Mark Kohlmann 2.1 1 Zum wired can be deployed in App (Zum) Mode or CNET Mode.  App mode will perform lighting control logic within the Zum JBOX hardware while CNET mode pushes all logic back to the Control System.  ShowRunnerCLC™ supports both modes and can be used to enhance app mode or allow complete control over the hardware to perform functionality.  All hardware does not need to be in app mode on a project.  You can mix and match as needed.  This is not an exhaustive list but serves as a guide for when Zum is required to be in CNET mode to achieve the desired functionality.
Mark Kohlmann 1.1 2
3 (% class="box warningmessage" %)
4 (((
5 Due to technical complexities with firmware, Zum AutoSwitch is not recommended.  Either provision entirely in Zum App Mode or CNET Mode.
6 )))
7
8 ==== App Mode vs CNET Mode Breakdown ====
9
10 (% style="margin-left:auto; margin-right:auto; width:100%" %)
11 |=Feature|=ShowRunnerCLC™ w/ Zum App Mode|=ShowRunnerCLC™ w/ Zum CNET Mode|=App-Mode Only
12 |(% colspan="3" %)**Hardware**|
13 |Requires Active Connection to Processor|Feature Dependent^^1,2^^|Y|N
14 |Max Zum Devices per room|(((
15 ZUMNET-JBOX-DALI (v3.09 or earlier, CI recommends 3.06.20 or lower): 32
16 ZUMNET-JBOX-DALI (v3.10 or later): 7
17 ZUMNET-JBOX-16A-LV (v3.09 or earlier): 32
18 ZUMNET-JBOX-16A-LV (v3.10 or later): 14
19 ZUMNET-DIN-*: 32
20 )))|32, can be expanded by adding additional ZUMNETs or DIN-CENCN-2s|ZUMNET-JBOX-DALI (v3.09 or earlier, CI recommends 3.06.20 or lower): 32
21 ZUMNET-JBOX-DALI (v3.10 or later): 7
22 ZUMNET-JBOX-16A-LV (v3.09 or earlier): 32
23 ZUMNET-JBOX-16A-LV (v3.10 or later): 14
24 ZUMNET-DIN-*: 32
25 |Requires Keypad to Program App Logic|Y|N/A, programmed in ShowRunnerCLC™|Y
26 |Crestron non-Zum Hardware Integration|Y^^1^^|Y|N
27 |Non-Crestron Hardware Integration|Y^^1^^|Y|N
28 |Multiple ZUMNET Masters in a Single Room|Y^^1^^|Y|N
Mark Kohlmann 2.1 29 |More than One Room per ZUMNET|Not Recommended, Requires Groups within App Mode|Y|Requires Groups
Mark Kohlmann 1.1 30 |Scheduling / Time Clock|Y^^1^^|Y|ZUMLINK-[DIN/JBOX]-IO per room or HUB4
31 |Dynamic White|Y^^1^^|Y|N
32 |(% colspan="4" %)**DALI**
33 |Address and Discover DALI
34 ZUMNET-JBOX-DALI
35 ZUMNET-DIN-DLI|
36 Zum App^^3^^
37 Zum App^^3^^|
38 Toolbox/ShowRunnerCLC™
39 Not Supported, Only Supports App Mode [Use DIN-DLI for CNET]|
40 Zum App^^3^^
41 Zum App^^3^^
42 |DALI Type 8|Y^^1^^|Y|N
43 |(% colspan="4" %)**Scenes**
44 |Max Scenes|(((
45 ShowRunnerCLC™: Unlimited
46 Local logic: 16 + Off
47 )))|Unlimited|16 + Off
Mark Kohlmann 2.1 48 |Per Scene Fade Times|Y^^1,2,4^^|Y|Partial^^4^^
Mark Kohlmann 1.1 49 |(% colspan="4" %)**Loads**
50 |Min/Max Trim|Y^^2^^|(((
51 Y
52 )))|(((
53 Min: 0-45%
54 Max: 55-100%
55 )))
56 |Dimming Curve|Y^^2^^|Y|N
57 |Unoccupied Level|Y(% style="font-size:10.5px" %)^^1^^|Y|N
58 |CCT / Dynamic White|Y^^1^^|Y|N
59 |RGB|Y^^1^^|Y|N
60 |(% colspan="4" %)**Occupancy Logic**
61 |Occupancy Modes|Y^^2^^|Y|Y
Craig Lewis 4.1 62 |Grace Timeout|Y^^1^^|Y|N
Mark Kohlmann 1.1 63 |Extended Timeout|Y^^1^^|Y|N
64 |2 Stage Vacancy|Y^^1^^|Y|N
65 |(% colspan="4" %)**Keypads**
66 |Disable Keypads|Y^^1^^|Y|N
67 |Custom Keypad Programming|Y^^2^^|Y|N
68 |(% colspan="2" rowspan="1" %)**Room Logic**| |
69 |After Hours / Auto Timeout|Y^^1^^|Y|N
Mark Kohlmann 3.1 70 |Plug Load (Auto/On/Off)|Y^^1^^|Y|Internal behavior only
Mark Kohlmann 1.1 71 |Recall Last Level|Y^^1^^|Y|N
72
73 ==== Notes ====
74
75 1 - [App Mode Only] Logic must be handled by ShowRunnerCLC™.  An active connection to the control system/ShowRunnerCLC™ is required.
Mark Kohlmann 2.1 76 2 - [App Mode Only] Some logic may be handled by ShowRunnerCLC™ depending on active setting.  An active connection to the control system/ShowRunnerCLC™ will be required if handled by ShowRunnerCLC™.
Mark Kohlmann 1.1 77 3 - [App Mode Only] Keypad Required
78 4 - [App Mode Only] 3 settings, On/Off and All Scenes Only, configured per load, max of 30 seconds