOWRUNNER™ and Crestron Licenses Needed|(((
77 SHOWRUNNER™: SHOWRUNNER™ and Crestron Licenses Needed
78 Floor Hub: Y
79 )))|Y|N/A
80 |BACNET Features|(((
81 Per Area Status:
82 Active Scene
83 Occupied
84 Occupancy Enabled
85 Individual Load Level
86 Photocell Level (per Photocell)
87 Plug Loads Enabled
88
89 System:
90 Demand Response Enabled
91 System Wide Override (Panic/Emergency)
92
93 ~* More Features added upon request
94 )))|See list for SHOWRUNNER™ Total Control|(((
95 SHOWRUNNER™: See list for SHOWRUNNER™ Total Control
96 Floor Hub: See list for ZUM-FLOOR-HUB
97 )))|(((
98 Per Room Status:
99 Online
100 On
101 Occupied
102 Daylighting Active
103 Device Battery is Low
104 Plug Loads Enabled
105 Occupancy Sensor Enabled
106 Current Daylight Level
107 Active Scene
108 \\System:
109 Demand Response Enabled
110 )))|N/A
111 |BACNET Settings Scope
112 (What Points are Exposed)|Per Area|Per Area|(((
113 SHOWRUNNER™: Per Area
114 Floor Hub: Global
115 )))|Global|N/A
116 |BACNET Points Supported|Depends on Crestron License and Hardware|Depends on Crestron License and Hardware|SHOWRUNNER™: Depends on Crestron License and Hardware
117 Floor Hub: 1000|1000|N/A
118 |Crestron Fusion|Y|Y|(((
119 SHOWRUNNER™: Y
120 Floor Hub: N
121 )))|N|N/A
122 |Export to Zūm Floor Hub|Y, Licensed|Y, Licensed|SHOWRUNNER™: Y, Licensed|N/A|N/A
123 |GLPAC|Y|Y|SHOWRUNNER™: Y
124 Floor Hub: Via SHOWRUNNER™|N|N/A
125 |System to System Link|Y|Y|(((
126 SHOWRUNNER™: Y
127 Floor Hub: N
128 )))|N|N/A
129 |Minimum NETBRIDGE Firmware|v1.12.0130 (PUF Zum MESHNET v1.06.09)|v1.010|N/A|See Crestron|See Crestron
130 |Minimum Gateway Firmware|v1.4469.00011|N/A|N/A|See Crestron|See Crestron
131 |Minimum SHOWRUNNER™ Version|2.198|2.198|N/A|N/A|N/A
132
133 {{{* Zūm Setup App works as long as the NETBRIDGE is physically near the iOS/Android device running the Zūm Setup App. ** Fade time is automatically applied if scene is set longer than 1 second. Must be triggered from SHOWRUNNER™, cannot be triggered from Zūm keypad with current firmware (as of April 2020). *** Zūm wireless does not support direct coupling of fade times and the behavior is different internally within the dimmer versus other Crestron products. Raise/Lower level accuracy is not guaranteed. For best performance when settings scenes, set the slider manually which will send exact levels to the dimmer. **** Zūm wireless scenes cannot presently be read on command. Scenes should be created and saved from SHOWRUNNER™ directly. Saved scenes are stored directly on the Zūm wireless dimmer and in ShowRunner. ShowRunner will query the NETBRIDGE after scene recall and attempt to build scene information but operations are done one at a time. ***** Zūm wireless real time load status is not available.  Any changes to loads performed using the raise/lower functions in room will not be propagated back to ShowRunner.  Levels set by the daylight sensor with daylighting enabled will not be reported by ShowRunner. }}}
134
135 {{id name="caveats"/}}
136 ==== Caveats ====
137
138 * Zum Wireless has an internal rate limit that will shutdown communication if a number of commands are received in a short period of time.  This can be seen when repeatedly pressing buttons on a keypad as well as repeatedly triggering actions from ShowRunner.
139 * Raise/Lower operations from ShowRunner cannot track directly with the load response, see ~*~** above.  ShowRunner will poll the NETBRIDGE for current levels ~~3 seconds after the raise/lower is stopped to obtain current load levels.
140 * Lower operations can turn the load off.  The load will not come on with a raise.  This is a firmware behavior in the Zum hardware.
141 * Wireless control presents some additional latency possibilities.  Commands required to provide full functionality (load control/raise/lower) with Zum wireless are more intensive than traditional Crestron hardware and may impact performance under heavy load.  Local operation of the Zum wireless room is not impacted.
142 * Real time load status is not available.  Any changes to loads performed using the raise/lower functions in room will not be propagated back to ShowRunner.  Levels set by the daylight sensor with daylighting enabled will not be reported by ShowRunner.
143 * Keypad behaviors cannot be modified.  Custom keypads can be implemented using the AVBRIDGE connected to the system via a serial port, Zum requires an AV specific keypad for this purpose.
144 * Zum Partition Sensors do not report back to the system and cannot be used to handle room divide/combine logic.
145 * Off Scene cannot be saved and is always room Off
146 * Scenes 1 through 16 are supported and may be modified and saved.
147 * Scenes with fade times greater than 1 second will result in loads being commanded individual from ShowRunner and may not be in sync depending on load quantity, RF gateway load, and RF signal integrity.  Zum hardware does not support a fade time as part of the Scene setting.  Fade times must be commanded from ShowRunner.  Scene fade times will be ignored when scenes are activated by Zum keypads or internal occupancy logic.
148 * Saving scenes from ShowRunner captures the levels set in ShowRunner at the time of the save.  ShowRunner will attempt to learn scenes as they are recalled.
149 * Override/Override Level features are not supported
150 * Load disable is not supported
151 * After hours logic is not supported
152 * Blink before timeout is not supported
153 * CCT control is presently not supported (ZUMMESH-JBOX-DALI support may be available in the future)
154 * RGB loads are not supported
155 * Minimum/Maximum Levels are not supported when loads are being recalled locally.  ShowRunner will honor them when control occurs from ShowRunner except for raise/lower which is peformed on hardware.
156 * Dimming curves are not supported when loads are being recalled locally.  Use Zum app to adjust dimming curves if necessary.  Recommended to leave ShowRunner dimming curve set to "Unaffected".
157 * BACNET support requires a processor hardware license and ShowRunner BACNET license.  BACNET point availability can be configured per Area.
158 * Chief Integrations recommends one 3-series processor per building floor at a minimum.
159 * Zummesh and infiNET EX devices are not officially supported on the same gateway, discuss with Crestron if needing both.
160
161 (% id="HTopologies" %)
162 ==== Topologies ====
163
164 (% class="box" %)
165 (((
166 **SHOWRUNNER™ Total Control**
167 [[image:ZumSr\@2x.png||alt="Zum SHOWRUNNER™ Total Control Topology"]]
168 )))
169
170 (% class="box" %)
171 (((
172 **SHOWRUNNER™ + AVBRIDGE + Serial Port**
173 [[image:ZumAvbSr\@2x.png||alt="Zum AVBRIDGE + SHOWRUNNER™ Topology"]]
174 )))
175
176 (% class="box" %)
177 (((
178 **SHOWRUNNER™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)**
179 [[image:ZumFhSr\@2x.png||alt="Zum Floor Hub + SHOWRUNNER™ Topology"]]
180 )))
181
182 (% class="box" %)
183 (((
184 **ZUM-FLOOR-HUB Only**
185 [[image:ZumFh\@2x.png||alt="Zum Floor Hub Topology"]]
186 )))
187
188 (% class="box" %)
189 (((