Wiki source code of Zūm Discovery

Version 9.1 by Alexander Mott on 2022/10/05 16:17

Hide last authors
Alexander Mott 1.1 1 (% class="box warningmessage" %)
2 (((
Alexander Mott 5.2 3 This article is about automatically building a SHOWRUNNER™ configuration using the Zūm Discovery feature of SHOWRUNNER™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Crestron Zūm App Overview.WebHome]].
Alexander Mott 1.1 4 For instructions on configuring Zūm Net devices using Crestron Toolbox, see [[this page>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.ZUMNET-JBOX Setup.WebHome]].
5 )))
6
7 {{box cssClass="floatinginfobox" title="**CONTENTS**"}}
8 {{toc/}}
9 {{/box}}
10
11 (% class="row" %)
12 (((
Alexander Mott 6.1 13 If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a SHOWRUNNER™ configuration file using the Zūm Discovery feature that is built into SHOWRUNNER™.
Alexander Mott 1.1 14
Alexander Mott 5.2 15 There are certain pre-requisites and limitations when building a SHOWRUNNER™ configuration this way, and it may sometimes be necessary make some adjustments to the final configuration, such as changing keypad types and moving loads between areas.
Alexander Mott 1.1 16
Alexander Mott 5.2 17 = Zūm Wired Discovery =
18
Alexander Mott 6.1 19 == Notes and Limitations ==
Alexander Mott 1.1 20
Alexander Mott 9.1 21 (% class="box errormessage" %)
22 (((
Alexander Mott 6.1 23 * SHOWRUNNER™ version 3.014 or newer required
Alexander Mott 6.2 24 * Zūm Wired firmware version 1.02.10 or greater required
25 * Disconnect from any ZUMNET devices you may be connected to in Toolbox prior to running the discovery commands
26 * Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release)
27 * One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually
Alexander Mott 9.1 28 )))
Alexander Mott 6.1 29
Alexander Mott 6.2 30 == Steps ==
31
Alexander Mott 7.1 32 1. [[Install SHOWRUNNER™>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.WebHome]] on the processor and configure the processor as necessary
33 1*. Note that while Zūm Wired discovery will build a configuration, if a configuration file was provided then it should still be loaded as it may contain location data or non-Zūm devices.
34 1. If the ZUMNET-JBOX firmware is too out-of-date to connect using the Crestron Zūm App, then there are some additional steps required: 
35 1*. Connect to the first ZUMNET-JBOX in Toolbox
36 1*. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
37 1**. Note: The SHOWRUNNER™ built-in DHCP server is not meant to be used in production
38 1**. If the SHOWRUNNER™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
39 1*. Set unique Connection IDs for each device hosted on the ZUMNET-JBOX so that their firmware can be updated
40 1*. Load the Zūm Wired firmware to the ZUMNET-JBOX
41 1*. Repeat the above steps for all ZUMNET-JBOXs
Alexander Mott 8.1 42 1*. Once all the ZUMNET-JBOXs have pushed the new firmware to their hosted devices, disconnect from them in Toolbox and proceed to the next step
Alexander Mott 7.1 43 1. Connect to first ZUMNET-JBOX in the Crestron Zūm App
44 1. Unique Connection IDs should be automatically assigned to any Zūm Link and Cresnet devices on the ZUMNET-JBOX
45 1*. If firmware was out-of-date, then this step should have already been completed
46 1*. If unique CIDs are not automatically assigned, connect to the JBOX in Toolbox and give the devices unique CIDs
47 1. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
48 1*. If firmware was out-of-date, then this step should have already been completed
49 1*. Note: The SHOWRUNNER™ built-in DHCP server is not meant to be used in production
50 1*. If the SHOWRUNNER™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
51 1. Optionally, manually configure the ZUMNET-JBOX IP table to point at the processor if you want to keep track of which ZUMNET-JBOX is at each IP-ID
52 1*. If you do not manually configure the IP table, then SHOWRUNNER™ will automatically configure the IP-ID for each ZUMNET-JBOX during discovery
53 1. Repeat from step 3 until all ZUMNET-JBOXs that are to be controlled by SHOWRUNNER™ have static IP addresses and unique CIDs for any hosted devices
Alexander Mott 8.1 54 1. Disconnect from any ZUMNET-JBOXs and then connect to the processor in Toolbox
