Wiki source code of Zūm Discovery
Version 31.1 by Craig Lewis on 2024/09/30 17:35
Hide last authors
| author | version | line-number | content |
|---|---|---|---|
| |
15.1 | 1 | (% class="box errormessage" %) |
| 2 | ((( | ||
| |
23.1 | 3 | **IMPORTANT:** When using ShowRunnerCLC™ with a ZUM-HUB4, **do not** discover Zūm Rooms using the Crestron HUB4 Web UI. During discovery, the HUB4 will claim ZUMNET-JBOXs and prevent ShowRunnerCLC™ from auto-discovering or registering the Zūm hardware for itself. |
| 4 | |||
| |
22.1 | 5 | **WARNING:** Cresnet Discovery is non-functional for ZUMNET-JBOXs with certain versions of Crestron Device Database. |
| 6 | ShowRunnerCLC™ versions v3.019 through v3.041 must be either downgraded to v3.018 or upgraded to v3.042 or newer in order to perform auto-discover functions. | ||
| |
15.1 | 7 | ))) |
| |
16.1 | 8 | |
| |
1.1 | 9 | (% class="box warningmessage" %) |
| 10 | ((( | ||
| |
24.1 | 11 | This article is about automatically building a ShowRunnerCLC™ configuration using the Zūm Discovery feature of ShowRunnerCLC™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Preparation.Zūm App Overview.WebHome]]. |
| |
1.1 | 12 | For instructions on configuring Zūm Net devices using Crestron Toolbox, see [[this page>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.ZUMNET-JBOX Setup.WebHome]]. |
| 13 | ))) | ||
| 14 | |||
| 15 | {{box cssClass="floatinginfobox" title="**CONTENTS**"}} | ||
| 16 | {{toc/}} | ||
| 17 | {{/box}} | ||
| 18 | |||
| |
19.1 | 19 | If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a ShowRunnerCLC™ configuration file using the Zūm Discovery feature that is built into ShowRunnerCLC™. |
| |
1.1 | 20 | |
| |
19.1 | 21 | There are certain pre-requisites and limitations when building a ShowRunnerCLC™ configuration this way, and it may sometimes be necessary make some adjustments to the final configuration, such as changing keypad types and moving loads between areas. |
| |
1.1 | 22 | |
| |
5.2 | 23 | = Zūm Wired Discovery = |
| 24 | |||
| |
6.1 | 25 | == Notes and Limitations == |
| |
1.1 | 26 | |
| |
15.1 | 27 | (% class="box warningmessage" %) |
| |
9.1 | 28 | ((( |
| |
19.1 | 29 | * ShowRunnerCLC™ version 3.014 or newer required |
| |
13.1 | 30 | * Zūm Wired firmware .puf version 1.02.10 or greater required (ZUMNET-JBOX installed minimum version 1.001.00081) |
| |
30.1 | 31 | * Disconnect from any ZUMNET devices you may be connected to in Toolbox and confirm all hardware (NETs and LINKs) are online prior to running the discovery commands |
| |
6.2 | 32 | * Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release) |
| |
31.1 | 33 | * ZUMLINK-IOs will not be discovered (Expected to be discoverable in future ShowRunnerCLC™ release) |
| |
30.1 | 34 | * ZUMLINK-KPs will not be discovered on older versions of ShowRunnerCLC™ (v3.058 or newer) |
| |
6.2 | 35 | * One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually |
| |
9.1 | 36 | ))) |
| |
6.1 | 37 | |
| |
6.2 | 38 | == Steps == |
| 39 | |||
| |
19.1 | 40 | 1. [[Install ShowRunner™>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.WebHome]] on the processor and configure the processor as necessary |
| |
7.1 | 41 | 1*. Note that while Zūm Wired discovery will build a configuration, if a configuration file was provided then it should still be loaded as it may contain location data or non-Zūm devices. |
