2 (((
Alexander Mott 23.1 3 **IMPORTANT:** When using ShowRunnerCLC™ with a ZUM-HUB4, **do not** discover Zūm Rooms using the Crestron HUB4 Web UI. During discovery, the HUB4 will claim ZUMNET-JBOXs and prevent ShowRunnerCLC™ from auto-discovering or registering the Zūm hardware for itself.
4
Alexander Mott 22.1 5 **WARNING:** Cresnet Discovery is non-functional for ZUMNET-JBOXs with certain versions of Crestron Device Database.
6 ShowRunnerCLC™ versions v3.019 through v3.041 must be either downgraded to v3.018 or upgraded to v3.042 or newer in order to perform auto-discover functions.
Alexander Mott 15.1 7 )))
Alexander Mott 16.1 8
Alexander Mott 1.1 9 (% class="box warningmessage" %)
10 (((
Alexander Mott 24.1 11 This article is about automatically building a ShowRunnerCLC™ configuration using the Zūm Discovery feature of ShowRunnerCLC™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Preparation.Zūm App Overview.WebHome]].
Alexander Mott 1.1 12 For instructions on configuring Zūm Net devices using Crestron Toolbox, see [[this page>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.ZUMNET-JBOX Setup.WebHome]].
13 )))
14
15 {{box cssClass="floatinginfobox" title="**CONTENTS**"}}
16 {{toc/}}
17 {{/box}}
18
Scott Kohlmann 19.1 19 If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a ShowRunnerCLC™ configuration file using the Zūm Discovery feature that is built into ShowRunnerCLC™.
Alexander Mott 1.1 20
Scott Kohlmann 19.1 21 There are certain pre-requisites and limitations when building a ShowRunnerCLC™ configuration this way, and it may sometimes be necessary make some adjustments to the final configuration, such as changing keypad types and moving loads between areas.
Alexander Mott 1.1 22
Alexander Mott 5.2 23 = Zūm Wired Discovery =
24
Alexander Mott 6.1 25 == Notes and Limitations ==
Alexander Mott 1.1 26
Alexander Mott 15.1 27 (% class="box warningmessage" %)
Alexander Mott 9.1 28 (((
Scott Kohlmann 19.1 29 * ShowRunnerCLC™ version 3.014 or newer required
Alexander Mott 13.1 30 * Zūm Wired firmware .puf version 1.02.10 or greater required (ZUMNET-JBOX installed minimum version 1.001.00081)
Craig Lewis 30.1 31 * Disconnect from any ZUMNET devices you may be connected to in Toolbox and confirm all hardware (NETs and LINKs) are online prior to running the discovery commands
Alexander Mott 6.2 32 * Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release)
Craig Lewis 31.1 33 * ZUMLINK-IOs will not be discovered (Expected to be discoverable in future ShowRunnerCLC™ release)
Craig Lewis 32.1 34 * ZUMLINK-KPs will not be discovered on older versions of ShowRunnerCLC™ (v3.058 or newer will discover keypads and set as remote type)
Alexander Mott 6.2 35 * One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually
Alexander Mott 9.1 36 )))
Alexander Mott 6.1 37
Alexander Mott 6.2 38 == Steps ==
39
Scott Kohlmann 19.1 40 1. [[Install ShowRunner™>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.WebHome]] on the processor and configure the processor as necessary
Alexander Mott 7.1 41 1*. Note that while Zūm Wired discovery will build a configuration, if a configuration file was provided then it should still be loaded as it may contain location data or non-Zūm devices.
42 1. If the ZUMNET-JBOX firmware is too out-of-date to connect using the Crestron Zūm App, then there are some additional steps required: 
43 1*. Connect to the first ZUMNET-JBOX in Toolbox
44 1*. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
Scott Kohlmann 19.1 45 1**. Note: The ShowRunnerCLC™ built-in DHCP server is not meant to be used in production
46 1**. If the ShowRunnerCLC™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
Alexander Mott 7.1 47 1*. Set unique Connection IDs for each device hosted on the ZUMNET-JBOX so that their firmware can be updated
48 1*. Load the Zūm Wired firmware to the ZUMNET-JBOX
49 1*. Repeat the above steps for all ZUMNET-JBOXs
Alexander Mott 8.1 50 1*. Once all the ZUMNET-JBOXs have pushed the new firmware to their hosted devices, disconnect from them in Toolbox and proceed to the next step
Craig Lewis 24.2 51 1. Connect to each ZUMNET-JBOX in the Crestron Zūm App
52 1*. Commission room through the app
53 1**. configure keypad logic
54 1**. configure occupancy sensor settings
55 1**. calibrate photocell(s)
Craig Lewis 24.3 56 1*. Set hostnames for the ZUMNETs.
