Changes for page Zūm Discovery

Last modified by Austin Weygandt on 2025/05/02 20:21

From version 9.1
edited by Alexander Mott
on 2022/10/05 16:17
Change comment: There is no comment for this version
To version 3.1
edited by Alexander Mott
on 2022/09/22 21:47
Change comment: There is no comment for this version

Summary

Details

Page properties
Title
... ... @@ -1,1 +1,1 @@
1 -Zūm Discovery
1 +Zūm Autodiscovery
Content
... ... @@ -1,6 +1,6 @@
1 1  (% class="box warningmessage" %)
2 2  (((
3 -This article is about automatically building a SHOWRUNNER™ configuration using the Zūm Discovery feature of SHOWRUNNER™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Crestron Zūm App Overview.WebHome]].
3 +This article is about automatically building a SHOWRUNNER™ configuration using the Zūm Autodiscovery feature of SHOWRUNNER™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Crestron Zūm App Overview.WebHome]].
4 4  For instructions on configuring Zūm Net devices using Crestron Toolbox, see [[this page>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.ZUMNET-JBOX Setup.WebHome]].
5 5  )))
6 6  
... ... @@ -10,133 +10,70 @@
10 10  
11 11  (% class="row" %)
12 12  (((
13 -If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a SHOWRUNNER™ configuration file using the Zūm Discovery feature that is built into SHOWRUNNER™.
13 +If Zūm Net devices have been configured using Crestron's Zūm App
14 14  
15 -There are certain pre-requisites and limitations when building a SHOWRUNNER™ configuration this way, and it may sometimes be necessary make some adjustments to the final configuration, such as changing keypad types and moving loads between areas.
15 += m Wired =
16 16  
17 -= Zūm Wired Discovery =
17 +Lorem
18 18  
19 -== Notes and Limitations ==
19 += Zūm Wireless =
20 20  
21 -(% class="box errormessage" %)
22 -(((
23 -* SHOWRUNNER™ version 3.014 or newer required
24 -* Zūm Wired firmware version 1.02.10 or greater required
25 -* Disconnect from any ZUMNET devices you may be connected to in Toolbox prior to running the discovery commands
26 -* Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release)
27 -* One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually
28 -)))
29 29  
30 -== Steps ==
22 +As of version 2.190 ShowRunner can discover RF Gateways and attached Zum NETBRIDGES. ShowRunner will find all devices, set them up, create areas and loads.
23 +*Disconnect from the gateway before discovery as they cannot support multiple connections*
24 +*Plug loads do not appear in the UI*
31 31  
32 -1. [[Install SHOWRUNNER™>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.WebHome]] on the processor and configure the processor as necessary
33 -1*. Note that while Zūm Wired discovery will build a configuration, if a configuration file was provided then it should still be loaded as it may contain location data or non-Zūm devices.
34 -1. If the ZUMNET-JBOX firmware is too out-of-date to connect using the Crestron Zūm App, then there are some additional steps required: 
35 -1*. Connect to the first ZUMNET-JBOX in Toolbox
36 -1*. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
37 -1**. Note: The SHOWRUNNER™ built-in DHCP server is not meant to be used in production
38 -1**. If the SHOWRUNNER™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
39 -1*. Set unique Connection IDs for each device hosted on the ZUMNET-JBOX so that their firmware can be updated
40 -1*. Load the Zūm Wired firmware to the ZUMNET-JBOX
41 -1*. Repeat the above steps for all ZUMNET-JBOXs
42 -1*. Once all the ZUMNET-JBOXs have pushed the new firmware to their hosted devices, disconnect from them in Toolbox and proceed to the next step
43 -1. Connect to first ZUMNET-JBOX in the Crestron Zūm App
44 -1. Unique Connection IDs should be automatically assigned to any Zūm Link and Cresnet devices on the ZUMNET-JBOX
45 -1*. If firmware was out-of-date, then this step should have already been completed
46 -1*. If unique CIDs are not automatically assigned, connect to the JBOX in Toolbox and give the devices unique CIDs
47 -1. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
48 -1*. If firmware was out-of-date, then this step should have already been completed
49 -1*. Note: The SHOWRUNNER™ built-in DHCP server is not meant to be used in production
50 -1*. If the SHOWRUNNER™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
51 -1. Optionally, manually configure the ZUMNET-JBOX IP table to point at the processor if you want to keep track of which ZUMNET-JBOX is at each IP-ID
52 -1*. If you do not manually configure the IP table, then SHOWRUNNER™ will automatically configure the IP-ID for each ZUMNET-JBOX during discovery