55 1. Run the command: ##sr discover zumnet true false##
Alexander Mott 7.1 56 1*. This command tells SHOWRUNNER™ to discover all ZUMMNET-JBOXs on the network, configure their IP tables, and then add corresponding areas and loads to the configuration
57 1*. One area will be created per ZUMNET-JBOX
58 1. Run the command: ##sr discover zumnet true true##
59 1*. This command tells SHOWRUNNER™ to discover all Zūm Link hardware on the previously discovered Zūm Net devices
60 1*. This command **does not** bring in Cresnet devices: those must be added to the configuration manually until this issue is fixed in the Zūm Wired firmware
61 1. Put all ZUMNET-JBOXs into CNET mode in order to allow full control from SHOWRUNNER™
62 1*. Odd behavior may result from conflicts between SHOWRUNNER™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
Alexander Mott 6.2 63
Alexander Mott 5.2 64 = Zūm Wireless Discovery =
Alexander Mott 1.1 65
Alexander Mott 5.2 66 == Notes and Limitations ==
Alexander Mott 9.1 67 )))
Alexander Mott 1.1 68
Alexander Mott 9.1 69 (% class="box errormessage" %)
70 (((
Alexander Mott 6.1 71 * Processor with SHOWRUNNER™ version 2.190 or newer must be running on the same network as the gateway(s) to be acquired
Alexander Mott 9.1 72 ** For SHOWRUNNER™ versions prior to 3.014 and newer, replace **##sr discover zummesh##** commands with **##sr discover zum##**
Alexander Mott 6.1 73 * ZUM-NETBRIDGES must already be acquired to their respective gateway
74 * SHOWRUNNER™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices
75 * Disconnect from any RF gateways you may be connected to in Toolbox prior to running the discovery command
76 * Plug loads will not appear in the SHOWRUNNER™ UI
Alexander Mott 4.1 77 )))
Alexander Mott 1.1 78
Alexander Mott 3.1 79 (% class="box warningmessage" id="HCaution:" %)
80 (((
Alexander Mott 6.1 81 **Note:** SHOWRUNNER™ has two different approaches for Zūm Wireless Discovery
Alexander Mott 4.1 82
83 1. **Manual RF Gateway Assignment** - SHOWRUNNER™ can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
84 1. **Claim All RF Gateways** - SHOWRUNNER™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different SHOWRUNNER™ or other Crestron systems on the same local network.
Alexander Mott 3.1 85 )))
Alexander Mott 1.1 86
Alexander Mott 4.1 87 (% class="row" %)
88 (((
Alexander Mott 6.2 89 == Manual RF Gateway Assignment Instructions ==
Alexander Mott 1.1 90
Alexander Mott 5.1 91 Use this method if you have multiple SHOWRUNNER™ instances on the same network or have gateways used by other Crestron systems.
Alexander Mott 1.1 92
Alexander Mott 2.1 93 * Connect to the processor's console with Toolbox or your favorite SSH client.
Alexander Mott 9.1 94 * Type ##sr devmgr ethernet query## and press enter. This queries the local network for RF Gateways.
95 * Type ##sr devmgr ethernet show devices## and press enter. This displays all found Crestron ethernet devices.
96 * For each gateway that you'd like this instance of SHOWRUNNER™ to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type ##sr ethernet device claim CEN-GWEXER-9E6ADA##. SHOWRUNNER™ will auto-assign an IP-ID. After all gateways have been claimed by SHOWRUNNER™, proceed to the next step.
97 * Type ##sr discover zummesh false## and press enter.
Alexander Mott 5.1 98 * Status messages and the results will be displayed on the console. The process should take about 3 minutes.
Alexander Mott 9.1 99 * When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, SHOWRUNNER™ must be restarted to complete the acquire process.
100 * Type ##progreset## and press enter to restart SHOWRUNNER™
101 * Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. SHOWRUNNER™ will be able to acquire the loads attached to the Zūm rooms at this point.
Alexander Mott 5.1 102 * Once completed SHOWRUNNER™ is now ready for full Zūm control
Alexander Mott 2.1 103
Alexander Mott 6.2 104 == Claim All RF Gateways Instructions ==
Alexander Mott 2.1 105
Alexander Mott 5.1 106 Use this method when you have a single SHOWRUNNER™ instance on a local network with all gateways being used for SHOWRUNNER™.
Alexander Mott 2.1 107
108 * Connect to the processor's console with Toolbox or your favorite SSH client.
Alexander Mott 9.1 109 * Type ##sr discover zummesh true## and press enter.
