1 +(% class="box errormessage" %)
2 +(((
3 +ūūūūūū**IMPORTANT:** When using ShowRunnerCLC™ with a ZUM-HUB4, **do not** discover Zūm Rooms using the Crestron HUB4 Web UI. During discovery, the HUB4 will claim ZUMNET-JBOXs and prevent ShowRunnerCLC™ from auto-discovering or registering the Zūm hardware for itself.
4 +
5 +**WARNING:** Cresnet Discovery is non-functional for ZUMNET-JBOXs with certain versions of Crestron Device Database.
6 +ShowRunnerCLC™ versions v3.019 through v3.041 must be either downgraded to v3.018 or upgraded to v3.042 or newer in order to perform auto-discover functions.
7 +)))
8 +
1 1  (% class="box warningmessage" %)
2 2  (((
3 -This article is about automatically building a SHOWRUNNER™ configuration using the Zūm Autodiscovery feature of SHOWRUNNER™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Crestron Zūm App Overview.WebHome]].
11 +This article is about automatically building a ShowRunnerCLC™ configuration using the Zūm Discovery feature of ShowRunnerCLC™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Preparation.Zūm App Overview.WebHome]].
4 4  For instructions on configuring Zūm Net devices using Crestron Toolbox, see [[this page>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.ZUMNET-JBOX Setup.WebHome]].
5 5  )))
6 6  
... ... @@ -8,70 +8,179 @@
8 8  {{toc/}}
9 9  {{/box}}
10 10  
11 -(% class="row" %)
12 -(((
13 -If Zūm Net devices have been configured using Crestron's Zūm App
19 +If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a ShowRunnerCLC™ configuration file using the Zūm Discovery feature that is built into ShowRunnerCLC™.
14 14  
15 -= m Wired =
21 +There are certain pre-requisites and limitations when building a ShowRunnerCLC™ configuration this way, and it may sometimes be necessary make some adjustments to the final configuration, such as changing keypad types and moving loads between areas.
16 16  
17 -Lorem
23 += Discovery Filter (ShowRunnerCLC™ 3.062 or newer) =
18 18  
19 -= m Wireless =
25 +Discovered ethernet devices may be filtered using either a hostname or IP Address filter.  The filter is configured from the command line interface.
20 20  
27 +##+~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-+~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-+
28 +~| Command | Help |
29 +~|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|
30 +~| SR discover clear filter | Remove Discovery Filter |
31 +~| SR discover filter | Show Discovery Filter |
32 +~| SR discover filter (X:S) | Set Discovery Filter |
33 +~| - | (X):S:Filter String |
34 +~|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|##
21 21  
22 -As of version 2.190 ShowRunner can discover RF Gateways and attached Zum NETBRIDGES. ShowRunner will find all devices, set them up, create areas and loads.
23 -*Disconnect from the gateway before discovery as they cannot support multiple connections*
24 -*Plug loads do not appear in the UI*
36 +=== Hostname Filter ===
25 25  
26 -== Pre-Requisites: ==
38 +The Hostname filter uses a regular expression to filter discovered ZUMNET GATEWAYs or JBOXs.  Multiple expressions can be applied by using a comma to separate the expressions.
27 27  
28 -* Zum NETBRIDGES acquired to their respective gateway (CEN-GWEXER/ZUMNET-GATEWAY)
29 -* ShowRunner installed and running on a 3-series processor on the same network as the gateway
30 -* NETBRIDGES do not need to have addresses assigned. ShowRunner will automatically address them. If devices all already addressed then their addresses will be honored.
31 -)))
40 +Command Syntax: ##"Type='Hostname' Settings='Expr1[,Expr2]'"##
32 32  
33 -(% class="box warningmessage" id="HCaution:" %)
42 +Examples:
43 +
44 +1. Only include hostnames that start with ZUMNET-06:
45 +(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='Hostname' Settings='^ZUMNET-06'"
46 +1. Include hostnames that start with ZUMNET-FL01 or contain FL03:
47 +(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='Hostname' Settings='^ZUMNET-FL01,FL03'"
48 +
49 +=== IP Address Filter ===
50 +
51 +The IP Address filter will restrict discovered ZUMNET GATEWAYs or JBOXs to matching IP Addresses or IP Address ranges.  Multiple addresses and ranges can be used.
52 +
53 +Command Syntax: ##"Type='IPAddress' Settings='Address[,AddressStart-AddressEnd]'"##
54 +
55 +Examples:
56 +
57 +1. Only include a device with an address of 192.168.0.10 or 192.168.0.50:
58 +(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='IPAddress' Settings='192.168.0.10,192.168.0.50'"
59 +1. Include addresses between 192.168.0.11 and 192.168.0.50 and 192.168.0.200 and 192.168.0.240:
60 +(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='IPAddress' Settings='192.168.0.11-192.168.0.50,192.168.0.200-192.168.0.240'"
61 +
62 +=== IP-ID Filter (Added in SR v3.067) ===
63 +
64 +The IP-ID filter will restrict discovered ZUMNET GATEWAYs or JBOXs to matching IP-IDs or IP-ID ranges.  Multiple IDs and ranges can be used.
65 +
66 +Command Syntax: ##"Type='IPID' Settings='IPID[,IPIDStart-IPIDEnd]'"##
67 +
68 +Examples:
69 +
70 +1. Only include a device with an IP-ID of 10 or 5A:
71 +(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='IPID' Settings='10,5A'"
72 +1. Include addresses between 11 and 4F and A0 and BF:
73 +(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='IPID' Settings='11-4F,A0-BF'"
74 +
75 += Zūm Wired Discovery =
76 +
77 +== Notes and Limitations ==
78 +
79 +(% class="box warningmessage" %)
34 34  (((
35 -**Note:** SHOWRUNNER™ has two different approaches for Zūm Wireless Autodiscovery
81 +* ShowRunnerCLC™ version 3.014 or newer required
82 +* Zūm Wired firmware .puf version 1.02.10 or greater required (ZUMNET-JBOX installed minimum version 1.001.00081)
83 +* Disconnect from any ZUMNET devices you may be connected to in Toolbox and confirm all hardware (NETs and LINKs) are online prior to running the discovery commands
84 +* Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release)
85 +* ZUMLINK-IOs will not be discovered (Expected to be discoverable in future ShowRunnerCLC™ release)
86 +* ZUMLINK-KPs will not be discovered on older versions of ShowRunnerCLC™ (v3.058 or newer will discover keypads and set as remote type)
87 +* One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually
88 +)))
36 36  
37 -1. **Manual RF Gateway Assignment** - SHOWRUNNER™ can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
38 -1. **Claim All RF Gateways** - SHOWRUNNER™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different SHOWRUNNER™ or other Crestron systems on the same local network.
90 +== Steps ==
91 +
92 +1. [[Install ShowRunner™>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.WebHome]] on the processor and configure the processor as necessary
93 +1*. Note that while Zūm Wired discovery will build a configuration, if a configuration file was provided then it should still be loaded as it may contain location data or non-Zūm devices.
94 +1. If the ZUMNET-JBOX firmware is too out-of-date to connect using the Crestron Zūm App, then there are some additional steps required: 
95 +1*. Connect to the first ZUMNET-JBOX in Toolbox
96 +1*. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
97 +1**. Note: The ShowRunnerCLC™ built-in DHCP server is not meant to be used in production
98 +1**. If the ShowRunnerCLC™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
99 +1*. Set unique Connection IDs for each device hosted on the ZUMNET-JBOX so that their firmware can be updated
100 +1*. Load the Zūm Wired firmware to the ZUMNET-JBOX
101 +1*. Repeat the above steps for all ZUMNET-JBOXs
102 +1*. Once all the ZUMNET-JBOXs have pushed the new firmware to their hosted devices, disconnect from them in Toolbox and proceed to the next step
103 +1. Connect to each ZUMNET-JBOX in the Crestron Zūm App
104 +1*. Commission room through the app
105 +1**. configure keypad logic
106 +1**. configure occupancy sensor settings
107 +1**. calibrate photocell(s)
108 +1*. Set hostnames for the ZUMNETs.
109 +1**. Zūm discovery will bring in hostnames.