53 -1. Repeat from step 3 until all ZUMNET-JBOXs that are to be controlled by SHOWRUNNER™ have static IP addresses and unique CIDs for any hosted devices
54 -1. Disconnect from any ZUMNET-JBOXs and then connect to the processor in Toolbox
55 -1. Run the command: ##sr discover zumnet true false##
56 -1*. This command tells SHOWRUNNER™ to discover all ZUMMNET-JBOXs on the network, configure their IP tables, and then add corresponding areas and loads to the configuration
57 -1*. One area will be created per ZUMNET-JBOX
58 -1. Run the command: ##sr discover zumnet true true##
59 -1*. This command tells SHOWRUNNER™ to discover all Zūm Link hardware on the previously discovered Zūm Net devices
60 -1*. This command **does not** bring in Cresnet devices: those must be added to the configuration manually until this issue is fixed in the Zūm Wired firmware
61 -1. Put all ZUMNET-JBOXs into CNET mode in order to allow full control from SHOWRUNNER™
62 -1*. Odd behavior may result from conflicts between SHOWRUNNER™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
26 +== Pre-Requisites: ==
63 63  
64 -= Zūm Wireless Discovery =
28 +* Zum NETBRIDGES acquired to their respective gateway (CEN-GWEXER/ZUMNET-GATEWAY)
29 +* ShowRunner installed and running on a 3-series processor on the same network as the gateway
30 +* NETBRIDGES do not need to have addresses assigned. ShowRunner will automatically address them. If devices all already addressed then their addresses will be honored.
65 65  
66 -== Notes and Limitations ==
67 -)))
68 -
69 -(% class="box errormessage" %)
70 -(((
71 -* Processor with SHOWRUNNER™ version 2.190 or newer must be running on the same network as the gateway(s) to be acquired
72 -** For SHOWRUNNER™ versions prior to 3.014 and newer, replace **##sr discover zummesh##** commands with **##sr discover zum##**
73 -* ZUM-NETBRIDGES must already be acquired to their respective gateway
74 -* SHOWRUNNER™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices
75 -* Disconnect from any RF gateways you may be connected to in Toolbox prior to running the discovery command
76 -* Plug loads will not appear in the SHOWRUNNER™ UI
77 -)))
78 -
79 79  (% class="box warningmessage" id="HCaution:" %)
80 80  (((
81 -**Note:** SHOWRUNNER™ has two different approaches for Zūm Wireless Discovery
82 -
83 -1. **Manual RF Gateway Assignment** - SHOWRUNNER™ can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
84 -1. **Claim All RF Gateways** - SHOWRUNNER™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different SHOWRUNNER™ or other Crestron systems on the same local network.
34 +**Note,** SHOWRUNNER has two different types of Zum Wireless autodiscovery:
35 +1. Claim All RF Gateways - ShowRunner will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own.  DO NOT use this method if there are gateways used by different ShowRunner or other Crestron systems on the same local network.
36 +1. Manual RF Gateway Assignment - ShowRunner can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
85 85  )))
86 86  
87 -(% class="row" %)
88 -(((
89 -== Manual RF Gateway Assignment Instructions ==
39 +== Option 1: Claim All Gateways: ==
90 90  
91 -Use this method if you have multiple SHOWRUNNER™ instances on the same network or have gateways used by other Crestron systems.
41 +Use this method when you have a single ShowRunner instance on a local network with all gateways being used for ShowRunner.
92 92  
93 93  * Connect to the processor's console with Toolbox or your favorite SSH client.
94 -* Type ##sr devmgr ethernet query## and press enter. This queries the local network for RF Gateways.
95 -* Type ##sr devmgr ethernet show devices## and press enter. This displays all found Crestron ethernet devices.
96 -* For each gateway that you'd like this instance of SHOWRUNNER™ to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type ##sr ethernet device claim CEN-GWEXER-9E6ADA##. SHOWRUNNER™ will auto-assign an IP-ID. After all gateways have been claimed by SHOWRUNNER™, proceed to the next step.
97 -* Type ##sr discover zummesh false## and press enter.
98 -* Status messages and the results will be displayed on the console. The process should take about 3 minutes.
99 -* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, SHOWRUNNER™ must be restarted to complete the acquire process.
100 -* Type ##progreset## and press enter to restart SHOWRUNNER™
101 -* Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. SHOWRUNNER™ will be able to acquire the loads attached to the Zūm rooms at this point.
102 -* Once completed SHOWRUNNER™ is now ready for full Zūm control
44 +* Type "//sr discover zum true//" and press enter.
45 +* Status messages and the results will be displayed on the console. The process should take about 3 minutes.
46 +* When the discovery is finished type "//sr save//" and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunner must be restarted to complete the acquire process.
47 +* Type "//progreset//" and press enter to restart ShowRunner
48 +* Once ShowRunner has finished restarting type "//sr discover zum false//" and press enter. ShowRunner will be able to acquire the loads attached to the Zum rooms at this point.
49 +* Once completed ShowRunner is now ready for full Zum control
103 103  
104 -== Claim All RF Gateways Instructions ==
51 +== Option 2: Manual RF Gateway Claiming: ==
105 105  
106 -Use this method when you have a single SHOWRUNNER™ instance on a local network with all gateways being used for SHOWRUNNER™.
53 +Use this method if you have multiple ShowRunner instances on the same network or have gateways used by other Crestron systems.
107 107  
108 108  * Connect to the processor's console with Toolbox or your favorite SSH client.
109 -* Type ##sr discover zummesh true## and press enter.
110 -* Status messages and the results will be displayed on the console. The process should take about 3 minutes.
111 -* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, SHOWRUNNER™ must be restarted to complete the acquire process.
112 -* Type ##progreset## and press enter to restart SHOWRUNNER™
113 -* Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. SHOWRUNNER™ will be able to acquire the loads attached to the Zūm rooms at this point.
114 -* Once completed SHOWRUNNER™ is now ready for full Zūm control
56 +* Type "//sr devmgr ethernet query//" and press enter. This queries the local network for RF Gateways.
57 +* Type "//sr devmgr ethernet show devices//" and press enter. This displays all found Crestron ethernet devices.
58 +* For each gateway that you'd like this instance of ShowRunner to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type "//sr ethernet device claim CEN-GWEXER-9E6ADA//". ShowRunner will auto-assign an IP-ID. After all gateways have been claimed by ShowRunner proceed to the next step.
59 +* Type "//sr discover zum false//" and press enter.
60 +* Status messages and the results will be displayed on the console. The process should take about 3 minutes.
61 +* When the discovery is finished type "//sr save//" and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunner must be restarted to complete the acquire process.
62 +* Type "//progreset//" and press enter to restart ShowRunner
63 +* Once ShowRunner has finished restarting type "//sr discover zum false//" and press enter. ShowRunner will be able to acquire the loads attached to the Zum rooms at this point.
64 +* Once completed ShowRunner is now ready for full Zum control
115 115  
116 116  == Examples ==
117 117  
118 -=== Manual Example ===
68 +=== Example for Option 1: ===
119 119  
120 -{{{MC4>sr devmgr ethernet query
121 -Ethrenet AutoDiscovery Result: AutoDiscoveryOperationSuccess
122 -MC4>sr devmgr ethernet show devices
123 -
124 -+--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
125 -| Adapter | Hostname | IP Address | IP-ID | ID |
126 -+--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
127 -| EthernetLANAdapter | CI-SJC-CEN-CI3-1-COM3 | 10.44.5.20 | 00 | CEN-CI3-1-C3COM-3 [v1.1620.00000, #008436E2] type:1 |
128 -+--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
129 -| EthernetLANAdapter | SB-DIN-CENCN-2 | 10.44.5.81 | 00 | DIN-CENCN-2-POE [v1.3544.00006, #8AB25AA3] |
130 -+--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
131 -| EthernetLANAdapter | CEN-GWEXER-9E6ADA | 10.44.5.120 | 00 | CEN-GWEXER [v1.4230.00015, #848210AD] |
132 -+--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
133 -
134 -MC4>sr ethernet device claim CEN-GWEXER-9E6ADA
135 -Claimed ethernet device: CEN-GWEXER-9E6ADA
136 -MC4>Update request from IP-ID-30 in Program 01
137 -MC4>sr discover zummesh false
138 -Starting Zum Discovery without gateway claiming
139 -MC4>Performing Discovery on 1 Gateways.
70 +{{{MC4>sr discover zum true
71 +Starting Zum Discovery with gateway claiming
72 +MC4>Found 1 Gateways to check.
73 +Claimed Gateway SN: 1720JBH04269 at IP-ID: 30
74 +Update request from IP-ID-30 in Program 01
75 +Claimed 1 Gateways. Waiting for queries to finish.
76 +Performing Discovery on 1 Gateways.
140 140  Evaluating 3 Devices on Gateway 30
141 141  Claiming ZUM-NETBRIDGE SN: 1726NEJ01096 from IP-ID: 30
142 142  Dev: ZUM-NETBRIDGE addrssing to RF ID: 03
... ... @@ -147,7 +147,6 @@
147 147  Claiming ZUM-NETBRIDGE SN: 1914NEJ03098 from IP-ID: 30
148 148  Dev: ZUM-NETBRIDGE addrssing to RF ID: 05
149 149  Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 05
150 -Querying cresnet
151 151  Discovering Zum Loads on 1 Gateways.
152 152  Discovering Zum Loads on 3 Devices.
153 153  NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0
... ... @@ -167,7 +167,7 @@
167 167  MC4>progreset
168 168  ...
169 169  CI ShowRunner startup completed successfully in 8072ms
170 -MC4>sr discover zummesh false
106 +MC4>sr discover zum false
171 171  Starting Zum Discovery without gateway claiming
172 172  MC4>Notice: SimplSharpPro[App01] # 2020-07-21 22:19:46 # Recalling startup scenes (if applicable)
173 173  Performing Discovery on 1 Gateways.
... ... @@ -216,17 +216,31 @@
216 216  New Loads: 6
217 217  Modified Loads: 0
218 218  Removed Loads: 0
219 -Zum Discovery Finished}}}
155 +Zum Discovery Finished
156 +}}}
220 220  
221 -=== Claim All Example ===
158 +=== Example for Option 2: ===
222 222  
223 -{{{MC4>sr discover zummesh true
224 -Starting Zum Discovery with gateway claiming
225 -MC4>Found 1 Gateways to check.
226 -Claimed Gateway SN: 1720JBH04269 at IP-ID: 30
227 -Update request from IP-ID-30 in Program 01
228 -Claimed 1 Gateways. Waiting for queries to finish.
229 -Performing Discovery on 1 Gateways.
160 +{{{MC4>sr devmgr ethernet query
161 +Ethrenet AutoDiscovery Result: AutoDiscoveryOperationSuccess
162 +MC4>sr devmgr ethernet show devices
163 +
164 ++--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
165 +| Adapter | Hostname | IP Address | IP-ID | ID |
166 ++--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
167 +| EthernetLANAdapter | CI-SJC-CEN-CI3-1-COM3 | 10.44.5.20 | 00 | CEN-CI3-1-C3COM-3 [v1.1620.00000, #008436E2] type:1 |
168 ++--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
169 +| EthernetLANAdapter | SB-DIN-CENCN-2 | 10.44.5.81 | 00 | DIN-CENCN-2-POE [v1.3544.00006, #8AB25AA3] |
170 ++--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
171 +| EthernetLANAdapter | CEN-GWEXER-9E6ADA | 10.44.5.120 | 00 | CEN-GWEXER [v1.4230.00015, #848210AD] |
172 ++--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
173 +
174 +MC4>sr ethernet device claim CEN-GWEXER-9E6ADA
175 +Claimed ethernet device: CEN-GWEXER-9E6ADA
176 +MC4>Update request from IP-ID-30 in Program 01
177 +MC4>sr discover zum false
178 +Starting Zum Discovery without gateway claiming
179 +MC4>Performing Discovery on 1 Gateways.
230 230  Evaluating 3 Devices on Gateway 30
231 231  Claiming ZUM-NETBRIDGE SN: 1726NEJ01096 from IP-ID: 30
232 232  Dev: ZUM-NETBRIDGE addrssing to RF ID: 03
... ... @@ -237,6 +237,7 @@
237 237  Claiming ZUM-NETBRIDGE SN: 1914NEJ03098 from IP-ID: 30
238 238  Dev: ZUM-NETBRIDGE addrssing to RF ID: 05
239 239  Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 05
190 +Querying cresnet
240 240  Discovering Zum Loads on 1 Gateways.
241 241  Discovering Zum Loads on 3 Devices.
242 242  NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0
... ... @@ -256,7 +256,7 @@
256 256  MC4>progreset
257 257  ...
258 258  CI ShowRunner startup completed successfully in 8072ms
259 -MC4>sr discover zummesh false
210 +MC4>sr discover zum false
260 260  Starting Zum Discovery without gateway claiming
261 261  MC4>Notice: SimplSharpPro[App01] # 2020-07-21 22:19:46 # Recalling startup scenes (if applicable)
262 262  Performing Discovery on 1 Gateways.
... ... @@ -306,5 +306,5 @@
306 306  Modified Loads: 0
307 307  Removed Loads: 0
308 308  Zum Discovery Finished
309 -}}}
260 + }}}
310 310  )))