Page properties
Content
... ... @@ -8,8 +8,6 @@
8 8  {{toc/}}
9 9  {{/box}}
10 10  
11 -(% class="row" %)
12 -(((
13 13  If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a SHOWRUNNER™ configuration file using the Zūm Discovery feature that is built into SHOWRUNNER™.
14 14  
15 15  There are certain pre-requisites and limitations when building a SHOWRUNNER™ configuration this way, and it may sometimes be necessary make some adjustments to the final configuration, such as changing keypad types and moving loads between areas.
... ... @@ -21,7 +21,7 @@
21 21  (% class="box errormessage" %)
22 22  (((
23 23  * SHOWRUNNER™ version 3.014 or newer required
24 -* Zūm Wired firmware version 1.02.10 or greater required
22 +* Zūm Wired firmware .puf version 1.02.10 or greater required (ZUMNET-JBOX installed minimum version 1.001.00081)
25 25  * Disconnect from any ZUMNET devices you may be connected to in Toolbox prior to running the discovery commands
26 26  * Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release)
27 27  * One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually
... ... @@ -50,21 +50,21 @@
50 50  1*. If the SHOWRUNNER™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
51 51  1. Optionally, manually configure the ZUMNET-JBOX IP table to point at the processor if you want to keep track of which ZUMNET-JBOX is at each IP-ID
52 52  1*. If you do not manually configure the IP table, then SHOWRUNNER™ will automatically configure the IP-ID for each ZUMNET-JBOX during discovery
51 +1. Set the ZUMNET-JBOX into either Zūm ("App") mode or CNET mode as required for the program
52 +1*. Full control from SHOWRUNNER™ is only possible if all ZUMNET-JBOXs are in CNET mode. Odd behavior may result from conflicts between SHOWRUNNER™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
53 53  1. Repeat from step 3 until all ZUMNET-JBOXs that are to be controlled by SHOWRUNNER™ have static IP addresses and unique CIDs for any hosted devices
54 54  1. Disconnect from any ZUMNET-JBOXs and then connect to the processor in Toolbox
55 55  1. Run the command: ##sr discover zumnet true false##
56 -1*. This command tells SHOWRUNNER™ to discover all ZUMMNET-JBOXs on the network, configure their IP tables, and then add corresponding areas and loads to the configuration
57 -1*. One area will be created per ZUMNET-JBOX
56 +1*. This command tells SHOWRUNNER™ to discover all ZUMMNET-JBOXs on the network, configure their IP tables, and then add corresponding IP Devices to the configuration
58 58  1. Run the command: ##sr discover zumnet true true##
59 -1*. This command tells SHOWRUNNER™ to discover all Zūm Link hardware on the previously discovered Zūm Net devices
58 +1*. This command tells SHOWRUNNER™ to discover all Zūm Link hardware (including the internal ZUMNET-JBOX load controller) on the previously discovered Zūm Net devices and then add corresponding areas, loads, sensors, etc. to the configuration
59 +1**. One area will be created per ZUMNET-JBOX, and all hardware attached to that ZUMNET-JBOX will be assigned to that area
60 60  1*. This command **does not** bring in Cresnet devices: those must be added to the configuration manually until this issue is fixed in the Zūm Wired firmware
61 -1. Put all ZUMNET-JBOXs into CNET mode in order to allow full control from SHOWRUNNER™
62 -1*. Odd behavior may result from conflicts between SHOWRUNNER™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
61 +1. If all steps have been performed successfully, then you should be able to use the ##sr show area##, ##sr show load##, ##sr show keypad##, and ##sr show occ## commands to see that the ZUMNET and ZUMLINK hardware has been discovered correctly.
63 63  
64 64  = Zūm Wireless Discovery =
65 65  
66 66  == Notes and Limitations ==
67 -)))
68 68  
69 69  (% class="box errormessage" %)
70 70  (((
... ... @@ -84,8 +84,6 @@
84 84  1. **Claim All RF Gateways** - SHOWRUNNER™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different SHOWRUNNER™ or other Crestron systems on the same local network.
85 85  )))
86 86  
87 -(% class="row" %)
88 -(((
89 89  == Manual RF Gateway Assignment Instructions ==
90 90  
91 91  Use this method if you have multiple SHOWRUNNER™ instances on the same network or have gateways used by other Crestron systems.
... ... @@ -307,4 +307,3 @@
307 307  Removed Loads: 0
308 308  Zum Discovery Finished
309 309  }}}
310 -)))