8 8  DIN-CENCN-2s are Cresnet-to-Ethernet bridges which convert data over the Cresnet bus into high-speed Ethernet traffic. This helps avoid issues with bandwidth over the Cresnet bus for jobs which have a large number of Cresnet devices, as well as allowing for additional power supplies to provide power Cresnet devices.
9 9  
... ... @@ -36,4 +36,3 @@
36 36  1. Cresnet IDs must be in the hexadecimal range 03 to 1B
37 37  1. Any children devices (such as NS occ sensors, photocells, GLPPA-KP keypads, etc.) must also be moved. If the parent Cresnet ID is changed then the children IDs must also be updated
38 38  1. If devices are moved from a DIN-CENCN-2 to be landed directly on a processor (or landed on a DIN-HUB on a processor), then the device host ID should be ##null## and the host branch should be ##0##