57 1**. Zūm discovery will bring in hostnames.
Alexander Mott 7.1 58 1. Unique Connection IDs should be automatically assigned to any Zūm Link and Cresnet devices on the ZUMNET-JBOX
59 1*. If firmware was out-of-date, then this step should have already been completed
60 1*. If unique CIDs are not automatically assigned, connect to the JBOX in Toolbox and give the devices unique CIDs
61 1. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
62 1*. If firmware was out-of-date, then this step should have already been completed
Scott Kohlmann 19.1 63 1*. Note: The ShowRunnerCLC™ built-in DHCP server is not meant to be used in production
64 1*. If the ShowRunnerCLC™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
Alexander Mott 7.1 65 1. Optionally, manually configure the ZUMNET-JBOX IP table to point at the processor if you want to keep track of which ZUMNET-JBOX is at each IP-ID
66 1*. If you do not manually configure the IP table, then SHOWRUNNER™ will automatically configure the IP-ID for each ZUMNET-JBOX during discovery
Alexander Mott 13.1 67 1. Set the ZUMNET-JBOX into either Zūm ("App") mode or CNET mode as required for the program
Scott Kohlmann 19.1 68 1*. Full control from ShowRunnerCLC™ is only possible if all ZUMNET-JBOXs are in CNET mode. Odd behavior may result from conflicts between ShowRunnerCLC™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
69 1. Repeat from step 3 until all ZUMNET-JBOXs that are to be controlled by ShowRunnerCLC™ have static IP addresses and unique CIDs for any hosted devices
Alexander Mott 8.1 70 1. Disconnect from any ZUMNET-JBOXs and then connect to the processor in Toolbox
71 1. Run the command: ##sr discover zumnet true false##
Scott Kohlmann 19.1 72 1*. This command tells ShowRunnerCLC™ to discover all ZUMMNET-JBOXs on the network, configure their IP tables, and then add corresponding IP Devices to the configuration
Alexander Mott 7.1 73 1. Run the command: ##sr discover zumnet true true##
Scott Kohlmann 19.1 74 1*. This command tells ShowRunnerCLC™ to discover all Zūm Link hardware (including the internal ZUMNET-JBOX load controller) on the previously discovered Zūm Net devices and then add corresponding areas, loads, sensors, etc. to the configuration
Alexander Mott 12.1 75 1**. One area will be created per ZUMNET-JBOX, and all hardware attached to that ZUMNET-JBOX will be assigned to that area
Alexander Mott 7.1 76 1*. This command **does not** bring in Cresnet devices: those must be added to the configuration manually until this issue is fixed in the Zūm Wired firmware
Alexander Mott 14.1 77 1. If all steps have been performed successfully, then you should be able to use the ##sr show area##, ##sr show load##, ##sr show keypad##, and ##sr show occ## commands to see that the ZUMNET and ZUMLINK hardware has been discovered correctly.