| 42 | 1. If the ZUMNET-JBOX firmware is too out-of-date to connect using the Crestron Zūm App, then there are some additional steps required: | ||
| 43 | 1*. Connect to the first ZUMNET-JBOX in Toolbox | ||
| 44 | 1*. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network | ||
| |
19.1 | 45 | 1**. Note: The ShowRunnerCLC™ built-in DHCP server is not meant to be used in production |
| 46 | 1**. If the ShowRunnerCLC™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses | ||
| |
7.1 | 47 | 1*. Set unique Connection IDs for each device hosted on the ZUMNET-JBOX so that their firmware can be updated |
| 48 | 1*. Load the Zūm Wired firmware to the ZUMNET-JBOX | ||
| 49 | 1*. Repeat the above steps for all ZUMNET-JBOXs | ||
| |
8.1 | 50 | 1*. Once all the ZUMNET-JBOXs have pushed the new firmware to their hosted devices, disconnect from them in Toolbox and proceed to the next step |
| |
24.2 | 51 | 1. Connect to each ZUMNET-JBOX in the Crestron Zūm App |
| 52 | 1*. Commission room through the app | ||
| 53 | 1**. configure keypad logic | ||
| 54 | 1**. configure occupancy sensor settings | ||
| 55 | 1**. calibrate photocell(s) | ||
| |
24.3 | 56 | 1*. Set hostnames for the ZUMNETs. |
| 57 | 1**. Zūm discovery will bring in hostnames. | ||
| |
7.1 | 58 | 1. Unique Connection IDs should be automatically assigned to any Zūm Link and Cresnet devices on the ZUMNET-JBOX |
| 59 | 1*. If firmware was out-of-date, then this step should have already been completed | ||
| 60 | 1*. If unique CIDs are not automatically assigned, connect to the JBOX in Toolbox and give the devices unique CIDs | ||
| 61 | 1. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network | ||
| 62 | 1*. If firmware was out-of-date, then this step should have already been completed | ||
| |
19.1 | 63 | 1*. Note: The ShowRunnerCLC™ built-in DHCP server is not meant to be used in production |
| 64 | 1*. If the ShowRunnerCLC™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses | ||
| |
7.1 | 65 | 1. Optionally, manually configure the ZUMNET-JBOX IP table to point at the processor if you want to keep track of which ZUMNET-JBOX is at each IP-ID |
| 66 | 1*. If you do not manually configure the IP table, then SHOWRUNNER™ will automatically configure the IP-ID for each ZUMNET-JBOX during discovery | ||
| |
13.1 | 67 | 1. Set the ZUMNET-JBOX into either Zūm ("App") mode or CNET mode as required for the program |
| |
19.1 | 68 | 1*. Full control from ShowRunnerCLC™ is only possible if all ZUMNET-JBOXs are in CNET mode. Odd behavior may result from conflicts between ShowRunnerCLC™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode |
| 69 | 1. Repeat from step 3 until all ZUMNET-JBOXs that are to be controlled by ShowRunnerCLC™ have static IP addresses and unique CIDs for any hosted devices | ||
| |
8.1 | 70 | 1. Disconnect from any ZUMNET-JBOXs and then connect to the processor in Toolbox |
| 71 | 1. Run the command: ##sr discover zumnet true false## | ||
| |
19.1 | 72 | 1*. This command tells ShowRunnerCLC™ to discover all ZUMMNET-JBOXs on the network, configure their IP tables, and then add corresponding IP Devices to the configuration |
| |
7.1 | 73 | 1. Run the command: ##sr discover zumnet true true## |
| |
