Wiki source code of Zummesh Dynamic White/CCT

Last modified by Scott Kohlmann on 2023/04/21 14:09

Show last authors
1 Zum wireless supports dynamic white using DALI Groups 2,4,6,8,10,12,14,16 (1,3,5,7,9,11,13,15 for console purposes).  Setup must be performed manually on the NETBRIDGE.  Once done, ShowRunner can use the CCT channels to provide CCT data to the fixtures.  Input from ShowRunnerCLC™ requires setting the scene recall for the CCT group to 255.  Any value of 0-254 will be sent to the CCT channel directly and the input from ShowRunnerCLC™ will be ignored.
2
3 ==== Typical Setup for up to 6 zones, 5 fixture types: ====
4
5 (% border="1" style="width:600px" %)
6 |=DALI Group|=Name|=Fixture Type|=Control Type
7 |0|Downlights, Main|F0|Intensity
8 |1|Downlights, Main/Screen CCT|F0|Color
9 |2|Accent Lights|F1a|Intensity
10 |3|Accent Lights CCT|F1a|Color
11 |4|Spot Lights|F3|Intensity
12 |5|Spot Lights CCT|F3|Color
13 |6|Troffers|F4c|Intensity
14 |7|Troffers CCT|F4c|Color
15 |8|Linear|F9|Intensity
16 |9|Linear|F9|Color
17 |10|Downlights @ Screen|F0|Intensity
18 |11|-|-|Color
19 |12|-|-|Intensity
20 |13|-|-|Color
21 |14|-|-|Intensity
22 |15|-|-|Color
23
24 ==== Caveats: ====
25
26 * Only intensity/CCT fixtures are supported.  This will not work with warm/cool fixtures.
27 * NETBRIDGE must be attached to the ZUMMESH-JBOX-DALI.  Only 1 ZUMMESH-JBOX-DALI is supported per room.  Use Zum Wired or DIN-DALI-2 if more capabilities are needed.
28 * Supports up to 8 CCT channels, DALI Groups 2,4,6,8,10,12,14,16 (1,3,5,7,9,11,13,15 for console purposes)
29 * Zum Scene must have the CCT channel set to 255 to accept input from ShowRunner.  Values of 0-254 will be sent directly to the group as fixed colors.
30 * Setup must be done from the gateway console
31
32 ==== Setup Steps: ====
33
34 1. Address all DALI drivers attached to the JBOX.  This can be done via the gateway console or via the Zum app on iOS/Android.
35 Command: //rfrcon <**NetbridgeID**> DALIGLOBALADDRESS <**Action**>//
36 **Action**: 0=stop, 1=start, 3=get status
37 Example (NETBRIDGE RF-ID 1A): //rfrcon 1A DALIGLOBALADDRESS 1//
38 1. Create DALI Groups.  If group already exists then go to step 3. This must be done from the gateway console.
39 Command: //rfrcon <**NetbridgeID**> DALIGROUPADDDELETE <**GroupID**> <**Operation**> <**GroupName**>//
40 **GroupID: **0 to 15
41 **Operation:** 0=Delete Group, 1=Add Intensity Group, 3=Add Color Group
42 **GroupName: **Name of the group, no spaces, 16 characters max
43 Example (NETBRIDGE RF-ID 1A): //rfrcon 1A DALIGROUPADDDELETE 8 3 TypeF1-Color//
44 1. Modify DALI Group to color, only needed if step 2 was not done.  If step 2 was performed skip this step.
45 Command: //rfrcon <**NetbridgeID**> DALIGROUPSETTWRITE <**GroupID**> 14 <**GroupType**>//
46 **GroupID: **0 to 15
47 **GroupType:** 0=Intensity, 1=Color
48 Example: (NETBRIDGE RF-ID 1A): //rfrcon 1A DALIGROUPSETTWRITE 8 14 1//
49 1. Set Scene settings for Color Support.  Enables or uses a fixed value for color temperature on color groups.
50 Command: rfrcon <**NetbridgeID**> DALIGROUPCOMMAND 4 <**GroupID**> <**SceneID**> <**SceneLevel**> <**Action**> <**FadeTime**>
51 **GroupID**: 0 to 15 (odd for color)
52 **SceneID**: Scene number (1 to 16)
53 **SceneLevel**: 255 for ShowRunner control, 0-254 for fixed scene level
54 **Action**: 0=Remove Scene, 1=Add Scene