Changes for page DIN-CENCN-2 Setup

Last modified by Alexander Mott on 2024/02/09 01:01

From version 10.1
edited by Alexander Mott
on 2022/09/19 16:07
Change comment: There is no comment for this version
To version 1.1
edited by Alexander Mott
on 2022/06/13 21:08
Change comment: There is no comment for this version

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.WebHome
1 +SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.WebHome
Content
... ... @@ -1,15 +1,10 @@
1 -{{box cssClass="floatinginfobox" title="**CONTENTS**"}}
2 -{{toc/}}
3 -{{/box}}
1 +=== DIN-CENCN-2s in SHOWRUNNER™ ===
4 4  
5 -(% class="row" %)
6 -(((
7 -
8 8  DIN-CENCN-2s are Cresnet-to-Ethernet bridges which convert data over the Cresnet bus into high-speed Ethernet traffic. This helps avoid issues with bandwidth over the Cresnet bus for jobs which have a large number of Cresnet devices, as well as allowing for additional power supplies to provide power Cresnet devices.
9 9  
10 -For SHOWRUNNER™ installations, the IP address of the DIN-CENCN-2 does not matter as long as it is in the same range as the processor and does not conflict with any other devices on the network. Instead, DIN-CENCN-2s are identified to the processor via their IP-ID. Note that which Cresnet devices are landed at each Net of each DIN-CENCN-2 matters, and if devices are moved between Nets or between DIN-CENCN-2s then the configuration will need to be updated (see below). Chief Integrations typically provides an SRTakeoff.xlsx spreadsheet with an IP Table tab that lists all the DIN-CENCN-2 IP-IDs in the program. If no takeoff is provided, then the processor's IP table can be checked by running the ##ipt -t ##command from the processor after the configuration is loaded. DIN-CENCN-2's will typically have IP-IDs in the "##Dx##" range.
5 +For SHOWRUNNER™ installations, the IP address of the DIN-CENCN-2 does not matter as long as it is in the same range as the processor and does not conflict with any other devices on the network. Instead, DIN-CENCN-2s are identified to the processor via their IP-ID. Note that which Cresnet devices are landed at each Net of each DIN-CENCN-2 matters, and if devices are moved between Nets or between DIN-CENCN-2s then the configuration will need to be updated (see below). Chief Integrations will provide an SRTakeoff.xlsx spreadsheet with an IP Table tab that lists all the DIN-CENCN-2 IP-IDs in the program.
11 11  
12 -= IP Configuration =
7 +=== IP Configuration ===
13 13  
14 14  Typically, each DIN-CENCN-2 will need to be initially configured via USB, unless their MAC addresses are already known and the lighting network has a DHCP server (either by running DHCP server software on your computer, or if the processor has a control subnet or is running the [[SHOWRUNNER™ DHCP Server>>doc:SHOWRUNNER™ User Guide & Wiki.Troubleshooting.DHCP Server.WebHome]]).
15 15  
... ... @@ -17,7 +17,7 @@
17 17  
18 18  * Open Text Console in Toolbox and connect to the DIN-CENCN-2
19 19  * Run the following commands to configure the DIN-CENCN-2's IP settings (example is for a **10.0.0.0(% style="color:darkgoldenrod" %)/24(%%)** subnet, with a CENCN-2 IP address of (% style="color:blue" %)**10.0.0.12**(%%), a CENCN-2 IP-ID of (% style="color:olive" %)**D1**(%%), a processor IP address of (% style="color:orange" %)**10.0.0.10**(%%), and a hostname of (% style="color:purple" %)**CENCN-L1**(%%))
20 -** Disable DHCP: ##dhcp off##
15 +** Disable DHCP: ##dhcp 0 off##
21 21  ** Set IP address: ##ipa 0 (% style="color:blue" %)**10.0.0.12**(%%)##
22 22  ** Set IP subnet mask: ##ipm 0 (% style="color:darkgoldenrod" %)**255.255.255.0**(%%)##
23 23  ** Set default gateway: ##defr 0 **10.0.0.1**##
... ... @@ -26,7 +26,7 @@
26 26  ** Reboot the DIN-CENCN-2: ##reboot##
27 27  * Repeat for all DIN-CENCN-2s on the job
28 28  
29 -= Moving Cresnet Devices =
24 +=== Moving Cresnet Devices ===
30 30  
31 31  In SHOWRUNNER™, which Net each Cresnet cable is landed on is important. Each DIN-CENCN-2 is firmware limited to a maximum of 25 Cresnet devices per Net, and which CENCN-2/Net each device is on is tracked in the configuration file. If devices are moved between DIN-CENCN-2s or moved between Nets on the same DIN-CENCN-2, then the configuration file must be updated. Every device in the configuration has a ##"DeviceHostId"## (the host DIN-CENCN-2's IP-ID) and a ##"DeviceHostBranch"## (the Net of the DIN-CENCN-2) associated with it.
32 32  
... ... @@ -36,4 +36,3 @@
36 36  1. Cresnet IDs must be in the hexadecimal range 03 to 1B
37 37  1. Any children devices (such as NS occ sensors, photocells, GLPPA-KP keypads, etc.) must also be moved. If the parent Cresnet ID is changed then the children IDs must also be updated
38 38  1. If devices are moved from a DIN-CENCN-2 to be landed directly on a processor (or landed on a DIN-HUB on a processor), then the device host ID should be ##null## and the host branch should be ##0##
39 -)))