110 +1. Unique Connection IDs should be automatically assigned to any Zūm Link and Cresnet devices on the ZUMNET-JBOX
111 +1*. If firmware was out-of-date, then this step should have already been completed
112 +1*. If unique CIDs are not automatically assigned, connect to the JBOX in Toolbox and give the devices unique CIDs
113 +1. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
114 +1*. If firmware was out-of-date, then this step should have already been completed
115 +1*. Note: The ShowRunnerCLC™ built-in DHCP server is not meant to be used in production
116 +1*. If the ShowRunnerCLC™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
117 +1. Optionally, manually configure the ZUMNET-JBOX IP table to point at the processor if you want to keep track of which ZUMNET-JBOX is at each IP-ID
118 +1*. If you do not manually configure the IP table, then SHOWRUNNER™ will automatically configure the IP-ID for each ZUMNET-JBOX during discovery
119 +1. Set the ZUMNET-JBOX into either Zūm ("App") mode or CNET mode as required for the program
120 +1*. Full control from ShowRunnerCLC™ is only possible if all ZUMNET-JBOXs are in CNET mode. Odd behavior may result from conflicts between ShowRunnerCLC™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
121 +1. Repeat from step 3 until all ZUMNET-JBOXs that are to be controlled by ShowRunnerCLC™ have static IP addresses and unique CIDs for any hosted devices
122 +1. Disconnect from any ZUMNET-JBOXs and then connect to the processor in Toolbox
123 +1. If trying to Auto Discover on a job with multiple processors or you are returning to a job where new ZUMNET-JBOXs have been added and you only wish to Auto Discover those new devices, ShowRunnerCLC™ 3.062 and newer allow [[filtering based on hostname or IP address>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Program Configuration.Zūm Discovery.WebHome||anchor="HDiscoveryFilter28ShowRunnerCLC21223.062ornewer29"]] in order to limit the devices that are brought into the ShowRunnerCLC™ configuration
124 +1. Run the command: ##sr discover zumnet true true## to add ZUMNET-JBOXs, connected ZUMLINK devices, and some Cresnet devices (such as Cameo keypads) to the configuration. (Note
125 +1*. This command will update the ShowRunnerCLC™ configuration with: 
126 +1**. One area per claimed ZUMNET-JBOX based on the Room Name set in the app
127 +1**. One ZUMNET-BRIDGE load controller per claimed ZUMNET-JBOX to allow the Zūm Room to communicate its current status (scene, occupancy, etc.) to ShowRunnerCLC™
128 +1**. One entry for each ZUMLINK-KP, ZUMLINK-JBOX, and ZUMLINK occupancy sensor connected to each ZUMNET-JBOX
129 +1***. All devices and loads will be auto-labeled based on their connection information, //not// the names they are given in the Zūm App
130 +1***. Keypads will be brought in as "Remote" type and only follow the logic as defined in the Zūm App, allowing for scheduled enabling/disabling of keypads without adding any additional button functions from ShowRunnerCLC™
131 +1***. Occupancy sensors will be brought in with "Use Hardware Logic" and only follow the logic as defined in the Zūm App
132 +1*. Optionally, run ##sr discover zumnet false true## to only add new ZUMLINK devices to the configuration. **Note that previously added ZUMLINK devices will be added again if their CID has been changed**
133 +1*. Run ##sr discover zumnet true false## to add ZUMNET-JBOXs without bringing in any devices. **Note that if a ZUMNET-JBOX already has an entry in its IP Table, ShowRunnerCLC™ will not claim it.** The ZUMNET-JBOX's IP Table must be cleared in order for it to be claimed by the ShowRunnerCLC™ program
134 +1. If all steps have been performed successfully, then you should be able to use the ##sr show area##, ##sr show load##, ##sr show keypad##, and ##sr show occ## commands to see that the ZUMNET and ZUMLINK hardware has been discovered correctly.