19.1 | 74 | 1*. This command tells ShowRunnerCLC™ to discover all Zūm Link hardware (including the internal ZUMNET-JBOX load controller) on the previously discovered Zūm Net devices and then add corresponding areas, loads, sensors, etc. to the configuration |
| |
12.1 | 75 | 1**. One area will be created per ZUMNET-JBOX, and all hardware attached to that ZUMNET-JBOX will be assigned to that area |
| |
7.1 | 76 | 1*. This command **does not** bring in Cresnet devices: those must be added to the configuration manually until this issue is fixed in the Zūm Wired firmware |
| |
14.1 | 77 | 1. If all steps have been performed successfully, then you should be able to use the ##sr show area##, ##sr show load##, ##sr show keypad##, and ##sr show occ## commands to see that the ZUMNET and ZUMLINK hardware has been discovered correctly. |
| |
6.2 | 78 | |
| |
5.2 | 79 | = Zūm Wireless Discovery = |
| |
1.1 | 80 | |
| |
5.2 | 81 | == Notes and Limitations == |
| |
1.1 | 82 | |
| |
16.2 | 83 | (% class="box warningmessage" %) |
| |
9.1 | 84 | ((( |
| |
19.1 | 85 | * Processor with ShowRunnerCLC™ version 2.190 or newer must be running on the same network as the gateway(s) to be acquired |
| 86 | ** For ShowRunnerCLC™ versions prior to 3.014 and newer, replace **##sr discover zummesh##** commands with **##sr discover zum##** | ||
| |
6.1 | 87 | * ZUM-NETBRIDGES must already be acquired to their respective gateway |
| |
19.1 | 88 | * ShowRunnerCLC™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices |
| |
6.1 | 89 | * Disconnect from any RF gateways you may be connected to in Toolbox prior to running the discovery command |
| |
19.1 | 90 | * Plug loads will not appear in the ShowRunnerCLC™ UI |
| |
28.1 | 91 | * Newer GWEXER firmware enables SSL by default. Follow the instructions at [[SSL User Configuration>>doc:SHOWRUNNER™ User Guide & Wiki.SHOWRUNNER™ Appendix.SSL User Configuration.WebHome]] and manually add the IP Table entries on the GWEXER |
| |
4.1 | 92 | ))) |
| |
1.1 | 93 | |
| |
16.2 | 94 | (% class="box infomessage" id="HCaution:" %) |
| |
3.1 | 95 | ((( |
| |
19.1 | 96 | **Note:** ShowRunnerCLC™ has two different approaches for Zūm Wireless Discovery |
| |
4.1 | 97 | |
| |
19.1 | 98 | 1. **Manual RF Gateway Assignment** - ShowRunnerCLC™ can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network. |
| 99 | 1. **Claim All RF Gateways** - ShowRunnerCLC™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different ShowRunnerCLC™ or other Crestron systems on the same local network. | ||
| |
3.1 | 100 | ))) |
| |
1.1 | 101 | |
| |
6.2 | 102 | == Manual RF Gateway Assignment Instructions == |
| |
1.1 | 103 | |
| |
19.1 | 104 | Use this method if you have multiple ShowRunnerCLC™ instances on the same network or have gateways used by other Crestron systems. |
| |
1.1 | 105 | |
| |
2.1 | 106 | * Connect to the processor's console with Toolbox or your favorite SSH client. |
| |
9.1 | 107 | * Type ##sr devmgr ethernet query## and press enter. This queries the local network for RF Gateways. |
| 108 | * Type ##sr devmgr ethernet show devices## and press enter. This displays all found Crestron ethernet devices. | ||
| |
