... ... @@ -1,18 +1,19 @@
1 -Crestron Zūm Wireless is a locally integrated lighting control system with various global control options.  SHOWRUNNER™ provides a number of integrations options that allow the designer to optimize the solution design.
1 +Crestron Zūm Wireless is a locally integrated lighting control system with various global control options.  SHOWRUNNER™ provides a number of integrations options that allow the designer to optimize the solution design.  SHOWRUNNER™
2 2  
3 3  ==== Integration Options ====
4 4  
5 -* SHOWRUNNER™ Total Control - The most comprehensive option.  Allows seamless integration of Zūm and non-Zūm Crestron lighting control products.  Extensive feature set allows centralized control and management of Zūm rooms.  Advanced scheduler provides more flexibility to the facility operator.  This solution replaces the ZUM-FLOOR-HUB.
6 -* SHOWRUNNER™ + AVBRIDGE + Serial Port - Provides scene setting and load control via a dedicated AVBRIDGE in each Zūm room.  Requires a dedicated serial port (C2N-IO/CEN-IO-COM2/etc) and a dedicated ZUMMESH-AVBRIDGE per room.
7 -* SHOWRUNNER™ + ZUM-FLOOR-HUB - Provides limited scene recall and room status for Zūm rooms paired with the Floor Hub.  SHOWRUNNER™ can export its own areas to the Floor Hub.
5 +* **SHOWRUNNER™ Total Control** - The most comprehensive option.  Allows seamless integration of Zūm and non-Zūm Crestron lighting control products.  Extensive feature set allows centralized control and management of Zūm rooms.  Advanced scheduler provides more flexibility to the facility operator.  This solution replaces the ZUM-FLOOR-HUB.
6 +* **SHOWRUNNER™ + AVBRIDGE + Serial Port** - Provides scene setting and load control via a dedicated AVBRIDGE in each Zūm room.  Requires a dedicated serial port (C2N-IO/CEN-IO-COM2/etc) and a dedicated ZUMMESH-AVBRIDGE per room.
7 +* **SHOWRUNNER™ + ZUM-FLOOR-HUB** - Provides limited scene recall and room status for Zūm rooms paired with the Floor Hub.  SHOWRUNNER™ can export its own areas to the Floor Hub.
8 8  
9 9  ==== Feature Matrix ====
10 10  
11 -|=Feature|=SHOWRUNNER™ Total Control|=SHOWRUNNER™ + AVBRIDGE + Serial Port|=SHOWRUNNER™ + ZUM-FLOOR-HUB|=ZUM-FLOOR-HUB Only|=Zūm iOS/Android Setup App*
11 +|=Feature|=SHOWRUNNER™ Total Control|=SHOWRUNNER™ + AVBRIDGE + Serial Port|=SHOWRUNNER™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)|=ZUM-FLOOR-HUB Only|=Zūm iOS/Android Setup App*
12 12  |(% colspan="6" %)**Hardware Requirements**
13 -|Requires JBOX and ZUMMESH-NETBRIDGE|Y|N|Y|Y|Y
13 +|Requires JBOX with ZUMMESH-NETBRIDGE|Y|N|Y|Y|Y
14 14  |Requires ZUMMESH-GATEWAY|Y|N|Y|Y|N/A
15 -|Requires RS-232 Serial Port per Room|N|Y|N|N|N/A
15 +|Requires Dedicated RS-232 Serial Port per Room|N|Y|N|N|N/A
16 +|Requires 3 or 4-Series Control System|Y|Y|Y|N|N/A
16 16  |Physical Presence in Room to Change Scenes|N|N|Y, via Zūm Setup App|Y, via Zūm Setup App|Y
17 17  |(% colspan="6" %)**User Interfaces**
18 18  |Web Browser|(((
... ... @@ -32,31 +32,98 @@
32 32  |Enable/Disable Occupancy|Y|Y|Y, from Floor Hub|Y|Y
33 33  |Override Occupancy Logic|Y|Y|N|N|N
34 34  |Plug Load On/Off|Y|Y|Y|Y|By Hardware
35 -|Integration with Non-Zūm Hardware|Y|Y|N|N|N
36 -|Custom Zūm Keypad Programming|N|Y, AV Keypad Only|N|N|Y, within the limits of the hardware
36 +|Integration with Non-Zūm Crestron Hardware|Y|Y|N|N|N
37 +|Custom Zūm Keypad Programming|N|Y, Zūm AV Keypad Only|N|N|Y, within the limits of the hardware
38 +|New Feature Release Cycle|Aggressive|Aggressive|SHOWRUNNER™: Aggressive
39 +Floor Hub: 6-12 months|6-12 months|6-12 months
40 +|Room Organization|(((
41 +Under Development:
42 +Building/Floor/Sub-Group/Area
43 +Categorization to Filter by Category/Tag
44 +)))|See SHOWRUNNER™ Total Control|SHOWRUNNER™: See SHOWRUNNER™ Total Control
45 +Floor Hub: Category/Room|Category/Room|(((
46 +N/A
47 +)))