Alexander Mott 5.1 110 * Status messages and the results will be displayed on the console. The process should take about 3 minutes.
Alexander Mott 9.1 111 * When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, SHOWRUNNER™ must be restarted to complete the acquire process.
112 * Type ##progreset## and press enter to restart SHOWRUNNER™
113 * Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. SHOWRUNNER™ will be able to acquire the loads attached to the Zūm rooms at this point.
Alexander Mott 5.1 114 * Once completed SHOWRUNNER™ is now ready for full Zūm control
Alexander Mott 2.1 115
116 == Examples ==
117
Alexander Mott 5.2 118 === Manual Example ===
Alexander Mott 4.1 119
120 {{{MC4>sr devmgr ethernet query
121 Ethrenet AutoDiscovery Result: AutoDiscoveryOperationSuccess
122 MC4>sr devmgr ethernet show devices
123
124 +--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
125 | Adapter | Hostname | IP Address | IP-ID | ID |
126 +--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
127 | EthernetLANAdapter | CI-SJC-CEN-CI3-1-COM3 | 10.44.5.20 | 00 | CEN-CI3-1-C3COM-3 [v1.1620.00000, #008436E2] type:1 |
128 +--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
129 | EthernetLANAdapter | SB-DIN-CENCN-2 | 10.44.5.81 | 00 | DIN-CENCN-2-POE [v1.3544.00006, #8AB25AA3] |
130 +--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
131 | EthernetLANAdapter | CEN-GWEXER-9E6ADA | 10.44.5.120 | 00 | CEN-GWEXER [v1.4230.00015, #848210AD] |
132 +--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
133
134 MC4>sr ethernet device claim CEN-GWEXER-9E6ADA
135 Claimed ethernet device: CEN-GWEXER-9E6ADA
136 MC4>Update request from IP-ID-30 in Program 01
Alexander Mott 9.1 137 MC4>sr discover zummesh false
Alexander Mott 4.1 138 Starting Zum Discovery without gateway claiming
139 MC4>Performing Discovery on 1 Gateways.
Alexander Mott 2.1 140 Evaluating 3 Devices on Gateway 30
141 Claiming ZUM-NETBRIDGE SN: 1726NEJ01096 from IP-ID: 30
142 Dev: ZUM-NETBRIDGE addrssing to RF ID: 03
143 Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 03
144 Claiming ZUM-NETBRIDGE SN: 1914NEJ03096 from IP-ID: 30
145 Dev: ZUM-NETBRIDGE addrssing to RF ID: 04
146 Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 04
147 Claiming ZUM-NETBRIDGE SN: 1914NEJ03098 from IP-ID: 30
148 Dev: ZUM-NETBRIDGE addrssing to RF ID: 05
149 Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 05
Alexander Mott 4.1 150 Querying cresnet
Alexander Mott 2.1 151 Discovering Zum Loads on 1 Gateways.
152 Discovering Zum Loads on 3 Devices.
153 NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0
154 Device: ZUM Netbridge 30:03 at 30:03 discovery result: .
155 NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0
156 Device: ZUM Netbridge 30:04 at 30:04 discovery result: .
157 NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0
158 Device: ZUM Netbridge 30:05 at 30:05 discovery result: .
159 RF Gateways: 0
160 RF Devices: 3
161 New Loads: 0
162 Modified Loads: 0
163 Removed Loads: 0
164 Zum Discovery Finished
165 MC4>sr save
166 Saved config
167 MC4>progreset
168 ...