19.1 | 109 | * For each gateway that you'd like this instance of SHOWRUNNER™ to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type ##sr ethernet device claim CEN-GWEXER-9E6ADA##. ShowRunnerCLC™ will auto-assign an IP-ID. After all gateways have been claimed by ShowRunnerCLC™, proceed to the next step. |
| |
9.1 | 110 | * Type ##sr discover zummesh false## and press enter. |
| |
5.1 | 111 | * Status messages and the results will be displayed on the console. The process should take about 3 minutes. |
| |
19.1 | 112 | * When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunnerCLC™ must be restarted to complete the acquire process. |
| 113 | * Type ##progreset## and press enter to restart ShowRunnerCLC™ | ||
| 114 | * Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. ShowRunnerCLC™ will be able to acquire the loads attached to the Zūm rooms at this point. | ||
| |
5.1 | 115 | * Once completed SHOWRUNNER™ is now ready for full Zūm control |
| |
2.1 | 116 | |
| |
6.2 | 117 | == Claim All RF Gateways Instructions == |
| |
2.1 | 118 | |
| |
19.1 | 119 | Use this method when you have a single ShowRunnerCLC™ instance on a local network with all gateways being used for ShowRunnerCLC™. |
| |
2.1 | 120 | |
| 121 | * Connect to the processor's console with Toolbox or your favorite SSH client. | ||
| |
9.1 | 122 | * Type ##sr discover zummesh true## and press enter. |
| |
5.1 | 123 | * Status messages and the results will be displayed on the console. The process should take about 3 minutes. |
| |
19.1 | 124 | * When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunnerCLC™ must be restarted to complete the acquire process. |
| 125 | * Type ##progreset## and press enter to restart ShowRunnerCLC™ | ||
| 126 | * Once ShowRunnerCLC™ has finished restarting type ##sr discover zummesh false## and press enter. ShowRunnerCLC™ will be able to acquire the loads attached to the Zūm rooms at this point. | ||
| 127 | * Once completed ShowRunnerCLC™ is now ready for full Zūm control | ||
| |
2.1 | 128 | |
| 129 | == Examples == | ||
| 130 | |||
| |
5.2 | 131 | === Manual Example === |
| |
4.1 | 132 | |
| 133 | {{{MC4>sr devmgr ethernet query | ||
| 134 | Ethrenet AutoDiscovery Result: AutoDiscoveryOperationSuccess | ||
| 135 | MC4>sr devmgr ethernet show devices | ||
| 136 | |||
| 137 | +--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+ | ||
| 138 | | Adapter | Hostname | IP Address | IP-ID | ID | | ||
| 139 | +--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+ | ||
| 140 | | EthernetLANAdapter | CI-SJC-CEN-CI3-1-COM3 | 10.44.5.20 | 00 | CEN-CI3-1-C3COM-3 [v1.1620.00000, #008436E2] type:1 | | ||
| 141 | +--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+ | ||
| 142 | | EthernetLANAdapter | SB-DIN-CENCN-2 | 10.44.5.81 | 00 | DIN-CENCN-2-POE [v1.3544.00006, #8AB25AA3] | | ||
| 143 | +--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+ | ||
| 144 | | EthernetLANAdapter | CEN-GWEXER-9E6ADA | 10.44.5.120 | 00 | CEN-GWEXER [v1.4230.00015, #848210AD] | | ||
| 145 | +--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+ | ||
| 146 | |||
| 147 | MC4>sr ethernet device claim CEN-GWEXER-9E6ADA | ||
| 148 | Claimed ethernet device: CEN-GWEXER-9E6ADA | ||
| 149 | MC4>Update request from IP-ID-30 in Program 01 | ||
| |
9.1 | 150 | MC4>sr discover zummesh false |
| |
4.1 | 151 | Starting Zum Discovery without gateway claiming |
| 152 | MC4>Performing Discovery on 1 Gateways. | ||