Alexander Mott 6.2 78
Alexander Mott 5.2 79 = Zūm Wireless Discovery =
Alexander Mott 1.1 80
Alexander Mott 5.2 81 == Notes and Limitations ==
Alexander Mott 1.1 82
Alexander Mott 16.2 83 (% class="box warningmessage" %)
Alexander Mott 9.1 84 (((
Scott Kohlmann 19.1 85 * Processor with ShowRunnerCLC™ version 2.190 or newer must be running on the same network as the gateway(s) to be acquired
86 ** For ShowRunnerCLC™ versions prior to 3.014 and newer, replace **##sr discover zummesh##** commands with **##sr discover zum##**
Alexander Mott 6.1 87 * ZUM-NETBRIDGES must already be acquired to their respective gateway
Scott Kohlmann 19.1 88 * ShowRunnerCLC™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices
Alexander Mott 6.1 89 * Disconnect from any RF gateways you may be connected to in Toolbox prior to running the discovery command
Scott Kohlmann 19.1 90 * Plug loads will not appear in the ShowRunnerCLC™ UI
Austin Weygandt 28.1 91 * Newer GWEXER firmware enables SSL by default. Follow the instructions at [[SSL User Configuration>>doc:SHOWRUNNER™ User Guide & Wiki.SHOWRUNNER™ Appendix.SSL User Configuration.WebHome]] and manually add the IP Table entries on the GWEXER
Alexander Mott 4.1 92 )))
Alexander Mott 1.1 93
Alexander Mott 16.2 94 (% class="box infomessage" id="HCaution:" %)
Alexander Mott 3.1 95 (((
Scott Kohlmann 19.1 96 **Note:** ShowRunnerCLC™ has two different approaches for Zūm Wireless Discovery
Alexander Mott 4.1 97
Scott Kohlmann 19.1 98 1. **Manual RF Gateway Assignment** - ShowRunnerCLC™ can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
99 1. **Claim All RF Gateways** - ShowRunnerCLC™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different ShowRunnerCLC™ or other Crestron systems on the same local network.
Alexander Mott 3.1 100 )))
Alexander Mott 1.1 101
Alexander Mott 6.2 102 == Manual RF Gateway Assignment Instructions ==
Alexander Mott 1.1 103
Scott Kohlmann 19.1 104 Use this method if you have multiple ShowRunnerCLC™ instances on the same network or have gateways used by other Crestron systems.
Alexander Mott 1.1 105
Alexander Mott 2.1 106 * Connect to the processor's console with Toolbox or your favorite SSH client.
Alexander Mott 9.1 107 * Type ##sr devmgr ethernet query## and press enter. This queries the local network for RF Gateways.
108 * Type ##sr devmgr ethernet show devices## and press enter. This displays all found Crestron ethernet devices.
Scott Kohlmann 19.1 109 * For each gateway that you'd like this instance of SHOWRUNNER™ to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type ##sr ethernet device claim CEN-GWEXER-9E6ADA##. ShowRunnerCLC™ will auto-assign an IP-ID. After all gateways have been claimed by ShowRunnerCLC™, proceed to the next step.
Alexander Mott 9.1 110 * Type ##sr discover zummesh false## and press enter.
Alexander Mott 5.1 111 * Status messages and the results will be displayed on the console. The process should take about 3 minutes.
Scott Kohlmann 19.1 112 * When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunnerCLC™ must be restarted to complete the acquire process.
113 * Type ##progreset## and press enter to restart ShowRunnerCLC™
114 * Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. ShowRunnerCLC™ will be able to acquire the loads attached to the Zūm rooms at this point.
Alexander Mott 5.1 115 * Once completed SHOWRUNNER™ is now ready for full Zūm control
Alexander Mott 2.1 116
Alexander Mott 6.2 117 == Claim All RF Gateways Instructions ==
Alexander Mott 2.1 118
Scott Kohlmann 19.1 119 Use this method when you have a single ShowRunnerCLC™ instance on a local network with all gateways being used for ShowRunnerCLC™.
Alexander Mott 2.1 120
121 * Connect to the processor's console with Toolbox or your favorite SSH client.
Alexander Mott 9.1 122 * Type ##sr discover zummesh true## and press enter.
Alexander Mott 5.1 123 * Status messages and the results will be displayed on the console. The process should take about 3 minutes.
Scott Kohlmann 19.1 124 * When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunnerCLC™ must be restarted to complete the acquire process.
125 * Type ##progreset## and press enter to restart ShowRunnerCLC™
126 * Once ShowRunnerCLC™ has finished restarting type ##sr discover zummesh false## and press enter. ShowRunnerCLC™ will be able to acquire the loads attached to the Zūm rooms at this point.
127 * Once completed ShowRunnerCLC™ is now ready for full Zūm control
Alexander Mott 2.1 128
129 == Examples ==
130
Alexander Mott 5.2 131 === Manual Example ===
Alexander Mott 4.1 132
133 {{{MC4>sr devmgr ethernet query
134 Ethrenet AutoDiscovery Result: AutoDiscoveryOperationSuccess
135 MC4>sr devmgr ethernet show devices
136
137 +--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
138 | Adapter | Hostname | IP Address | IP-ID | ID |
139 +--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
140 | EthernetLANAdapter | CI-SJC-CEN-CI3-1-COM3 | 10.44.5.20 | 00 | CEN-CI3-1-C3COM-3 [v1.1620.00000, #008436E2] type:1 |
141 +--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
142 | EthernetLANAdapter | SB-DIN-CENCN-2 | 10.44.5.81 | 00 | DIN-CENCN-2-POE [v1.3544.00006, #8AB25AA3] |
143 +--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
144 | EthernetLANAdapter | CEN-GWEXER-9E6ADA | 10.44.5.120 | 00 | CEN-GWEXER [v1.4230.00015, #848210AD] |
145 +--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
146
147 MC4>sr ethernet device claim CEN-GWEXER-9E6ADA
148 Claimed ethernet device: CEN-GWEXER-9E6ADA
149 MC4>Update request from IP-ID-30 in Program 01
Alexander Mott 9.1 150 MC4>sr discover zummesh false
Alexander Mott 4.1 151 Starting Zum Discovery without gateway claiming
152 MC4>Performing Discovery on 1 Gateways.
Alexander Mott 2.1 153 Evaluating 3 Devices on Gateway 30
154 Claiming ZUM-NETBRIDGE SN: 1726NEJ01096 from IP-ID: 30
155 Dev: ZUM-NETBRIDGE addrssing to RF ID: 03
156 Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 03
157 Claiming ZUM-NETBRIDGE SN: 1914NEJ03096 from IP-ID: 30
158 Dev: ZUM-NETBRIDGE addrssing to RF ID: 04
159 Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 04
160 Claiming ZUM-NETBRIDGE SN: 1914NEJ03098 from IP-ID: 30
161 Dev: ZUM-NETBRIDGE addrssing to RF ID: 05
162 Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 05
Alexander Mott 4.1 163 Querying cresnet
Alexander Mott 2.1 164 Discovering Zum Loads on 1 Gateways.
165 Discovering Zum Loads on 3 Devices.
166 NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0
167 Device: ZUM Netbridge 30:03 at 30:03 discovery result: .
168 NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0
169 Device: ZUM Netbridge 30:04 at 30:04 discovery result: .
170 NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0
171 Device: ZUM Netbridge 30:05 at 30:05 discovery result: .
172 RF Gateways: 0
173 RF Devices: 3
174 New Loads: 0
175 Modified Loads: 0
176 Removed Loads: 0
177 Zum Discovery Finished
178 MC4>sr save
179 Saved config
180 MC4>progreset
181 ...
182 CI ShowRunner startup completed successfully in 8072ms
Alexander Mott 9.1 183 MC4>sr discover zummesh false
Alexander Mott 2.1 184 Starting Zum Discovery without gateway claiming
185 MC4>Notice: SimplSharpPro[App01] # 2020-07-21 22:19:46 # Recalling startup scenes (if applicable)
186 Performing Discovery on 1 Gateways.
187 Evaluating 3 Devices on Gateway 30
188 Claiming ZUM-NETBRIDGE SN: 1726NEJ01096 from IP-ID: 30
189 Dev: ZUMMESH-NETBRIDGE already claimed at RF ID: 03
190 Claiming ZUM-NETBRIDGE SN: 1914NEJ03096 from IP-ID: 30
191 Dev: ZUMMESH-NETBRIDGE already claimed at RF ID: 04
192 Claiming ZUM-NETBRIDGE SN: 1914NEJ03098 from IP-ID: 30
193 Dev: ZUMMESH-NETBRIDGE already claimed at RF ID: 05
194 Discovering Zum Loads on 1 Gateways.
195 Discovering Zum Loads on 3 Devices.
196 Evaluating Device: ZUM-BLE ShortAddress: FFFA Type: BLERadio
197 Evaluating Device: ZUM-JBOX-20A-PLUG ShortAddress: 0000 Type: PlugLoad
198 Evaluating Device: ZUM-KP10C-BATT ShortAddress: 52E5 Type: Keypad
199 Evaluating Device: ZUM-PIR-OCC-BATT ShortAddress: DAF1 Type: OccupancySensor
200 Evaluating Device: ZUM-JBOX-5A-LV ShortAddress: 92EF Type: DimmableLoad
201 Load: Load37615 Added
202 NETBIRDGE: NewLoads: 1 ModifiedLoads: 0 RemovedLoads: 0
203 Device: ZUM Netbridge 30:03 at 30:03 discovery result: .
204 Evaluating Device: ZUM-BLE ShortAddress: FFFA Type: BLERadio
205 Evaluating Device: ZUM-DALI ShortAddress: 740D Type: Unknown
206 Evaluating Device: ZUM-5A-LV ShortAddress: 0482 Type: DimmableLoad
207 Load: Load1154 Added
208 Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: 0000 Type: DimmableLoad
209 Load: Load0 Added
210 Evaluating Device: ZUM-KP10C-BATT ShortAddress: D766 Type: Keypad
211 Evaluating Device: ZUM-OL-PHO-BATT ShortAddress: 95ED Type: Photocell
212 Evaluating Device: ZUM-PIR-OCC-BATT ShortAddress: 44C2 Type: OccupancySensor
213 Evaluating Device: ZUM-DALI-GROUP ShortAddress: 740D Type: Unknown
214 Evaluating Device: ZUM-DALI-GROUP ShortAddress: 740D Type: Unknown
215 NETBIRDGE: NewLoads: 2 ModifiedLoads: 0 RemovedLoads: 0
216 Device: ZUM Netbridge 30:04 at 30:04 discovery result: .
217 Evaluating Device: ZUM-BLE ShortAddress: FFFA Type: BLERadio
218 Evaluating Device: ZUM-SIM ShortAddress: 0000 Type: OccupancySensor, PartitionSensor
219 Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: EBCF Type: DimmableLoad
220 Load: Load60367 Added
221 Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: 3CC1 Type: DimmableLoad
222 Load: Load15553 Added
223 Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: F94A Type: DimmableLoad
224 Load: Load63818 Added
225 NETBIRDGE: NewLoads: 3 ModifiedLoads: 0 RemovedLoads: 0
226 Device: ZUM Netbridge 30:05 at 30:05 discovery result: .
227 RF Gateways: 0
228 RF Devices: 3
229 New Loads: 6
230 Modified Loads: 0
231 Removed Loads: 0
Alexander Mott 4.1 232 Zum Discovery Finished}}}
Alexander Mott 2.1 233
Alexander Mott 5.1 234 === Claim All Example ===
Alexander Mott 2.1 235
Alexander Mott 9.1 236 {{{MC4>sr discover zummesh true
Alexander Mott 4.1 237 Starting Zum Discovery with gateway claiming
238 MC4>Found 1 Gateways to check.
239 Claimed Gateway SN: 1720JBH04269 at IP-ID: 30
240 Update request from IP-ID-30 in Program 01
241 Claimed 1 Gateways. Waiting for queries to finish.
242 Performing Discovery on 1 Gateways.
Alexander Mott 2.1 243 Evaluating 3 Devices on Gateway 30
244 Claiming ZUM-NETBRIDGE SN: 1726NEJ01096 from IP-ID: 30
245 Dev: ZUM-NETBRIDGE addrssing to RF ID: 03
246 Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 03
247 Claiming ZUM-NETBRIDGE SN: 1914NEJ03096 from IP-ID: 30
248 Dev: ZUM-NETBRIDGE addrssing to RF ID: 04
249 Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 04
250 Claiming ZUM-NETBRIDGE SN: 1914NEJ03098 from IP-ID: 30
251 Dev: ZUM-NETBRIDGE addrssing to RF ID: 05
252 Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 05
253 Discovering Zum Loads on 1 Gateways.
254 Discovering Zum Loads on 3 Devices.
255 NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0
256 Device: ZUM Netbridge 30:03 at 30:03 discovery result: .
257 NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0
258 Device: ZUM Netbridge 30:04 at 30:04 discovery result: .
259 NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0
260 Device: ZUM Netbridge 30:05 at 30:05 discovery result: .
261 RF Gateways: 0
262 RF Devices: 3
263 New Loads: 0
264 Modified Loads: 0
265 Removed Loads: 0
266 Zum Discovery Finished
267 MC4>sr save
268 Saved config
269 MC4>progreset
270 ...