169 CI ShowRunner startup completed successfully in 8072ms
Alexander Mott 9.1 170 MC4>sr discover zummesh false
Alexander Mott 2.1 171 Starting Zum Discovery without gateway claiming
172 MC4>Notice: SimplSharpPro[App01] # 2020-07-21 22:19:46 # Recalling startup scenes (if applicable)
173 Performing Discovery on 1 Gateways.
174 Evaluating 3 Devices on Gateway 30
175 Claiming ZUM-NETBRIDGE SN: 1726NEJ01096 from IP-ID: 30
176 Dev: ZUMMESH-NETBRIDGE already claimed at RF ID: 03
177 Claiming ZUM-NETBRIDGE SN: 1914NEJ03096 from IP-ID: 30
178 Dev: ZUMMESH-NETBRIDGE already claimed at RF ID: 04
179 Claiming ZUM-NETBRIDGE SN: 1914NEJ03098 from IP-ID: 30
180 Dev: ZUMMESH-NETBRIDGE already claimed at RF ID: 05
181 Discovering Zum Loads on 1 Gateways.
182 Discovering Zum Loads on 3 Devices.
183 Evaluating Device: ZUM-BLE ShortAddress: FFFA Type: BLERadio
184 Evaluating Device: ZUM-JBOX-20A-PLUG ShortAddress: 0000 Type: PlugLoad
185 Evaluating Device: ZUM-KP10C-BATT ShortAddress: 52E5 Type: Keypad
186 Evaluating Device: ZUM-PIR-OCC-BATT ShortAddress: DAF1 Type: OccupancySensor
187 Evaluating Device: ZUM-JBOX-5A-LV ShortAddress: 92EF Type: DimmableLoad
188 Load: Load37615 Added
189 NETBIRDGE: NewLoads: 1 ModifiedLoads: 0 RemovedLoads: 0
190 Device: ZUM Netbridge 30:03 at 30:03 discovery result: .
191 Evaluating Device: ZUM-BLE ShortAddress: FFFA Type: BLERadio
192 Evaluating Device: ZUM-DALI ShortAddress: 740D Type: Unknown
193 Evaluating Device: ZUM-5A-LV ShortAddress: 0482 Type: DimmableLoad
194 Load: Load1154 Added
195 Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: 0000 Type: DimmableLoad
196 Load: Load0 Added
197 Evaluating Device: ZUM-KP10C-BATT ShortAddress: D766 Type: Keypad
198 Evaluating Device: ZUM-OL-PHO-BATT ShortAddress: 95ED Type: Photocell
199 Evaluating Device: ZUM-PIR-OCC-BATT ShortAddress: 44C2 Type: OccupancySensor
200 Evaluating Device: ZUM-DALI-GROUP ShortAddress: 740D Type: Unknown
201 Evaluating Device: ZUM-DALI-GROUP ShortAddress: 740D Type: Unknown
202 NETBIRDGE: NewLoads: 2 ModifiedLoads: 0 RemovedLoads: 0
203 Device: ZUM Netbridge 30:04 at 30:04 discovery result: .
204 Evaluating Device: ZUM-BLE ShortAddress: FFFA Type: BLERadio
205 Evaluating Device: ZUM-SIM ShortAddress: 0000 Type: OccupancySensor, PartitionSensor
206 Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: EBCF Type: DimmableLoad
207 Load: Load60367 Added
208 Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: 3CC1 Type: DimmableLoad
209 Load: Load15553 Added
210 Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: F94A Type: DimmableLoad
211 Load: Load63818 Added
212 NETBIRDGE: NewLoads: 3 ModifiedLoads: 0 RemovedLoads: 0
213 Device: ZUM Netbridge 30:05 at 30:05 discovery result: .
214 RF Gateways: 0
215 RF Devices: 3
216 New Loads: 6
217 Modified Loads: 0
218 Removed Loads: 0
Alexander Mott 4.1 219 Zum Discovery Finished}}}
Alexander Mott 2.1 220
Alexander Mott 5.1 221 === Claim All Example ===
Alexander Mott 2.1 222
Alexander Mott 9.1 223 {{{MC4>sr discover zummesh true
Alexander Mott 4.1 224 Starting Zum Discovery with gateway claiming
225 MC4>Found 1 Gateways to check.
226 Claimed Gateway SN: 1720JBH04269 at IP-ID: 30
227 Update request from IP-ID-30 in Program 01
228 Claimed 1 Gateways. Waiting for queries to finish.
229 Performing Discovery on 1 Gateways.
Alexander Mott 2.1 230 Evaluating 3 Devices on Gateway 30
231 Claiming ZUM-NETBRIDGE SN: 1726NEJ01096 from IP-ID: 30
232 Dev: ZUM-NETBRIDGE addrssing to RF ID: 03
233 Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 03
234 Claiming ZUM-NETBRIDGE SN: 1914NEJ03096 from IP-ID: 30
235 Dev: ZUM-NETBRIDGE addrssing to RF ID: 04
236 Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 04
237 Claiming ZUM-NETBRIDGE SN: 1914NEJ03098 from IP-ID: 30
238 Dev: ZUM-NETBRIDGE addrssing to RF ID: 05
239 Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 05
240 Discovering Zum Loads on 1 Gateways.
241 Discovering Zum Loads on 3 Devices.
242 NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0
243 Device: ZUM Netbridge 30:03 at 30:03 discovery result: .
244 NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0
245 Device: ZUM Netbridge 30:04 at 30:04 discovery result: .
246 NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0
247 Device: ZUM Netbridge 30:05 at 30:05 discovery result: .
248 RF Gateways: 0
249 RF Devices: 3
250 New Loads: 0
251 Modified Loads: 0
252 Removed Loads: 0
253 Zum Discovery Finished
254 MC4>sr save
255 Saved config
256 MC4>progreset
257 ...
