13 -If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a SHOWRUNNER™ configuration file using the Autodiscovery feature that is built into SHOWRUNNER™.
13 +If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a SHOWRUNNER™ configuration file using the Zūm Discovery feature that is built into SHOWRUNNER™.
14 14  
15 15  There are certain pre-requisites and limitations when building a SHOWRUNNER™ configuration this way, and it may sometimes be necessary make some adjustments to the final configuration, such as changing keypad types and moving loads between areas.
16 16  
17 17  = Zūm Wired Discovery =
18 18  
19 -Lorem
19 +== Notes and Limitations ==
20 20  
21 -= Zūm Wireless Discovery =
21 +* SHOWRUNNER™ version 3.014 or newer required
22 +* Zūm Wired firmware version 1.02.10 or greater required
23 +* Disconnect from any ZUMNET devices you may be connected to in Toolbox prior to running the discovery commands
24 +* Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release)
25 +* One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually
22 22  
23 -*Disconnect from the gateway before discovery as they cannot support multiple connections*
24 -*Plug loads do not appear in the UI*
27 +== Steps ==
25 25  
26 -== Notes and Limitations ==
29 +1. [[Install SHOWRUNNER™>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.WebHome]] on the processor and configure the processor as necessary
30 +1*. Note that while Zūm Wired discovery will build a configuration, if a configuration file was provided then it should still be loaded as it may contain location data or non-Zūm devices.
31 +1. If the ZUMNET-JBOX firmware is too out-of-date to connect using the Crestron Zūm App, then there are some additional steps required: 
32 +1*. Connect to the first ZUMNET-JBOX in Toolbox
33 +1*. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
34 +1**. Note: The SHOWRUNNER™ built-in DHCP server is not meant to be used in production
35 +1**. If the SHOWRUNNER™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
36 +1*. Set unique Connection IDs for each device hosted on the ZUMNET-JBOX so that their firmware can be updated
37 +1*. Load the Zūm Wired firmware to the ZUMNET-JBOX
38 +1*. Repeat the above steps for all ZUMNET-JBOXs
39 +1*. Once all the ZUMNET-JBOXs have pushed the new firmware to their hosted devices, proceed to the next step
40 +1. Connect to first ZUMNET-JBOX in the Crestron Zūm App
41 +1. Unique Connection IDs should be automatically assigned to any Zūm Link and Cresnet devices on the ZUMNET-JBOX
42 +1*. If firmware was out-of-date, then this step should have already been completed
43 +1*. If unique CIDs are not automatically assigned, connect to the JBOX in Toolbox and give the devices unique CIDs
44 +1. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
45 +1*. If firmware was out-of-date, then this step should have already been completed
46 +1*. Note: The SHOWRUNNER™ built-in DHCP server is not meant to be used in production
47 +1*. If the SHOWRUNNER™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
48 +1. Optionally, manually configure the ZUMNET-JBOX IP table to point at the processor if you want to keep track of which ZUMNET-JBOX is at each IP-ID
49 +1*. If you do not manually configure the IP table, then SHOWRUNNER™ will automatically configure the IP-ID for each ZUMNET-JBOX during discovery
50 +1. Repeat from step 3 until all ZUMNET-JBOXs that are to be controlled by SHOWRUNNER™ have static IP addresses and unique CIDs for any hosted devices
51 +1. Connect to the processor in Toolbox and run the command: ##sr discover zumnet true false##
52 +1*. This command tells SHOWRUNNER™ to discover all ZUMMNET-JBOXs on the network, configure their IP tables, and then add corresponding areas and loads to the configuration
53 +1*. One area will be created per ZUMNET-JBOX
54 +1. Run the command: ##sr discover zumnet true true##
55 +1*. This command tells SHOWRUNNER™ to discover all Zūm Link hardware on the previously discovered Zūm Net devices
56 +1*. This command **does not** bring in Cresnet devices: those must be added to the configuration manually until this issue is fixed in the Zūm Wired firmware
57 +1. Put all ZUMNET-JBOXs into CNET mode in order to allow full control from SHOWRUNNER™
58 +1*. Odd behavior may result from conflicts between SHOWRUNNER™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
27 27  
28 -* SHOWRUNNER™ version 2.190 or newer required
29 -* Disconnect from any RF gateways you are connected to prior to running the autodiscovery command,
60 += Zūm Wireless Discovery =
30 30  
31 -== Pre-Requisites ==
62 +== Notes and Limitations ==
32 32  
33 -* Zum NETBRIDGES acquired to their respective gateway (CEN-GWEXER/ZUMNET-GATEWAY)
34 -* SHOWRUNNER™ installed and running on a 3-series processor on the same network as the gateway
35 -* NETBRIDGES do not need to have addresses assigned. SHOWRUNNER™ will automatically address them. If devices all already addressed then their addresses will be honored.
64 +* Processor with SHOWRUNNER™ version 2.190 or newer must be running on the same network as the gateway(s) to be acquired
65 +** For SHOWRUNNER™ versions 3.014 and newer, replace ##sr discover zum## commands with ##sr discover zummesh##
66 +* ZUM-NETBRIDGES must already be acquired to their respective gateway
67 +* SHOWRUNNER™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices
68 +* Disconnect from any RF gateways you may be connected to in Toolbox prior to running the discovery command
69 +* Plug loads will not appear in the SHOWRUNNER™ UI
36 36  )))
37 37  
38 38  (% class="box warningmessage" id="HCaution:" %)
39 39  (((
40 -**Note:** SHOWRUNNER™ has two different approaches for Zūm Wireless Autodiscovery
74 +**Note:** SHOWRUNNER™ has two different approaches for Zūm Wireless Discovery
41 41  
42 42  1. **Manual RF Gateway Assignment** - SHOWRUNNER™ can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
43 43  1. **Claim All RF Gateways** - SHOWRUNNER™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different SHOWRUNNER™ or other Crestron systems on the same local network.
... ... @@ -45,7 +45,7 @@
45 45  
46 46  (% class="row" %)
47 47  (((
48 -== Manual RF Gateway Assignment ==
82 +== Manual RF Gateway Assignment Instructions ==
49 49  
50 50  Use this method if you have multiple SHOWRUNNER™ instances on the same network or have gateways used by other Crestron systems.
51 51  
... ... @@ -60,7 +60,7 @@
60 60  * Once SHOWRUNNER™ has finished restarting type "//sr discover zum false//" and press enter. SHOWRUNNER™ will be able to acquire the loads attached to the Zūm rooms at this point.
61 61  * Once completed SHOWRUNNER™ is now ready for full Zūm control
62 62  
63 -== Claim All RF Gateways ==
97 +== Claim All RF Gateways Instructions ==
64 64  
65 65  Use this method when you have a single SHOWRUNNER™ instance on a local network with all gateways being used for SHOWRUNNER™.