Changes for page ZUM-HUB4 Processor Setup

Last modified by Alexander Mott on 2026/03/04 22:05

From version 52.2
edited by Alexander Mott
on 2026/03/04 20:07
Change comment: There is no comment for this version
To version 56.1
edited by Alexander Mott
on 2026/03/04 22:05
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -2,8 +2,14 @@
2 2  This page is for ZUM-HUB4 deployments. For other processors, see our [[normal processor setup page>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.Processor Setup.WebHome]].
3 3  {{/info}}
4 4  
5 +{{warning}}
6 +ZUM-HUB4 requires **firmware v2.8000.00009 or greater** for third party software to be loaded.
7 +Text console "**##ver##**" command will give the current firmware version.
8 +{{/warning}}
9 +
5 5  {{error}}
6 -All 4-Series processors require authentication to be configured when first connecting: **the Crestron Agent or Field Tech are responsible for recording these credentials. Chief Integrations cannot provide assistance unless the credentials are known. The only way to connect to a device for which the credentials have been lost is to [[factory reset>>https://docs.crestron.com/en-us/8559/Content/Topics/Reference/Restore-Factory-Defaults.htm]] the device, which may require redoing the start-up from scratch if the latest configuration was not saved and backed up. **
11 +Per Crestron's ZUM-HUB4 firmware v3.009.0039 release notes, updating to PUF versions 3.009.0039 or newer require first updating to PUF version 3.008.054. Failure to do so will result in longer ##progreset## times (up to 10 minutes) as well as other potential issues such as keypads becoming unresponsive.
12 +The PUF firmware version is can be viewed using the ##**ver -all**## command (PUF firmware version is different than the version displayed with just the ##**ver**## command)
7 7  {{/error}}
8 8  
9 9  {{error}}
... ... @@ -11,16 +11,9 @@
11 11  {{/error}}
12 12  
13 13  {{error}}
14 -Per Crestron's ZUM-HUB4 firmware v3.009.0039 release notes, updating to PUF versions 3.009.0039 or newer require first updating to PUF version 3.008.054. Failure to do so will result in longer ##progreset## times (up to 10 minutes) as well as other potential issues such as keypads becoming unresponsive.
15 -
16 -The PUF firmware version is can be viewed using the ##**ver -all**## command (PUF firmware version is different than the version displayed with just the ##**ver**## command)
20 +All 4-Series processors require authentication to be configured when first connecting: **the Crestron Agent or Field Tech are responsible for recording these credentials. Chief Integrations cannot provide assistance unless the credentials are known. The only way to connect to a device for which the credentials have been lost is to [[factory reset>>https://docs.crestron.com/en-us/8559/Content/Topics/Reference/Restore-Factory-Defaults.htm]] the device, which may require redoing the start-up from scratch if the latest configuration was not saved and backed up. **
17 17  {{/error}}
18 18  
19 -{{warning}}
20 -ZUM-HUB4 requires firmware version **2.8000.00009 or greater** for third party software to be loaded.
21 -(Once installed, running the command should report a FW version of 2.8000.00009 or greater.)
22 -{{/warning}}
23 -
24 24  {{box cssClass="floatinginfobox" title="**CONTENTS**"}}
25 25  {{toc/}}
26 26  {{/box}}
... ... @@ -86,8 +86,9 @@
86 86  ***1. Be connected to the Control Subnet port
87 87  ***1*. Control Subnet must be configured correctly (see above)
88 88  ***1*. If lighting devices must be able to communicate with the building LAN, run the command: ##isolatenetworks off##
89 -* At this point, it is a good idea to [[update the device firmware>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.Updating Firmware.WebHome]]
90 90  
89 +{{display excludeFirstHeading="false" reference="SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.Processor Setup.WebHome" section="HFirmwareUpdate"/}}
90 +
91 91  = Update NVRAM Folder Permissions =
92 92  
93 93  * Ensure that the NVRAM folder permissions are set correctly using a third party SFTP program: