Zum Wired App Mode vs CNET Decision Guide

Last modified by Craig Lewis on 2026/04/08 20:33

Zum wired can be deployed in App (Zum) Mode or CNET Mode.  App mode will perform lighting control logic within the Zum JBOX hardware while CNET mode pushes all logic back to the Control System.  ShowRunnerCLC™ supports both modes and can be used to enhance app mode or allow complete control over the hardware to perform functionality.  All hardware does not need to be in app mode on a project.  You can mix and match as needed.  This is not an exhaustive list but serves as a guide for when Zum is required to be in CNET mode to achieve the desired functionality.

Due to technical complexities with firmware, Zum AutoSwitch is not recommended.  Either provision entirely in Zum App Mode or CNET Mode.

App Mode vs CNET Mode Breakdown

FeatureShowRunnerCLC™ w/ Zum App ModeShowRunnerCLC™ w/ Zum CNET ModeApp-Mode Only
Hardware 
Requires Active Connection to ProcessorFeature Dependent1,2YN
Max Zum Devices per room

ZUMNET-JBOX-DALI (v3.09 or earlier, CI recommends 3.06.20 or lower): 32
ZUMNET-JBOX-DALI (v3.10 or later): 7
ZUMNET-JBOX-16A-LV (v3.09 or earlier): 32
ZUMNET-JBOX-16A-LV (v3.10 or later): 14
ZUMNET-DIN-*: 32

32, can be expanded by adding additional ZUMNETs or DIN-CENCN-2sZUMNET-JBOX-DALI (v3.09 or earlier, CI recommends 3.06.20 or lower): 32
ZUMNET-JBOX-DALI (v3.10 or later): 7
ZUMNET-JBOX-16A-LV (v3.09 or earlier): 32
ZUMNET-JBOX-16A-LV (v3.10 or later): 14
ZUMNET-DIN-*: 32
Requires Keypad to Program App LogicYN/A, programmed in ShowRunnerCLC™Y
Crestron non-Zum Hardware IntegrationY1YN
Non-Crestron Hardware IntegrationY1YN
Multiple ZUMNET Masters in a Single RoomY1YN
More than One Room per ZUMNETNot Recommended, Requires Groups within App ModeYRequires Groups
Scheduling / Time ClockY1YZUMLINK-[DIN/JBOX]-IO per room or HUB4
Dynamic WhiteY1YN
DALI
Address and Discover DALI
ZUMNET-JBOX-DALI
ZUMNET-DIN-DLI

Zum App3
Zum App3

Toolbox/ShowRunnerCLC™
Not Supported, Only Supports App Mode [Use DIN-DLI for CNET]

Zum App3
Zum App3
DALI Type 8Y1YN
Scenes
Max Scenes

ShowRunnerCLC™: Unlimited
Local logic: 16 + Off

Unlimited16 + Off
Per Scene Fade TimesY1,2,4YPartial4
Loads
Min/Max TrimY2

Y

Min: 0-45%
Max: 55-100%

Dimming CurveY2YN
Unoccupied LevelY1YN
CCT / Dynamic WhiteY1YN
RGBY1YN
Occupancy Logic
Occupancy ModesY2YY
Grace TimeoutY1YN
Extended TimeoutY1YN
2 Stage VacancyY1YN
Keypads
Disable KeypadsY1YN
Custom Keypad ProgrammingY2YN
Room Logic  
After Hours / Auto TimeoutY1YN
Plug Load (Auto/On/Off)Y1YInternal behavior only
Recall Last LevelY1YN

Notes

1 - [App Mode Only] Logic must be handled by ShowRunnerCLC™.  An active connection to the control system/ShowRunnerCLC™ is required.
2 - [App Mode Only] Some logic may be handled by ShowRunnerCLC™ depending on active setting.  An active connection to the control system/ShowRunnerCLC™ will be required if handled by ShowRunnerCLC™.
3 - [App Mode Only] Keypad Required
4 - [App Mode Only] 3 settings, On/Off and All Scenes Only, configured per load, max of 30 seconds