258 CI ShowRunner startup completed successfully in 8072ms
Alexander Mott 9.1 259 MC4>sr discover zummesh false
Alexander Mott 2.1 260 Starting Zum Discovery without gateway claiming
261 MC4>Notice: SimplSharpPro[App01] # 2020-07-21 22:19:46 # Recalling startup scenes (if applicable)
262 Performing Discovery on 1 Gateways.
263 Evaluating 3 Devices on Gateway 30
264 Claiming ZUM-NETBRIDGE SN: 1726NEJ01096 from IP-ID: 30
265 Dev: ZUMMESH-NETBRIDGE already claimed at RF ID: 03
266 Claiming ZUM-NETBRIDGE SN: 1914NEJ03096 from IP-ID: 30
267 Dev: ZUMMESH-NETBRIDGE already claimed at RF ID: 04
268 Claiming ZUM-NETBRIDGE SN: 1914NEJ03098 from IP-ID: 30
269 Dev: ZUMMESH-NETBRIDGE already claimed at RF ID: 05
270 Discovering Zum Loads on 1 Gateways.
271 Discovering Zum Loads on 3 Devices.
272 Evaluating Device: ZUM-BLE ShortAddress: FFFA Type: BLERadio
273 Evaluating Device: ZUM-JBOX-20A-PLUG ShortAddress: 0000 Type: PlugLoad
274 Evaluating Device: ZUM-KP10C-BATT ShortAddress: 52E5 Type: Keypad
275 Evaluating Device: ZUM-PIR-OCC-BATT ShortAddress: DAF1 Type: OccupancySensor
276 Evaluating Device: ZUM-JBOX-5A-LV ShortAddress: 92EF Type: DimmableLoad
277 Load: Load37615 Added
278 NETBIRDGE: NewLoads: 1 ModifiedLoads: 0 RemovedLoads: 0
279 Device: ZUM Netbridge 30:03 at 30:03 discovery result: .
280 Evaluating Device: ZUM-BLE ShortAddress: FFFA Type: BLERadio
281 Evaluating Device: ZUM-DALI ShortAddress: 740D Type: Unknown
282 Evaluating Device: ZUM-5A-LV ShortAddress: 0482 Type: DimmableLoad
283 Load: Load1154 Added
284 Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: 0000 Type: DimmableLoad
285 Load: Load0 Added
286 Evaluating Device: ZUM-KP10C-BATT ShortAddress: D766 Type: Keypad
287 Evaluating Device: ZUM-OL-PHO-BATT ShortAddress: 95ED Type: Photocell
288 Evaluating Device: ZUM-PIR-OCC-BATT ShortAddress: 44C2 Type: OccupancySensor
289 Evaluating Device: ZUM-DALI-GROUP ShortAddress: 740D Type: Unknown
290 Evaluating Device: ZUM-DALI-GROUP ShortAddress: 740D Type: Unknown
291 NETBIRDGE: NewLoads: 2 ModifiedLoads: 0 RemovedLoads: 0
292 Device: ZUM Netbridge 30:04 at 30:04 discovery result: .
293 Evaluating Device: ZUM-BLE ShortAddress: FFFA Type: BLERadio
294 Evaluating Device: ZUM-SIM ShortAddress: 0000 Type: OccupancySensor, PartitionSensor
295 Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: EBCF Type: DimmableLoad
296 Load: Load60367 Added
297 Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: 3CC1 Type: DimmableLoad
298 Load: Load15553 Added
299 Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: F94A Type: DimmableLoad
300 Load: Load63818 Added
301 NETBIRDGE: NewLoads: 3 ModifiedLoads: 0 RemovedLoads: 0
302 Device: ZUM Netbridge 30:05 at 30:05 discovery result: .
303 RF Gateways: 0
304 RF Devices: 3
305 New Loads: 6
306 Modified Loads: 0
307 Removed Loads: 0
308 Zum Discovery Finished
Alexander Mott 4.1 309 }}}
Alexander Mott 1.1 310 )))