Changes for page Crestron Zūm Wireless

Last modified by Scott Kohlmann on 2023/04/20 22:28

From version 16.1
edited by Mark Kohlmann
on 2020/11/09 18:16
Change comment: There is no comment for this version
To version 11.1
edited by Mark Kohlmann
on 2020/04/15 16:18
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,8 +1,8 @@
1 -Crestron Zūm Wireless is a locally integrated lighting control system with various global control options.  Zūm rooms are self-contained control units with primary logic occurring at the room level.  Central control systems offer scheduling and management.  SHOWRUNNER™ provides a number of integrations options that allow the designer to optimize the solution design.
1 +Crestron Zūm Wireless is a locally integrated lighting control system with various global control options.  SHOWRUNNER™ provides a number of integrations options that allow the designer to optimize the solution design.  SHOWRUNNER™
2 2  
3 3  ==== Integration Options ====
4 4  
5 -* **SHOWRUNNER™ Total Control** - The most comprehensive option.  Allows seamless integration of Zūm and non-Zūm Crestron lighting control products.  Extensive feature set allows centralized control and management of Zūm rooms.  Advanced scheduler provides more flexibility to the facility operator.  This solution replaces the ZUM-FLOOR-HUB in the system design.
5 +* **SHOWRUNNER™ Total Control** - The most comprehensive option.  Allows seamless integration of Zūm and non-Zūm Crestron lighting control products.  Extensive feature set allows centralized control and management of Zūm rooms.  Advanced scheduler provides more flexibility to the facility operator.  This solution replaces the ZUM-FLOOR-HUB.
6 6  * **SHOWRUNNER™ + AVBRIDGE + Serial Port** - Provides scene setting and load control via a dedicated AVBRIDGE in each Zūm room.  Requires a dedicated serial port (C2N-IO/CEN-IO-COM2/etc) and a dedicated ZUMMESH-AVBRIDGE per room.
7 7  * **SHOWRUNNER™ + ZUM-FLOOR-HUB** - Provides limited scene recall and room status for Zūm rooms paired with the Floor Hub.  SHOWRUNNER™ can export its own areas to the Floor Hub.
8 8  
... ... @@ -15,7 +15,7 @@
15 15  |Requires ZUMMESH-GATEWAY|Y|N|Y|Y|N/A
16 16  |Requires Dedicated RS-232 Serial Port per Room|N|Y|N|N|N/A
17 17  |Requires 3 or 4-Series Control System|Y|Y|Y|N|N/A
18 -|Requires Physical Presence in Room to Change Scenes|N|N|Y, via Zūm Setup App|Y, via Zūm Setup App|Y
18 +|Physical Presence in Room to Change Scenes|N|N|Y, via Zūm Setup App|Y, via Zūm Setup App|Y
19 19  |(% colspan="6" %)**User Interfaces**
20 20  |Web Browser|(((
21 21  Crestron SmartGraphics XPanel
... ... @@ -26,10 +26,10 @@
26 26  |iOS/Android|Y, Crestron App (Paid Upgrade)|Y, Crestron App (Paid Upgrade)|Y, Crestron App (Paid Upgrade), Limited Features for Zūm Rooms|N|Y*
27 27  |Touchscreens (Crestron TSW series)|Y|Y|Y, Limited Features for Zūm Rooms|N|N
28 28  |(% colspan="6" %)**Features**
29 -|Scene Recall|Y ~*~*~*~*|Y ~*~*~*~*|Y|Y|Y
30 -|Override Fade Time for Scene Recall ~*~*|Y|N|N|N|N
31 -|Scene Save|Y ~*~*~*~*|Y ~*~*~*~*|N|N|Y
32 -|Load Control|Y ~*~**|Y ~*~**|N|N|Y
29 +|Scene Recall|Y|Y|Y|Y|Y
30 +|Override Fade Time for Scene Recall~*~*|Y|N|N|N|N
31 +|Scene Save|Y|Y|N|N|Y
32 +|Load Control|Y|Y|N|N|Y
33 33  |Demand Response|Y|N|Y, separate triggers for SHOWRUNNER™ and ZUM-FLOOR-HUB required|Y|N
34 34  |Enable/Disable Occupancy|Y|Y|Y, from Floor Hub|Y|Y
35 35  |Override Occupancy Logic|Y|Y|N|N|N
... ... @@ -127,42 +127,32 @@
127 127  Floor Hub: N
128 128  )))|N|N/A
129 129  
130 -{{{* Zūm Setup App works as long as the NETBRIDGE is physically near the iOS/Android device running the Zūm Setup App.
131 -** Fade time is automatically applied if scene is set longer than 1 second. Must be triggered from SHOWRUNNER™, cannot be triggered from Zūm keypad with current firmware (as of April 2020).
132 -*** Zūm wireless does not support direct coupling of fade times and the behavior is different internally within the dimmer versus other Crestron products. Raise/Lower level accuracy is not guaranteed. For best performance when settings scenes, set the slider manually which will send exact levels to the dimmer.
133 -**** Zūm wireless scenes cannot presently be read. Scenes should be created and saved from SHOWRUNNER™ directly. Saved scenes are stored directly on the Zūm wireless dimmer.
134 -}}}
130 +##* Zūm Setup App works as long as the NETBRIDGE is physically near the iOS/Android device running the Zūm Setup App.##
131 +##~*~* Fade time is automatically applied if scene is set longer than 1 second.  Must be triggered from SHOWRUNNER™, cannot be triggered from Zūm keypad with current firmware (as of April 2020).##
135 135  
136 136  
137 -(% id="HTopologies" %)
138 138  ==== Topologies ====
139 139  
140 -(% class="box" %)
141 -(((
142 142  **SHOWRUNNER™ Total Control**
137 +
143 143  [[image:ZumSr\@2x.png||alt="Zum SHOWRUNNER™ Total Control Topology"]]
144 -)))
145 145  
146 -(% class="box" %)
147 -(((
140 +
148 148  **SHOWRUNNER™ + AVBRIDGE + Serial Port**
142 +
149 149  [[image:ZumAvbSr\@2x.png||alt="Zum AVBRIDGE + SHOWRUNNER™ Topology"]]
150 -)))
151 151  
152 -(% class="box" %)
153 -(((
145 +
154 154  **SHOWRUNNER™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)**
147 +
155 155  [[image:ZumFhSr\@2x.png||alt="Zum Floor Hub + SHOWRUNNER™ Topology"]]
156 -)))
157 157  
158 -(% class="box" %)
159 -(((
150 +
160 160  **ZUM-FLOOR-HUB Only**
161 -[[image:ZumFh\@2x.png||alt="Zum Floor Hub Topology"]]
162 -)))
163 163  
164 -(% class="box" %)
165 -(((
153 +[[image:ZumApp\@2x.png||alt="Zum App Topology"]]
154 +
155 +
166 166  **Zūm iOS/Android Setup App**
157 +
167 167  [[image:ZumApp\@2x.png||alt="Zum App Topology"]]
168 -)))