48 +|Room Discovery|Automatic Discovery of Gateways and NETBRIDGES|Pre-Configured at Order|SHOWRUNNER™: Pre-Configured at Order
49 +Floor Hub: Map Mirrored Rooms to SHOWRUNNER™ and Discovery External Rooms|Automatic Discovery of Gateways and NETBRIDGES|N/A
50 +|Firmware Updates|PUF Tool
51 +Automatic Support on Roadmap|(((
52 +PUF Tool
53 +Automatic Support on Roadmap
54 +)))|SHOWRUNNER™: PUF Tool
55 +Floor Hub: Automatic, Internet Connection Required|Automatic, Internet Connection Required|N/A
37 37  |(% colspan="6" %)**Calendar/Scheduling**
38 38  |Logic Type|Event Driven
39 39  Profile Support (Under Development)|Event Driven
40 40  Profile Support (Under Development)|SHOWRUNNER™: Event Driven
41 41  Floor Hub: Pattern assigned to Category|Pattern assigned to Category|N/A
42 -|Astronomical Clock|Y|Y|Y|Y|N/A
61 +|Astronomical Clock|Y|Y|Y, Per Category|Y, Per Category|N/A
43 43  |Holidays|Pattern|Pattern|SHOWRUNNER™: Pattern
44 44  Floor Hub: Hard Coded|Hard Coded|N/A
45 45  |Custom Patterns|Y, Advanced Scheduler License|Y, Advanced Scheduler License|SHOWRUNNER™: Y, Advanced Scheduler License
46 46  Floor Hub: N|N|N/A
47 47  |(% colspan="6" %)**Integrations**
67 +|A/V Integration: API|Y|Y|SHOWRUNNER™: Y
68 +Floor Hub: Limited|Limited|N/A
69 +|A/V Integration: Crestron EISC|Y|Y|SHOWRUNNER™: Y
70 +Floor Hub: N|N|N/A
71 +|A/V Integration: RS-232|Y|Y|(((
72 +SHOWRUNNER™: Y
73 +Floor Hub: AVBRIDGE per Area
74 +)))|AVBRIDGE per Area|N/A
48 48  |BACNET|Y, SHOWRUNNER™ and Crestron Licenses Needed|Y, SHOWRUNNER™ and Crestron Licenses Needed|(((
49 49  SHOWRUNNER™: SHOWRUNNER™ and Crestron Licenses Needed
50 50  Floor Hub: Y
51 51  )))|Y|N/A
52 -|BACNET Features|Area Scene, Load Control, Occupancy Status/Enable/Disable|Area Scene, Load Control, Occupancy Status/Enable/Disable|(((
53 -SHOWRUNNER™: See list to the left
54 -Floor Hub:
55 -)))| |N/A
56 -|BACNET Settings Scope|Per Area|Per Area|(((
79 +|BACNET Features|(((
80 +Per Area Status:
81 +Active Scene
82 +Occupied
83 +Occupancy Enabled
84 +Individual Load Level
85 +Photocell Level (per Photocell)
86 +Plug Loads Enabled
87 +
88 +System:
89 +Demand Response Enabled
90 +System Wide Override (Panic/Emergency)
91 +
92 +~* More Features added upon request
93 +)))|See list for SHOWRUNNER™ Total Control|(((
94 +SHOWRUNNER™: See list for SHOWRUNNER™ Total Control
95 +Floor Hub: See list for ZUM-FLOOR-HUB
96 +)))|(((
97 +Per Room Status:
98 +Online
99 +On
100 +Occupied
101 +Daylighting Active
102 +Device Battery is Low
103 +Plug Loads Enabled
104 +Occupancy Sensor Enabled
105 +Current Daylight Level
106 +Active Scene
107 +\\System:
108 +Demand Response Enabled
109 +)))|N/A
110 +|BACNET Settings Scope
111 +(What Points are Exposed)|Per Area|Per Area|(((
57 57  SHOWRUNNER™: Per Area
58 58  Floor Hub: Global
59 59  )))|Global|N/A
115 +|BACNET Points Supported|Depends on Crestron License and Hardware|Depends on Crestron License and Hardware|SHOWRUNNER™: Depends on Crestron License and Hardware
116 +Floor Hub: 1000|1000|N/A
117 +|Crestron Fusion|Y|Y|(((
118 +SHOWRUNNER™: Y
119 +Floor Hub: N
120 +)))|N|N/A
121 +|Export to Zūm Floor Hub|Y, Licensed|Y, Licensed|SHOWRUNNER™: Y, Licensed|N/A|N/A
122 +|GLPAC|Y|Y|SHOWRUNNER™: Y
123 +Floor Hub: Via SHOWRUNNER™|N|N/A
124 +|System to System Link|Y|Y|(((
125 +SHOWRUNNER™: Y
126 +Floor Hub: N
127 +)))|N|N/A
60 60  
61 61  ##* Zūm Setup App works as long as the NETBRIDGE is physically near the iOS/Android device running the Zūm Setup App.##
62 -##~*~* Fade time is automatically applied if scene is set longer than 1 second.  Must be triggered from SHOWRUNNER™, cannot be triggered from Zūm keypad with current firmware (Apr 2020).##
130 +##~*~* Fade time is automatically applied if scene is set longer than 1 second.  Must be triggered from SHOWRUNNER™, cannot be triggered from Zūm keypad with current firmware (as of April 2020).##