135 +1. If new Zūm Link hardware has been added, it is not necessary to do a full Auto Discovery to bring the new devices into ShowRunnerCLC™; instead you can just run ##sr discover zumnet false true## to bring in the new Zūm Link devices without claiming any new Zūm Net devices
136 +
137 += Zūm Wireless Discovery =
138 +
139 +== Notes and Limitations ==
140 +
141 +(% class="box warningmessage" %)
142 +(((
143 +* Processor with ShowRunnerCLC™ version 2.190 or newer must be running on the same network as the gateway(s) to be acquired
144 +** For ShowRunnerCLC™ versions prior to 3.014 and newer, replace **##sr discover zummesh##** commands with **##sr discover zum##**
145 +* ZUM-NETBRIDGES must already be acquired to their respective gateway
146 +* ShowRunnerCLC™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices
147 +* Disconnect from any RF gateways you may be connected to in Toolbox prior to running the discovery command
148 +* Plug loads will not appear in the ShowRunnerCLC™ UI
149 +* Newer GWEXER firmware enables SSL by default. Follow the instructions at [[SSL User Configuration>>doc:SHOWRUNNER™ User Guide & Wiki.SHOWRUNNER™ Appendix.SSL User Configuration.WebHome]] and manually add the IP Table entries on the GWEXER
39 39  )))
40 40  
41 -(% class="row" %)
152 +(% class="box infomessage" id="HCaution:" %)
42 42  (((
43 -== Option 1: Manual RF Gateway Claiming: ==
154 +**Note:** ShowRunnerCLC™ has two different approaches for Zūm Wireless Discovery
44 44  
45 -Use this method if you have multiple ShowRunner instances on the same network or have gateways used by other Crestron systems.
156 +1. **Manual RF Gateway Assignment** - ShowRunnerCLC™ can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
157 +1. **Claim All RF Gateways** - ShowRunnerCLC™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different ShowRunnerCLC™ or other Crestron systems on the same local network.
158 +)))
46 46  
160 +== Manual RF Gateway Assignment Instructions ==
161 +
162 +Use this method if you have multiple ShowRunnerCLC™ instances on the same network or have gateways used by other Crestron systems.
163 +
47 47  * Connect to the processor's console with Toolbox or your favorite SSH client.
48 -* Type "//sr devmgr ethernet query//" and press enter. This queries the local network for RF Gateways.
49 -* Type "//sr devmgr ethernet show devices//" and press enter. This displays all found Crestron ethernet devices.
50 -* For each gateway that you'd like this instance of ShowRunner to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type "//sr ethernet device claim CEN-GWEXER-9E6ADA//". ShowRunner will auto-assign an IP-ID. After all gateways have been claimed by ShowRunner proceed to the next step.
51 -* Type "//sr discover zum false//" and press enter.
52 -* Status messages and the results will be displayed on the console. The process should take about 3 minutes.
53 -* When the discovery is finished type "//sr save//" and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunner must be restarted to complete the acquire process.
54 -* Type "//progreset//" and press enter to restart ShowRunner
55 -* Once ShowRunner has finished restarting type "//sr discover zum false//" and press enter. ShowRunner will be able to acquire the loads attached to the Zum rooms at this point.
56 -* Once completed ShowRunner is now ready for full Zum control
165 +* Type ##sr devmgr ethernet query## and press enter. This queries the local network for RF Gateways.
166 +* Type ##sr devmgr ethernet show devices## and press enter. This displays all found Crestron ethernet devices.
167 +* For each gateway that you'd like this instance of SHOWRUNNER™ to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type ##sr ethernet device claim CEN-GWEXER-9E6ADA##. ShowRunnerCLC™ will auto-assign an IP-ID. After all gateways have been claimed by ShowRunnerCLC™, proceed to the next step.
168 +* Type ##sr discover zummesh false## and press enter.
169 +* Status messages and the results will be displayed on the console. The process should take about 3 minutes.
170 +* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunnerCLC™ must be restarted to complete the acquire process.
171 +* Type ##progreset## and press enter to restart ShowRunnerCLC™
172 +* Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. ShowRunnerCLC™ will be able to acquire the loads attached to the Zūm rooms at this point.
173 +* Once completed SHOWRUNNER™ is now ready for full Zūm control
57 57  
58 -== Option 2: Claim All Gateways: ==
175 +== Claim All RF Gateways Instructions ==
59 59  
60 -Use this method when you have a single ShowRunner instance on a local network with all gateways being used for ShowRunner.