271 CI ShowRunner startup completed successfully in 8072ms
Alexander Mott 9.1 272 MC4>sr discover zummesh false
Alexander Mott 2.1 273 Starting Zum Discovery without gateway claiming
274 MC4>Notice: SimplSharpPro[App01] # 2020-07-21 22:19:46 # Recalling startup scenes (if applicable)
275 Performing Discovery on 1 Gateways.
276 Evaluating 3 Devices on Gateway 30
277 Claiming ZUM-NETBRIDGE SN: 1726NEJ01096 from IP-ID: 30
278 Dev: ZUMMESH-NETBRIDGE already claimed at RF ID: 03
279 Claiming ZUM-NETBRIDGE SN: 1914NEJ03096 from IP-ID: 30
280 Dev: ZUMMESH-NETBRIDGE already claimed at RF ID: 04
281 Claiming ZUM-NETBRIDGE SN: 1914NEJ03098 from IP-ID: 30
282 Dev: ZUMMESH-NETBRIDGE already claimed at RF ID: 05
283 Discovering Zum Loads on 1 Gateways.
284 Discovering Zum Loads on 3 Devices.
285 Evaluating Device: ZUM-BLE ShortAddress: FFFA Type: BLERadio
286 Evaluating Device: ZUM-JBOX-20A-PLUG ShortAddress: 0000 Type: PlugLoad
287 Evaluating Device: ZUM-KP10C-BATT ShortAddress: 52E5 Type: Keypad
288 Evaluating Device: ZUM-PIR-OCC-BATT ShortAddress: DAF1 Type: OccupancySensor
289 Evaluating Device: ZUM-JBOX-5A-LV ShortAddress: 92EF Type: DimmableLoad
290 Load: Load37615 Added
291 NETBIRDGE: NewLoads: 1 ModifiedLoads: 0 RemovedLoads: 0
292 Device: ZUM Netbridge 30:03 at 30:03 discovery result: .
293 Evaluating Device: ZUM-BLE ShortAddress: FFFA Type: BLERadio
294 Evaluating Device: ZUM-DALI ShortAddress: 740D Type: Unknown
295 Evaluating Device: ZUM-5A-LV ShortAddress: 0482 Type: DimmableLoad
296 Load: Load1154 Added
297 Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: 0000 Type: DimmableLoad
298 Load: Load0 Added
299 Evaluating Device: ZUM-KP10C-BATT ShortAddress: D766 Type: Keypad
300 Evaluating Device: ZUM-OL-PHO-BATT ShortAddress: 95ED Type: Photocell
301 Evaluating Device: ZUM-PIR-OCC-BATT ShortAddress: 44C2 Type: OccupancySensor
302 Evaluating Device: ZUM-DALI-GROUP ShortAddress: 740D Type: Unknown
303 Evaluating Device: ZUM-DALI-GROUP ShortAddress: 740D Type: Unknown
304 NETBIRDGE: NewLoads: 2 ModifiedLoads: 0 RemovedLoads: 0
305 Device: ZUM Netbridge 30:04 at 30:04 discovery result: .
306 Evaluating Device: ZUM-BLE ShortAddress: FFFA Type: BLERadio
307 Evaluating Device: ZUM-SIM ShortAddress: 0000 Type: OccupancySensor, PartitionSensor
308 Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: EBCF Type: DimmableLoad
309 Load: Load60367 Added
310 Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: 3CC1 Type: DimmableLoad
311 Load: Load15553 Added
312 Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: F94A Type: DimmableLoad
313 Load: Load63818 Added
314 NETBIRDGE: NewLoads: 3 ModifiedLoads: 0 RemovedLoads: 0
315 Device: ZUM Netbridge 30:05 at 30:05 discovery result: .
316 RF Gateways: 0
317 RF Devices: 3
318 New Loads: 6
319 Modified Loads: 0