| |
2.1 | 153 | Evaluating 3 Devices on Gateway 30 |
| 154 | Claiming ZUM-NETBRIDGE SN: 1726NEJ01096 from IP-ID: 30 | ||
| 155 | Dev: ZUM-NETBRIDGE addrssing to RF ID: 03 | ||
| 156 | Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 03 | ||
| 157 | Claiming ZUM-NETBRIDGE SN: 1914NEJ03096 from IP-ID: 30 | ||
| 158 | Dev: ZUM-NETBRIDGE addrssing to RF ID: 04 | ||
| 159 | Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 04 | ||
| 160 | Claiming ZUM-NETBRIDGE SN: 1914NEJ03098 from IP-ID: 30 | ||
| 161 | Dev: ZUM-NETBRIDGE addrssing to RF ID: 05 | ||
| 162 | Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 05 | ||
| |
4.1 | 163 | Querying cresnet |
| |
2.1 | 164 | Discovering Zum Loads on 1 Gateways. |
| 165 | Discovering Zum Loads on 3 Devices. | ||
| 166 | NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0 | ||
| 167 | Device: ZUM Netbridge 30:03 at 30:03 discovery result: . | ||
| 168 | NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0 | ||
| 169 | Device: ZUM Netbridge 30:04 at 30:04 discovery result: . | ||
| 170 | NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0 | ||
| 171 | Device: ZUM Netbridge 30:05 at 30:05 discovery result: . | ||
| 172 | RF Gateways: 0 | ||
| 173 | RF Devices: 3 | ||
| 174 | New Loads: 0 | ||
| 175 | Modified Loads: 0 | ||
| 176 | Removed Loads: 0 | ||
| 177 | Zum Discovery Finished | ||
| 178 | MC4>sr save | ||
| 179 | Saved config | ||
| 180 | MC4>progreset | ||
| 181 | ... | ||
| 182 | CI ShowRunner startup completed successfully in 8072ms | ||
| |
9.1 | 183 | MC4>sr discover zummesh false |
| |
2.1 | 184 | Starting Zum Discovery without gateway claiming |
| 185 | MC4>Notice: SimplSharpPro[App01] # 2020-07-21 22:19:46 # Recalling startup scenes (if applicable) | ||
| 186 | Performing Discovery on 1 Gateways. | ||
| 187 | Evaluating 3 Devices on Gateway 30 | ||
| 188 | Claiming ZUM-NETBRIDGE SN: 1726NEJ01096 from IP-ID: 30 | ||
| 189 | Dev: ZUMMESH-NETBRIDGE already claimed at RF ID: 03 | ||
| 190 | Claiming ZUM-NETBRIDGE SN: 1914NEJ03096 from IP-ID: 30 | ||
| 191 | Dev: ZUMMESH-NETBRIDGE already claimed at RF ID: 04 | ||
| 192 | Claiming ZUM-NETBRIDGE SN: 1914NEJ03098 from IP-ID: 30 | ||
| 193 | Dev: ZUMMESH-NETBRIDGE already claimed at RF ID: 05 | ||
| 194 | Discovering Zum Loads on 1 Gateways. | ||
| 195 | Discovering Zum Loads on 3 Devices. | ||
| 196 | Evaluating Device: ZUM-BLE ShortAddress: FFFA Type: BLERadio | ||
| 197 | Evaluating Device: ZUM-JBOX-20A-PLUG ShortAddress: 0000 Type: PlugLoad | ||
| 198 | Evaluating Device: ZUM-KP10C-BATT ShortAddress: 52E5 Type: Keypad | ||
| 199 | Evaluating Device: ZUM-PIR-OCC-BATT ShortAddress: DAF1 Type: OccupancySensor | ||
| 200 | Evaluating Device: ZUM-JBOX-5A-LV ShortAddress: 92EF Type: DimmableLoad | ||
| 201 | Load: Load37615 Added | ||
| 202 | NETBIRDGE: NewLoads: 1 ModifiedLoads: 0 RemovedLoads: 0 | ||
| 203 | Device: ZUM Netbridge 30:03 at 30:03 discovery result: . | ||
| 204 | Evaluating Device: ZUM-BLE ShortAddress: FFFA Type: BLERadio | ||
| 205 | Evaluating Device: ZUM-DALI ShortAddress: 740D Type: Unknown | ||
| 206 | Evaluating Device: ZUM-5A-LV ShortAddress: 0482 Type: DimmableLoad | ||
| 207 | Load: Load1154 Added | ||
| 208 | Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: 0000 Type: DimmableLoad | ||
| 209 | Load: Load0 Added | ||
| 210 | Evaluating Device: ZUM-KP10C-BATT ShortAddress: D766 Type: Keypad | ||
| 211 | Evaluating Device: ZUM-OL-PHO-BATT ShortAddress: 95ED Type: Photocell | ||
| 212 | Evaluating Device: ZUM-PIR-OCC-BATT ShortAddress: 44C2 Type: OccupancySensor | ||
| 213 | Evaluating Device: ZUM-DALI-GROUP ShortAddress: 740D Type: Unknown | ||
| 214 | Evaluating Device: ZUM-DALI-GROUP ShortAddress: 740D Type: Unknown | ||
| 215 | NETBIRDGE: NewLoads: 2 ModifiedLoads: 0 RemovedLoads: 0 | ||
| 216 | Device: ZUM Netbridge 30:04 at 30:04 discovery result: . | ||
| 217 | Evaluating Device: ZUM-BLE ShortAddress: FFFA Type: BLERadio | ||
| 218 | Evaluating Device: ZUM-SIM ShortAddress: 0000 Type: OccupancySensor, PartitionSensor | ||
| 219 | Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: EBCF Type: DimmableLoad | ||
| 220 | Load: Load60367 Added | ||
| 221 | Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: 3CC1 Type: DimmableLoad | ||
| 222 | Load: Load15553 Added | ||
| 223 | Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: F94A Type: DimmableLoad | ||
| 224 | Load: Load63818 Added | ||
| 225 | NETBIRDGE: NewLoads: 3 ModifiedLoads: 0 RemovedLoads: 0 | ||
| 226 | Device: ZUM Netbridge 30:05 at 30:05 discovery result: . | ||
| 227 | RF Gateways: 0 | ||
| 228 | RF Devices: 3 | ||
| 229 | New Loads: 6 | ||
| 230 | Modified Loads: 0 | ||
| 231 | Removed Loads: 0 | ||
| |
4.1 | 232 | Zum Discovery Finished}}} |
| |
2.1 | 233 | |
| |
5.1 | 234 | === Claim All Example === |
| |
2.1 | 235 | |
| |
9.1 | 236 | {{{MC4>sr discover zummesh true |
| |
4.1 | 237 | Starting Zum Discovery with gateway claiming |
| 238 | MC4>Found 1 Gateways to check. | ||
| 239 | Claimed Gateway SN: 1720JBH04269 at IP-ID: 30 | ||
| 240 | Update request from IP-ID-30 in Program 01 | ||
| 241 | Claimed 1 Gateways. Waiting for queries to finish. | ||
| 242 | Performing Discovery on 1 Gateways. | ||
| |
2.1 | 243 | Evaluating 3 Devices on Gateway 30 |
| 244 | Claiming ZUM-NETBRIDGE SN: 1726NEJ01096 from IP-ID: 30 | ||
| 245 | Dev: ZUM-NETBRIDGE addrssing to RF ID: 03 | ||
| 246 | Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 03 | ||
| 247 | Claiming ZUM-NETBRIDGE SN: 1914NEJ03096 from IP-ID: 30 | ||
| 248 | Dev: ZUM-NETBRIDGE addrssing to RF ID: 04 | ||
| 249 | Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 04 | ||
| 250 | Claiming ZUM-NETBRIDGE SN: 1914NEJ03098 from IP-ID: 30 | ||
| 251 | Dev: ZUM-NETBRIDGE addrssing to RF ID: 05 | ||
| 252 | Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 05 | ||
| 253 | Discovering Zum Loads on 1 Gateways. | ||
| 254 | Discovering Zum Loads on 3 Devices. | ||
| 255 | NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0 | ||
| 256 | Device: ZUM Netbridge 30:03 at 30:03 discovery result: . | ||
| 257 | NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0 | ||
| 258 | Device: ZUM Netbridge 30:04 at 30:04 discovery result: . | ||
| 259 | NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0 | ||
| 260 | Device: ZUM Netbridge 30:05 at 30:05 discovery result: . | ||
| 261 | RF Gateways: 0 | ||
| 262 | RF Devices: 3 | ||
| 263 | New Loads: 0 | ||
| 264 | Modified Loads: 0 | ||
| 265 | Removed Loads: 0 | ||
| 266 | Zum Discovery Finished | ||
| 267 | MC4>sr save | ||
| 268 | Saved config | ||
| 269 | MC4>progreset | ||
| 270 | ... | ||
| 271 | CI ShowRunner startup completed successfully in 8072ms | ||
| |
9.1 | 272 | MC4>sr discover zummesh false |
| |
2.1 | 273 | Starting Zum Discovery without gateway claiming |
| 274 | MC4>Notice: SimplSharpPro[App01] # 2020-07-21 22:19:46 # Recalling startup scenes (if applicable) | ||
| 275 | Performing Discovery on 1 Gateways. | ||
| 276 | Evaluating 3 Devices on Gateway 30 | ||
| 277 | Claiming ZUM-NETBRIDGE SN: 1726NEJ01096 from IP-ID: 30 | ||
| 278 | Dev: ZUMMESH-NETBRIDGE already claimed at RF ID: 03 | ||
| 279 | Claiming ZUM-NETBRIDGE SN: 1914NEJ03096 from IP-ID: 30 | ||
| 280 | Dev: ZUMMESH-NETBRIDGE already claimed at RF ID: 04 | ||
| 281 | Claiming ZUM-NETBRIDGE SN: 1914NEJ03098 from IP-ID: 30 | ||
| 282 | Dev: ZUMMESH-NETBRIDGE already claimed at RF ID: 05 | ||
| 283 | Discovering Zum Loads on 1 Gateways. | ||
| 284 | Discovering Zum Loads on 3 Devices. | ||
| 285 | Evaluating Device: ZUM-BLE ShortAddress: FFFA Type: BLERadio | ||
| 286 | Evaluating Device: ZUM-JBOX-20A-PLUG ShortAddress: 0000 Type: PlugLoad | ||
| 287 | Evaluating Device: ZUM-KP10C-BATT ShortAddress: 52E5 Type: Keypad | ||
| 288 | Evaluating Device: ZUM-PIR-OCC-BATT ShortAddress: DAF1 Type: OccupancySensor | ||
| 289 | Evaluating Device: ZUM-JBOX-5A-LV ShortAddress: 92EF Type: DimmableLoad | ||
| 290 | Load: Load37615 Added | ||
| 291 | NETBIRDGE: NewLoads: 1 ModifiedLoads: 0 RemovedLoads: 0 | ||
| 292 | Device: ZUM Netbridge 30:03 at 30:03 discovery result: . | ||
| 293 | Evaluating Device: ZUM-BLE ShortAddress: FFFA Type: BLERadio | ||
| 294 | Evaluating Device: ZUM-DALI ShortAddress: 740D Type: Unknown | ||
| 295 | Evaluating Device: ZUM-5A-LV ShortAddress: 0482 Type: DimmableLoad | ||
| 296 | Load: Load1154 Added | ||
| 297 | Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: 0000 Type: DimmableLoad | ||
| 298 | Load: Load0 Added | ||
| 299 | Evaluating Device: ZUM-KP10C-BATT ShortAddress: D766 Type: Keypad | ||
| 300 | Evaluating Device: ZUM-OL-PHO-BATT ShortAddress: 95ED Type: Photocell | ||
| 301 | Evaluating Device: ZUM-PIR-OCC-BATT ShortAddress: 44C2 Type: OccupancySensor | ||
| 302 | Evaluating Device: ZUM-DALI-GROUP ShortAddress: 740D Type: Unknown | ||
| 303 | Evaluating Device: ZUM-DALI-GROUP ShortAddress: 740D Type: Unknown | ||
| 304 | NETBIRDGE: NewLoads: 2 ModifiedLoads: 0 RemovedLoads: 0 | ||
| 305 | Device: ZUM Netbridge 30:04 at 30:04 discovery result: . | ||
| 306 | Evaluating Device: ZUM-BLE ShortAddress: FFFA Type: BLERadio | ||
| 307 | Evaluating Device: ZUM-SIM ShortAddress: 0000 Type: OccupancySensor, PartitionSensor | ||
| 308 | Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: EBCF Type: DimmableLoad | ||
| 309 | Load: Load60367 Added | ||
| 310 | Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: 3CC1 Type: DimmableLoad | ||
| 311 | Load: Load15553 Added | ||
| 312 | Evaluating Device: ZUM-JBOX-16A-LV ShortAddress: F94A Type: DimmableLoad | ||
| 313 | Load: Load63818 Added | ||
| 314 | NETBIRDGE: NewLoads: 3 ModifiedLoads: 0 RemovedLoads: 0 | ||
| 315 | Device: ZUM Netbridge 30:05 at 30:05 discovery result: . | ||
| 316 | RF Gateways: 0 | ||
| 317 | RF Devices: 3 | ||
| 318 | New Loads: 6 | ||
| 319 | Modified Loads: 0 | ||
| 320 | Removed Loads: 0 | ||
| 321 | Zum Discovery Finished | ||
| |
4.1 | 322 | }}} |