... ... @@ -10,34 +10,39 @@
10 10  
11 11  (% class="row" %)
12 12  (((
13 -If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a SHOWRUNNER™ configuration file using the Autodiscovery feature that is built into SHOWRUNNER™.
13 +If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a SHOWRUNNER™ configuration file using the Zūm Discovery feature that is built into SHOWRUNNER™.
14 14  
15 15  There are certain pre-requisites and limitations when building a SHOWRUNNER™ configuration this way, and it may sometimes be necessary make some adjustments to the final configuration, such as changing keypad types and moving loads between areas.
16 16  
17 17  = Zūm Wired Discovery =
18 18  
19 -Lorem
19 +== Notes and Limitations ==
20 20  
21 -= Zūm Wireless Discovery =
21 +* SHOWRUNNER™ version 3.014 or newer required
22 +* Zūm Wired firmware version 1.02.10 or greater required
23 +* Disconnect from any ZUMNET devices you may be connected to in Toolbox prior to running the discovery commands
24 +* Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release)
25 +* One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually
22 22  
23 -*Disconnect from the gateway before discovery as they cannot support multiple connections*
24 -*Plug loads do not appear in the UI*
27 +== Steps ==
25 25  
26 -== Notes and Limitations ==
29 +1.
27 27  
28 -* SHOWRUNNER™ version 2.190 or newer required
29 -* Disconnect from any RF gateways you are connected to prior to running the autodiscovery command,
31 += Zūm Wireless Discovery =
30 30  
31 -== Pre-Requisites ==
33 +== Notes and Limitations ==
32 32  
33 -* Zum NETBRIDGES acquired to their respective gateway (CEN-GWEXER/ZUMNET-GATEWAY)
34 -* SHOWRUNNER™ installed and running on a 3-series processor on the same network as the gateway
35 -* NETBRIDGES do not need to have addresses assigned. SHOWRUNNER™ will automatically address them. If devices all already addressed then their addresses will be honored.
35 +* Processor with SHOWRUNNER™ version 2.190 or newer must be running on the same network as the gateway(s) to be acquired
36 +** For SHOWRUNNER™ versions 3.014 and newer, replace ##sr discover zum## commands with ##sr discover zummesh##
37 +* ZUM-NETBRIDGES must already be acquired to their respective gateway
38 +* SHOWRUNNER™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices
39 +* Disconnect from any RF gateways you may be connected to in Toolbox prior to running the discovery command
40 +* Plug loads will not appear in the SHOWRUNNER™ UI
36 36  )))
37 37  
38 38  (% class="box warningmessage" id="HCaution:" %)
39 39  (((
40 -**Note:** SHOWRUNNER™ has two different approaches for Zūm Wireless Autodiscovery
45 +**Note:** SHOWRUNNER™ has two different approaches for Zūm Wireless Discovery
41 41  
42 42  1. **Manual RF Gateway Assignment** - SHOWRUNNER™ can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
43 43  1. **Claim All RF Gateways** - SHOWRUNNER™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different SHOWRUNNER™ or other Crestron systems on the same local network.
... ... @@ -45,7 +45,7 @@
45 45  
46 46  (% class="row" %)
47 47  (((
48 -== Manual RF Gateway Assignment ==
53 +== Manual RF Gateway Assignment Instructions ==
49 49  
50 50  Use this method if you have multiple SHOWRUNNER™ instances on the same network or have gateways used by other Crestron systems.
51 51  
... ... @@ -60,7 +60,7 @@
60 60  * Once SHOWRUNNER™ has finished restarting type "//sr discover zum false//" and press enter. SHOWRUNNER™ will be able to acquire the loads attached to the Zūm rooms at this point.
61 61  * Once completed SHOWRUNNER™ is now ready for full Zūm control
62 62  
63 -== Claim All RF Gateways ==
68 +== Claim All RF Gateways Instructions ==
64 64  
65 65  Use this method when you have a single SHOWRUNNER™ instance on a local network with all gateways being used for SHOWRUNNER™.
66 66