177 +Use this method when you have a single ShowRunnerCLC™ instance on a local network with all gateways being used for ShowRunnerCLC™.
61 61  
62 62  * Connect to the processor's console with Toolbox or your favorite SSH client.
63 -* Type "//sr discover zum true//" and press enter.
64 -* Status messages and the results will be displayed on the console. The process should take about 3 minutes.
65 -* When the discovery is finished type "//sr save//" and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunner must be restarted to complete the acquire process.
66 -* Type "//progreset//" and press enter to restart ShowRunner
67 -* Once ShowRunner has finished restarting type "//sr discover zum false//" and press enter. ShowRunner will be able to acquire the loads attached to the Zum rooms at this point.
68 -* Once completed ShowRunner is now ready for full Zum control
180 +* Type ##sr discover zummesh true## and press enter. ShowRunnerCLC™ will auto-assign an IP-ID. After all gateways have been claimed by ShowRunnerCLC™, proceed to the next step.
181 +* Type ##sr discover zummesh false## and press enter.
182 +* Status messages and the results will be displayed on the console. The process should take about 3 minutes.
183 +* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunnerCLC™ must be restarted to complete the acquire process.
184 +* Type ##progreset## and press enter to restart ShowRunnerCLC™
185 +* Once ShowRunnerCLC™ has finished restarting type ##sr discover zummesh false## and press enter. ShowRunnerCLC™ will be able to acquire the loads attached to the Zūm rooms at this point.
186 +* Once completed ShowRunnerCLC™ is now ready for full Zūm control
69 69  
70 70  == Examples ==
71 71  
190 +=== Manual Example ===
72 72  
73 -=== Example for Option 1: ===
74 -
75 75  {{{MC4>sr devmgr ethernet query
76 76  Ethrenet AutoDiscovery Result: AutoDiscoveryOperationSuccess
77 77  MC4>sr devmgr ethernet show devices
... ... @@ -89,7 +89,7 @@
89 89  MC4>sr ethernet device claim CEN-GWEXER-9E6ADA
90 90  Claimed ethernet device: CEN-GWEXER-9E6ADA
91 91  MC4>Update request from IP-ID-30 in Program 01
92 -MC4>sr discover zum false
209 +MC4>sr discover zummesh false
93 93  Starting Zum Discovery without gateway claiming
94 94  MC4>Performing Discovery on 1 Gateways.
95 95  Evaluating 3 Devices on Gateway 30
... ... @@ -122,7 +122,7 @@
122 122  MC4>progreset
123 123  ...
124 124  CI ShowRunner startup completed successfully in 8072ms
125 -MC4>sr discover zum false
242 +MC4>sr discover zummesh false
126 126  Starting Zum Discovery without gateway claiming
127 127  MC4>Notice: SimplSharpPro[App01] # 2020-07-21 22:19:46 # Recalling startup scenes (if applicable)
128 128  Performing Discovery on 1 Gateways.
... ... @@ -173,9 +173,9 @@
173 173  Removed Loads: 0
174 174  Zum Discovery Finished}}}
175 175  
176 -=== Example for Option 2: ===
293 +=== Claim All Example ===
177 177  
178 -{{{MC4>sr discover zum true
295 +{{{MC4>sr discover zummesh true
179 179  Starting Zum Discovery with gateway claiming
180 180  MC4>Found 1 Gateways to check.
181 181  Claimed Gateway SN: 1720JBH04269 at IP-ID: 30
... ... @@ -211,7 +211,7 @@
211 211  MC4>progreset
212 212  ...
213 213  CI ShowRunner startup completed successfully in 8072ms
214 -MC4>sr discover zum false
331 +MC4>sr discover zummesh false
215 215  Starting Zum Discovery without gateway claiming
216 216  MC4>Notice: SimplSharpPro[App01] # 2020-07-21 22:19:46 # Recalling startup scenes (if applicable)
217 217  Performing Discovery on 1 Gateways.
... ... @@ -262,4 +262,3 @@
262 262  Removed Loads: 0
263 263  Zum Discovery Finished
264 264  }}}