... ... @@ -8,7 +8,9 @@
8 8  {{/warning}}
9 9  
10 10  {{error}}
11 -All 4-Series processors require authentication to be configured when first connecting: **the Crestron Agent or Field Tech are responsible for recording these credentials. Chief Integrations cannot provide assistance unless the credentials are known. The only way to connect to a device for which the credentials have been lost is to [[factory reset>>https://docs.crestron.com/en-us/8559/Content/Topics/Reference/Restore-Factory-Defaults.htm]] the device, which may require redoing the start-up from scratch if the latest configuration was not saved and backed up. **
11 +Per Crestron's ZUM-HUB4 firmware v3.009.0039 release notes, updating to PUF versions 3.009.0039 or newer require first updating to PUF version 3.008.054. Failure to do so will result in longer ##progreset## times (up to 10 minutes) as well as other potential issues such as keypads becoming unresponsive.
12 +
13 +The PUF firmware version is can be viewed using the ##**ver -all**## command (PUF firmware version is different than the version displayed with just the ##**ver**## command)
12 12  {{/error}}
13 13  
14 14  {{error}}
... ... @@ -16,9 +16,7 @@
16 16  {{/error}}
17 17  
18 18  {{error}}
19 -Per Crestron's ZUM-HUB4 firmware v3.009.0039 release notes, updating to PUF versions 3.009.0039 or newer require first updating to PUF version 3.008.054. Failure to do so will result in longer ##progreset## times (up to 10 minutes) as well as other potential issues such as keypads becoming unresponsive.
20 -
21 -The PUF firmware version is can be viewed using the ##**ver -all**## command (PUF firmware version is different than the version displayed with just the ##**ver**## command)
21 +All 4-Series processors require authentication to be configured when first connecting: **the Crestron Agent or Field Tech are responsible for recording these credentials. Chief Integrations cannot provide assistance unless the credentials are known. The only way to connect to a device for which the credentials have been lost is to [[factory reset>>https://docs.crestron.com/en-us/8559/Content/Topics/Reference/Restore-Factory-Defaults.htm]] the device, which may require redoing the start-up from scratch if the latest configuration was not saved and backed up. **
22 22  {{/error}}
23 23  
24 24  {{box cssClass="floatinginfobox" title="**CONTENTS**"}}
... ... @@ -86,8 +86,9 @@
86 86  ***1. Be connected to the Control Subnet port
87 87  ***1*. Control Subnet must be configured correctly (see above)
88 88  ***1*. If lighting devices must be able to communicate with the building LAN, run the command: ##isolatenetworks off##
89 -* At this point, it is a good idea to [[update the device firmware>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.Updating Firmware.WebHome]]
90 90  
90 +{{display excludeFirstHeading="false" reference="SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.Processor Setup.WebHome" section="HFirmwareUpdate"/}}
91 +
91 91  = Update NVRAM Folder Permissions =
92 92  
93 93  * Ensure that the NVRAM folder permissions are set correctly using a third party SFTP program: