Summary

Details

Page properties
Content
... ... @@ -18,11 +18,14 @@
18 18  
19 19  == Notes and Limitations ==
20 20  
21 +(% class="box errormessage" %)
22 +(((
21 21  * SHOWRUNNER™ version 3.014 or newer required
22 22  * Zūm Wired firmware version 1.02.10 or greater required
23 23  * Disconnect from any ZUMNET devices you may be connected to in Toolbox prior to running the discovery commands
24 24  * Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release)
25 25  * One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually
28 +)))
26 26  
27 27  == Steps ==
28 28  
... ... @@ -61,9 +61,12 @@
61 61  = Zūm Wireless Discovery =
62 62  
63 63  == Notes and Limitations ==
67 +)))
64 64  
69 +(% class="box errormessage" %)
70 +(((
65 65  * Processor with SHOWRUNNER™ version 2.190 or newer must be running on the same network as the gateway(s) to be acquired
66 -** For SHOWRUNNER™ versions 3.014 and newer, replace ##sr discover zum## commands with ##sr discover zummesh##
72 +** For SHOWRUNNER™ versions prior to 3.014 and newer, replace **##sr discover zummesh##** commands with **##sr discover zum##**
67 67  * ZUM-NETBRIDGES must already be acquired to their respective gateway
68 68  * SHOWRUNNER™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices
69 69  * Disconnect from any RF gateways you may be connected to in Toolbox prior to running the discovery command
... ... @@ -85,14 +85,14 @@
85 85  Use this method if you have multiple SHOWRUNNER™ instances on the same network or have gateways used by other Crestron systems.
86 86  
87 87  * Connect to the processor's console with Toolbox or your favorite SSH client.
88 -* Type "//sr devmgr ethernet query//" and press enter. This queries the local network for RF Gateways.
89 -* Type "//sr devmgr ethernet show devices//" and press enter. This displays all found Crestron ethernet devices.
90 -* For each gateway that you'd like this instance of SHOWRUNNER™ to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type "//sr ethernet device claim CEN-GWEXER-9E6ADA//". SHOWRUNNER™ will auto-assign an IP-ID. After all gateways have been claimed by SHOWRUNNER™, proceed to the next step.
91 -* Type "//sr discover zum false//" and press enter.
94 +* Type ##sr devmgr ethernet query## and press enter. This queries the local network for RF Gateways.
95 +* Type ##sr devmgr ethernet show devices## and press enter. This displays all found Crestron ethernet devices.
96 +* For each gateway that you'd like this instance of SHOWRUNNER™ to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type ##sr ethernet device claim CEN-GWEXER-9E6ADA##. SHOWRUNNER™ will auto-assign an IP-ID. After all gateways have been claimed by SHOWRUNNER™, proceed to the next step.
97 +* Type ##sr discover zummesh false## and press enter.
92 92  * Status messages and the results will be displayed on the console. The process should take about 3 minutes.
93 -* When the discovery is finished type "//sr save//" and press enter to save the updated config. Due to an unknown quirk that we are looking into, SHOWRUNNER™ must be restarted to complete the acquire process.
94 -* Type "//progreset//" and press enter to restart SHOWRUNNER™
95 -* Once SHOWRUNNER™ has finished restarting type "//sr discover zum false//" and press enter. SHOWRUNNER™ will be able to acquire the loads attached to the Zūm rooms at this point.
99 +* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, SHOWRUNNER™ must be restarted to complete the acquire process.
100 +* Type ##progreset## and press enter to restart SHOWRUNNER™
101 +* Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. SHOWRUNNER™ will be able to acquire the loads attached to the Zūm rooms at this point.
96 96  * Once completed SHOWRUNNER™ is now ready for full Zūm control
97 97  
98 98  == Claim All RF Gateways Instructions ==
... ... @@ -100,11 +100,11 @@
100 100  Use this method when you have a single SHOWRUNNER™ instance on a local network with all gateways being used for SHOWRUNNER™.
101 101  
102 102  * Connect to the processor's console with Toolbox or your favorite SSH client.
103 -* Type "//sr discover zum true//" and press enter.
109 +* Type ##sr discover zummesh true## and press enter.
104 104  * Status messages and the results will be displayed on the console. The process should take about 3 minutes.
105 -* When the discovery is finished type "//sr save//" and press enter to save the updated config. Due to an unknown quirk that we are looking into, SHOWRUNNER™ must be restarted to complete the acquire process.
106 -* Type "//progreset//" and press enter to restart SHOWRUNNER™
107 -* Once SHOWRUNNER™ has finished restarting type "//sr discover zum false//" and press enter. SHOWRUNNER™ will be able to acquire the loads attached to the Zūm rooms at this point.
111 +* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, SHOWRUNNER™ must be restarted to complete the acquire process.
112 +* Type ##progreset## and press enter to restart SHOWRUNNER™
113 +* Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. SHOWRUNNER™ will be able to acquire the loads attached to the Zūm rooms at this point.
108 108  * Once completed SHOWRUNNER™ is now ready for full Zūm control
109 109  
110 110  == Examples ==
... ... @@ -128,7 +128,7 @@
128 128  MC4>sr ethernet device claim CEN-GWEXER-9E6ADA
129 129  Claimed ethernet device: CEN-GWEXER-9E6ADA
130 130  MC4>Update request from IP-ID-30 in Program 01
131 -MC4>sr discover zum false
137 +MC4>sr discover zummesh false
132 132  Starting Zum Discovery without gateway claiming
133 133  MC4>Performing Discovery on 1 Gateways.
134 134  Evaluating 3 Devices on Gateway 30
... ... @@ -161,7 +161,7 @@
161 161  MC4>progreset
162 162  ...
163 163  CI ShowRunner startup completed successfully in 8072ms
164 -MC4>sr discover zum false
170 +MC4>sr discover zummesh false
165 165  Starting Zum Discovery without gateway claiming
166 166  MC4>Notice: SimplSharpPro[App01] # 2020-07-21 22:19:46 # Recalling startup scenes (if applicable)
167 167  Performing Discovery on 1 Gateways.
... ... @@ -214,7 +214,7 @@
214 214  
215 215  === Claim All Example ===
216 216  
217 -{{{MC4>sr discover zum true
223 +{{{MC4>sr discover zummesh true
218 218  Starting Zum Discovery with gateway claiming
219 219  MC4>Found 1 Gateways to check.
220 220  Claimed Gateway SN: 1720JBH04269 at IP-ID: 30
... ... @@ -250,7 +250,7 @@
250 250  MC4>progreset
251 251  ...
252 252  CI ShowRunner startup completed successfully in 8072ms
253 -MC4>sr discover zum false
259 +MC4>sr discover zummesh false
254 254  Starting Zum Discovery without gateway claiming
255 255  MC4>Notice: SimplSharpPro[App01] # 2020-07-21 22:19:46 # Recalling startup scenes (if applicable)