Changes for page ZUM-HUB4 Processor Setup

Last modified by Craig Lewis on 2025/03/13 15:50

From version 34.1
edited by Alexander Mott
on 2023/12/12 00:01
Change comment: There is no comment for this version
To version 35.1
edited by Alexander Mott
on 2024/03/27 15:36
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -39,6 +39,7 @@
39 39  ** Disable CWS Anti-CSRF feature (case sensitive): ##cwsanticsrf OFF##
40 40  ** Force waiting to start program: ##startprogafterrouter on##
41 41  ** Processor must be rebooted with "##reboot##" command before these take effect, but you can wait to reboot if there are other settings you must change that also require a reboot
42 +** ShowRunnerCLC™ .puf versions 3.042 and newer automatically run this command when the "Configure ZUM-HUB4" and "Reboot ZUM-HUB4" options are selected.
42 42  * Determine whether the lighting control hardware will be connected to the ZUM-HUB4's LAN port or the Control Subnet port:
43 43  ** If the system is standalone (not integrated with building LAN), then lighting hardware can be connected to either the LAN port or the Control Subnet port, but it is still recommended to use the Control Subnet for Crestron hardware as the ZUM-HUB4 has a router built-in that will assign IP addresses:
44 44  *** If connecting lighting hardware to the LAN port, then you must configure the LAN as a static IP (example is for a **10.0.0.0(% style="color:darkgoldenrod" %)/24(%%)** subnet, with a processor IP address of (% style="color:blue" %)**10.0.0.10**(%%)):
... ... @@ -57,6 +57,7 @@
57 57  **** Using Text Console commands (example for a **100.64.0.0(% style="color:darkgoldenrod" %)/20(%%)** subnet, with a processor IP address of (% style="color:blue" %)**100.64.0.1**(%%))
58 58  ***** Set CS IP: ##csrouterprefix **100.64.0.0/20**##
59 59  ***** Reboot the processor: ##reboot##
61 +**** ShowRunnerCLC™ .puf versions 3.042 and newer automatically run this command when the "Configure ZUM-HUB4 Control Subnet" and "Reboot ZUM-HUB4" options are selected.
60 60  ** If the system is intended to connect to the building LAN:
61 61  *** The building LAN must be connected to ZUM-HUB4's LAN port
62 62  *** The ZUM-HUB4's LAN IP settings should be configured per the building requirements
... ... @@ -65,6 +65,7 @@
65 65  ***1*. The ZUM-HUB4 LAN should be configured with a static IP or DHCP reservation
66 66  ***1*. Building network must be configured to allow communication between ZUM-HUB4 and all lighting devices
67 67  ***1*. Run the command: ##securegateway default##
70 +***1*. ShowRunnerCLC™ .puf versions 3.042 and newer automatically run this command when the "Configure ZUM-HUB4 SecureGateway" option is selected.
68 68  ***1. Be connected to the Control Subnet port
69 69  ***1*. Control Subnet must be configured correctly (see above)
70 70  ***1*. If lighting devices must be able to communicate with the building LAN, run the command: ##isolatenetworks off##